Industry · heat treatment

Temperature control for furnaces, kilns and dryers

One zone or twelve: the sensor, the controller, the switching element and the isolation are chosen together, because a furnace that trips at temperature costs more than the parts.

How one zone is built

1 · Measure

A thermocouple or Pt100 in each zone. Type K covers most furnaces; use sheathed probes where the atmosphere or the wiring route is hostile.

SE-TC-WRNK236

2 · Control

A PID controller with relay, SSR drive or 4–20 mA output, one per zone. The TC4 covers the three output types in one part number.

SE-TC4

3 · Switch

Below roughly 3 kW an SSR with its heat sink is enough; above that, or on three-phase, a thyristor unit switches the whole zone with phase-angle or zero-cross control.

SE-SSR-DA / SE-BDTY

4 · Protect

A contactor isolates the heating circuit, and a thermal overload or phase-failure relay stops the load when a fan or an element fails.

SE-CJX2

The set to order, by furnace size

Furnace sizeSensorControllerSwitchingIsolation
Up to 3 kW, single phaseK-type probe, 3 mm sheathTC4, SSR drive outputSSR-DA 25 A + HS-SSR heat sinkCJX2-0910 contactor
3–9 kW, single phaseK-type probe, 6 mm sheathTC4, 4–20 mA outputBDTY single-phase SCR unitCJX2-1810 + thermal overload
9–30 kW, three phase3 × K-type probes, one per zoneTC4 or TC5, three unitsBSTY three-phase SCR unitCJX2-3210 + phase-failure relay

Sizes are a starting point, not a rule: inductive loads, a frequent on/off cycle or an ambient above 40 °C all push the switching element up one size. Send the element wattage and the number of zones and we size it on the quote.

Choosing between an SSR and a thyristor unit

Solid state relay

  • • Best on single-zone loads up to about 3 kW, and where the controller already has an SSR drive output.
  • • Zero-cross switching keeps electrical noise low, which matters on the same supply as instruments.
  • • Needs a heat sink sized for the current: 25 A of load is roughly 1.2 V × 25 A of heat to remove.

Thyristor unit (SCR)

  • • For three-phase furnaces, larger elements, and loads where the current must be limited softly.
  • • Phase-angle control avoids the thermal cycling of on/off switching on elements with a long heat-up.
  • • Fed from a 4–20 mA or 0–10 V signal, so the same controller family drives either option.

What goes wrong, and what it usually is

The reading climbs slowly and overshoots on start-up
Autotune with the furnace loaded. An empty chamber tunes to a much smaller thermal mass and hunts for hours once the load goes in.
One zone reads open circuit
Check the thermocouple before the controller: a broken sheath or a corroded terminal reads as an open input. Swap the probe between zones; if the fault follows the probe, the probe is the problem.
The element is on when the controller says off
A shorted SSR fails closed. Pull the controller signal and measure the load side — voltage with no drive means the SSR has to be replaced, and the heat sink should be checked for a dried thermal pad.
The heating trips the breaker at switch-on
Cold elements draw well above rated current. Either the SSR is switching at the wrong point in the cycle or the contactor is too small; check the inrush against the contactor rating.

Related reading

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.