A generating set is judged by two numbers nobody can argue with: how many hours it has run, and whether it started when the mains failed. Both are panel parts, not engine parts.
The four parts of a genset panel
1 · Hours
A sealed hour meter on the engine: the service interval and the rental billing both come from this one figure, so it has to survive vibration and heat.
SE-H7ET2 · Protection
A phase-failure and voltage relay on the alternator output drops the load on over- or under-voltage and on phase loss before the AVR is damaged.
SE-XJ3-D3 · Switching
A contactor or changeover between mains and generator; on marine sets the same contactor carries the shore supply.
SE-CJX24 · Starting
A time relay holds the start signal, the warm-up and the transfer delay, so the set is loaded only when it is at speed.
SE-H3Y-2What to order, by set
| Set | Metering | Protection | Switching | Timing |
|---|---|---|---|---|
| Portable / rental set, 10–60 kVA | H7ET hour meter | XJ3-D voltage protector | CJX2 contactor | |
| Standby set with ATS, 100–400 kVA | H7ET + LY-11J counter for starts | XJ3-D + thermal overload | 2 × CJX2, mains and generator | |
| Marine auxiliary set | H7ET hour meter, sealed | XJ3-D + insulation monitor | CJX2 + shore/generator changeover |
The service interval is the reason the hour meter matters commercially: a set sold on a 500-hour service promise needs a meter the customer trusts, and a sealed one cannot be reset.
What goes wrong on site
- The set runs but the hour meter stands still
- Usually the meter is wired to the control circuit rather than the alternator output, so it stops when the panel is switched off. Move the feed to the running signal.
- The ATS transfers but the load trips
- Transfer happens before the set is at speed. Add the warm-up delay on the H3Y-2 and check the transfer relay sequence.
- The voltage protector trips on every start
- A large set dips the bus on start-up. Widen the voltage window, or delay the relay by two seconds so it ignores the dip.
- Marine set shows an earth fault with no obvious damage
- Salt and condensation. Check the insulation monitor and the heater in the panel before chasing the alternator.