Industry · water

Level, pressure and motor control for water treatment and pump stations

A pump station is a chain of small decisions: when to start the pump, how to keep the pressure steady, what to do when the phase order is wrong, and how to know the tank is dry. Four parts, one panel.

The four decisions in a pump panel

1 · Level

Floatless level relays with stainless probes for tanks and sumps, so there is no float to jam on sludge. Two or three probes give low, high and common.

SE-61F

2 · Drive

A VFD holds constant pressure from a pressure transmitter instead of cycling a contactor. On a small station it also removes the water hammer at start.

SE-VFD-H350

3 · Protect

Phase-failure and voltage relays drop the contactor on loss of phase, phase order reversal or a voltage window breach — the pump never runs backwards.

SE-XJ3

4 · Time

A cycle timer alternates duty and standby pumps, so both wear evenly and one is always available.

SE-H3Y-2

What to order, by station

StationLevel controlPumpingProtection
Single pump, tank fill61F floatless relay + 3 probesCJX2 contactor, DOLXJ3 phase-failure relay
Duty / standby pair61F + H3Y-2 alternation2 × CJX2 contactorsXJ3 + thermal overload
Constant pressure boosterPressure transmitter to VFDH350 VFD, 2.2–7.5 kWXJ3 + dry-run relay

The dry-run protection is the part that saves the pump: a level probe in the suction tank wired to stop the drive costs less than one impeller.

What goes wrong on site

The pump runs backwards after a supply repair
Phase order reversed at the incoming terminals. The XJ3 detects it and holds the contactor out; check the order before overriding it.
Pressure hunts between two set points
A contactor-based booster always does this. Move to a VFD with a pressure transmitter, or widen the differential and accept the swing.
The tank overflows at night
A float switch that sticks. Floatless probes with a high-level relay are the fix, and they also give a low-level signal for the same cost.
The pump trips on overload once a week
Usually a worn impeller or a partially closed valve, not the relay. Log the running current before changing the thermal setting.

Related reading

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.