A battery container fails quietly: the cells drift a few degrees apart, the spread grows over months, and the capacity warranty is spent before anyone notices. Temperature control here is about evenness, not about a set point.

The four parts of a rack control loop

1 · Sense

Pt100 RTD probes on the rack inlet, the outlet and two cells per module. The spread between them is the number that matters, not the absolute value.

SE-TC-WRNK236

2 · Control

A controller per container with heating and cooling outputs, or one per rack where the enclosure is zoned. Set point plus a narrow dead band.

SE-TC5

3 · Switch

SSR switching for the heater bank; the compressor or chiller is switched by a contactor, because it is a motor load, not a resistive one.

SE-SSR-DA

4 · Protect and drive

Phase-failure and voltage relays on the chiller supply, and a VFD where the circulation pump or fan runs continuously at part load.

SE-XJ3-D

What to order, by installation

InstallationSensingControlSwitching
Cabinet BESS, 100–300 kWh4 × Pt100 RTD probesTC5 with heat/cool outputsSSR-DA 25 A + CJX2 contactor
Containerised BESS, 1–5 MWhPt100 RTD probes per rack, 12–24 pointsTC5 per zone + alarm relaySSR bank + CJX2 for the chiller
PCS / inverter cabinet2 × Pt100 RTD, inlet and outletTC5 + fan speed controlContactor + VFD on the fan

The alarm matters more than the set point: a rack that reports a 6 °C spread a month before it fails is worth more than a controller that holds 25.0 °C and says nothing.

What goes wrong on site

One rack runs 5 °C hotter than its neighbours
Airflow, not control. Check for a blocked baffle, a failed fan or a rack that has been re-stacked since commissioning.
The heater bank cycles hard and the SSR runs hot
Heater load above the SSR rating, or a heat sink in still air inside a sealed cabinet. Derate by 30 % and mount the sink in the airflow.
The chiller trips on phase loss twice a month
Supply quality at the site. Fit the XJ3-D on the chiller feed and log it — the trips are the symptom, the supply is the cause.
Cell temperatures swing with the ambient day curve
The dead band is too wide or the circulation fan is off at low load. Keep the fan running and narrow the band to ±1 °C.