Thermal control for battery racks and containerised storage
A battery container fails quietly: the cells drift a few degrees apart, the spread grows over months, and the capacity warranty is spent before anyone notices. Temperature control here is about evenness, not about a set point.
The four parts of a rack control loop
1 · Sense
Pt100 RTD probes on the rack inlet, the outlet and two cells per module. The spread between them is the number that matters, not the absolute value.
SE-TC-WRNK2362 · Control
A controller per container with heating and cooling outputs, or one per rack where the enclosure is zoned. Set point plus a narrow dead band.
SE-TC53 · Switch
SSR switching for the heater bank; the compressor or chiller is switched by a contactor, because it is a motor load, not a resistive one.
SE-SSR-DA4 · Protect and drive
Phase-failure and voltage relays on the chiller supply, and a VFD where the circulation pump or fan runs continuously at part load.
SE-XJ3-DWhat to order, by installation
| Installation | Sensing | Control | Switching |
|---|---|---|---|
| Cabinet BESS, 100–300 kWh | 4 × Pt100 RTD probes | TC5 with heat/cool outputs | SSR-DA 25 A + CJX2 contactor |
| Containerised BESS, 1–5 MWh | Pt100 RTD probes per rack, 12–24 points | TC5 per zone + alarm relay | SSR bank + CJX2 for the chiller |
| PCS / inverter cabinet | 2 × Pt100 RTD, inlet and outlet | TC5 + fan speed control | Contactor + VFD on the fan |
The alarm matters more than the set point: a rack that reports a 6 °C spread a month before it fails is worth more than a controller that holds 25.0 °C and says nothing.
What goes wrong on site
- One rack runs 5 °C hotter than its neighbours
- Airflow, not control. Check for a blocked baffle, a failed fan or a rack that has been re-stacked since commissioning.
- The heater bank cycles hard and the SSR runs hot
- Heater load above the SSR rating, or a heat sink in still air inside a sealed cabinet. Derate by 30 % and mount the sink in the airflow.
- The chiller trips on phase loss twice a month
- Supply quality at the site. Fit the XJ3-D on the chiller feed and log it — the trips are the symptom, the supply is the cause.
- Cell temperatures swing with the ambient day curve
- The dead band is too wide or the circulation fan is off at low load. Keep the fan running and narrow the band to ±1 °C.