Industry · heat treatment
Temperature control for furnaces, kilns and dryers
One zone or twelve: the sensor, the controller, the switching element and the isolation are chosen together, because a furnace that trips at temperature costs more than the parts.
How one zone is built
1 · Measure
A thermocouple or Pt100 in each zone. Type K covers most furnaces; use sheathed probes where the atmosphere or the wiring route is hostile.
SE-TC-WRNK2362 · Control
A PID controller with relay, SSR drive or 4–20 mA output, one per zone. The TC4 covers the three output types in one part number.
SE-TC43 · Switch
Below roughly 3 kW an SSR with its heat sink is enough; above that, or on three-phase, a thyristor unit switches the whole zone with phase-angle or zero-cross control.
SE-SSR-DA / SE-BDTY4 · Protect
A contactor isolates the heating circuit, and a thermal overload or phase-failure relay stops the load when a fan or an element fails.
SE-CJX2The set to order, by furnace size
| Furnace size | Sensor | Controller | Switching | Isolation |
|---|---|---|---|---|
| Up to 3 kW, single phase | K-type probe, 3 mm sheath | TC4, SSR drive output | SSR-DA 25 A + HS-SSR heat sink | CJX2-0910 contactor |
| 3–9 kW, single phase | K-type probe, 6 mm sheath | TC4, 4–20 mA output | BDTY single-phase SCR unit | CJX2-1810 + thermal overload |
| 9–30 kW, three phase | 3 × K-type probes, one per zone | TC4 or TC5, three units | BSTY three-phase SCR unit | CJX2-3210 + phase-failure relay |
Sizes are a starting point, not a rule: inductive loads, a frequent on/off cycle or an ambient above 40 °C all push the switching element up one size. Send the element wattage and the number of zones and we size it on the quote.
Choosing between an SSR and a thyristor unit
Solid state relay
- • Best on single-zone loads up to about 3 kW, and where the controller already has an SSR drive output.
- • Zero-cross switching keeps electrical noise low, which matters on the same supply as instruments.
- • Needs a heat sink sized for the current: 25 A of load is roughly 1.2 V × 25 A of heat to remove.
Thyristor unit (SCR)
- • For three-phase furnaces, larger elements, and loads where the current must be limited softly.
- • Phase-angle control avoids the thermal cycling of on/off switching on elements with a long heat-up.
- • Fed from a 4–20 mA or 0–10 V signal, so the same controller family drives either option.
What goes wrong, and what it usually is
- The reading climbs slowly and overshoots on start-up
- Autotune with the furnace loaded. An empty chamber tunes to a much smaller thermal mass and hunts for hours once the load goes in.
- One zone reads open circuit
- Check the thermocouple before the controller: a broken sheath or a corroded terminal reads as an open input. Swap the probe between zones; if the fault follows the probe, the probe is the problem.
- The element is on when the controller says off
- A shorted SSR fails closed. Pull the controller signal and measure the load side — voltage with no drive means the SSR has to be replaced, and the heat sink should be checked for a dried thermal pad.
- The heating trips the breaker at switch-on
- Cold elements draw well above rated current. Either the SSR is switching at the wrong point in the cycle or the contactor is too small; check the inrush against the contactor rating.
Related reading
Need help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.