Control and protection for HVAC plant and cold rooms

Cooling equipment runs unattended for years, which changes what matters: the controller has to hold a defrost cycle, the compressor has to survive a lost phase, and the panel has to be readable in a plant room.

The four parts of an HVAC control panel

1 · Temperature

A controller with a heating and a cooling output, or one per stage on a larger plant. NTC or Pt100 probes for room and duct, with a waterproof version for cold rooms.

SE-NTC-PROBE

2 · Defrost

A cycle timer runs the defrost on a schedule and terminates it on temperature, which is what keeps the coil clear without heating the room.

SE-DH48S-S

3 · Motor protection

Phase-failure and voltage relays protect the compressor; a thermal overload covers the fan motor. Both drop the contactor rather than the control circuit.

SE-XJ3

4 · Drive

Fan and pump VFDs for part-load running, which is where most of the energy saving in an HVAC plant actually comes from.

SE-VFD-H350

What to order, by plant

PlantControlTimingProtection
Cold room, single stageTC4 + Pt100 probeDH48S-S defrost timerXJ3 + thermal overload
AHU with heating and coolingTC5 + 2 probes, duct and roomH3Y-2 fan delayXJ3 phase-failure relay
Chiller plant, fan and pumpTC5 per loopH3CR-A pump delayH350 VFD on fans and pumps

In a plant room the display matters as much as the accuracy: the TC5 white LED is readable from two metres away, which is the distance an operator actually stands at.

What goes wrong on site

Cold room ices up over a weekend
Defrost termination probe failed open, so the timer runs to its maximum every cycle. Check the termination probe before the timer.
Compressor trips on phase loss but the panel looks normal
The phase relay has dropped the contactor and the control circuit is still live, which is correct. Fit an indicator so the cause is visible.
Room temperature swings 3 °C around set point
Either the differential is too tight for the compressor, or the probe is in the return air path. Widen the differential first.
Fan VFD trips at low ambient
Condensing fans over-speed in cold weather. Set a minimum frequency, or fit a pressure-based control instead of a temperature one.