Variable Frequency Drives
H350 Series Variable Frequency Drive (VFD)
Variable frequency drives from 0.4kW to 15kW with V/F control with multi-step speed, analogue 0–10V and 4–20mA reference, in single-phase 220V and three-phase 380V input versions.

- Output
- three-phase 220VAC or 380VAC, matched to the input configuration
- Input
- single-phase 220VAC, 50/60Hz
- Power range
- 0.4kW to 15kW
- Input (380V builds)
- three-phase 380VAC, 50/60Hz
Technical specifications
| Product | Variable frequency drive for three-phase motor speed control |
|---|---|
| Power range | 0.4kW to 15kW |
| Input | single-phase 220VAC, 50/60Hz |
| Input (380V builds) | three-phase 380VAC, 50/60Hz |
| Output | three-phase 220VAC or 380VAC, matched to the input configuration |
| Control | V/F control with multi-step speed, analogue 0–10V and 4–20mA reference |
| Protection | over-current, over-voltage, under-voltage, over-heat and short circuit |
| Cooling | fan-cooled, panel or wall mounting |
| Applications | Fans, pumps, conveyors, mixers and machine tool spindles |
| 350 0.4 kW | 0.4 kW, single phase 220–240 V · 2.1 A · 1.0 kg |
| 350 0.75 kW | 0.75 kW, single phase 220–240 V · 4 A · 1.0 kg |
| 350 1.5 kW | 1.5 kW, single phase 220–240 V · 7 A · 1.1 kg |
| 350 2.2 kW | 2.2 kW, single phase 220–240 V · 9.5 A · 1.1 kg |
| 350 3.0 kW | 3.0 kW, single phase 220–240 V · 11 A · 1.15 kg |
| 350 0.75 kW 380 | 0.75 kW, three phase 380–440 V · 2.5 A · 1.0 kg |
| 350 1.5 kW 380 | 1.5 kW, three phase 380–440 V · 4.1 A · 1.1 kg |
| 350 2.2 kW 380 | 2.2 kW, three phase 380–440 V · 5.8 A · 1.15 kg |
| 350 3.0 kW 380 | 3.0 kW, three phase 380–440 V · 7.9 A · 1.2 kg |
| 350 4.0 kW | 4.0 kW, three phase 220–240 V · 9.4 A · 2.3 kg |
| 350 5.5 kW | 5.5 kW, three phase 220–240 V · 12.6 A · 2.35 kg |
| 350 7.5 kW | 7.5 kW, three phase 220–240 V · 16.1 A · 2.35 kg |
Product overview
Part no. SE-VFD-H350industry model VFD-H350
Also known as: H350 VFD · H350 frequency inverter · H350 variador de frecuencia
The H350 series takes a fixed supply and gives a three-phase motor a variable one, so speed follows the process instead of the mains. Three input configurations cover the usual panel arrangements: single-phase 220V to three-phase 220V, three-phase 380V to three-phase 380V, and single-phase 220V to three-phase 380V. Power runs from 0.4kW to 15kW.
Key features
- Power range from 0.4kW to 15kW
- Single-phase 220V input, three-phase 220V output
- Three-phase 380V input, three-phase 380V output
- Single-phase 220V input stepped up to three-phase 380V
- Analogue 0–10V and 4–20mA speed reference
- Multi-step speed and panel keypad control
- Over-current, over-voltage, over-heat and short-circuit protection
- Fan-cooled, panel or wall mounting
Works with
The parts that go into the same panel and are usually ordered with it.
Line-side AC contactor
SE-CJX2
Provides mains-side isolation upstream of the VFD (never switch a contactor on the VFD output)
Rotary encoder
SE-SEP
Speed and position feedback for vector drives and closed-loop motor control
Voltage & phase relays
Monitors incoming mains phase sequence and under/over-voltage ahead of the drive
Panel and keys
Five controls on the faceplate: value up and value down, the set key, the start and stop keys, and the speed knob in the middle. The display is four digits above the digital operator marking.

Dimensions, weights and output current
The cabinet is sized from three of these columns: the overall size for the space, the packing size for the shipping carton, and the gross weight for the freight quote. Output current is what the motor actually sees.

Single-phase 220V in, three-phase 220V out
| Version | Output current | Overall (mm) | Packing (mm) | Net | Gross |
|---|---|---|---|---|---|
| H350-0D4-S2G | 2.1A | 150 × 115 × 130 | 173 × 135 × 172 | 1.0kg | 1.2kg |
| H350-0D75-S2G | 4A | 150 × 115 × 130 | 173 × 135 × 172 | 1.1kg | 1.3kg |
| H350-1D5-S2G | 7A | 150 × 115 × 150 | 173 × 135 × 172 | 1.1kg | 1.3kg |
| H350-2D2-S2G | 9.5A | 150 × 115 × 150 | 173 × 135 × 172 | 1.1kg | 1.3kg |
| H350-3D0-S2G | 11A | 150 × 115 × 150 | 173 × 135 × 172 | 1.15kg | 1.35kg |
Three-phase 380V in, three-phase 380V out
| Version | Output current | Overall (mm) | Packing (mm) | Net | Gross |
|---|---|---|---|---|---|
| H350-0D75-T4G | 2.5A | 150 × 115 × 130 | 173 × 135 × 172 | 1.1kg | 1.3kg |
| H350-1D5-T4G | 4.1A | 150 × 115 × 150 | 173 × 135 × 172 | 1.1kg | 1.3kg |
| H350-2D2-T4G | 5.8A | 150 × 115 × 150 | 173 × 135 × 172 | 1.15kg | 1.35kg |
| H350-3D0-T4G | 7.9A | 150 × 115 × 150 | 173 × 135 × 172 | 1.2kg | 1.4kg |
| H350-3D7-T4G | 9.4A | 210 × 118 × 180 | 265 × 175 × 232 | 2.3kg | 2.55kg |
| H350-5D5-T4G | 12.6A | 210 × 118 × 180 | 265 × 175 × 232 | 2.35kg | 2.6kg |
| H350-7D5-T4G | 16.1A | 210 × 118 × 180 | 265 × 175 × 232 | 2.35kg | 2.6kg |
Terminals and what each one does
Two blocks, and the split matters: R, S, T take the supply and U, V, W drive the motor, so the two must never be swapped. Everything on the lower strip is control-level, referenced to COM for the digital inputs and to GND for the analogue ones.

Main circuit
| Terminal | Function | Note |
|---|---|---|
| R · S · T | Supply input | 380V versions use all three; 220V versions use R and S or R and T, as the terminal label shows. |
| U · V · W | Motor output | Keep the cable under 50m to hold leakage current down. Never put a contactor or a capacitor on this side. |
| P · B | Braking resistor | Across P and B, to the value in the table below. |
| PE | Earth | Must be connected; the drive is not isolated from the supply. |
Control circuit
| Terminal | Function | Note |
|---|---|---|
| COM | Digital common | Zero potential for S1 to S5. |
| S1 | Digital input 1 | Factory set to forward run (F2.13). |
| S2 | Digital input 2 | Factory set to reverse (F2.14). |
| S3 | Digital input 3 | Factory set to multi-speed step 1 (F2.15). |
| S4 | Digital input 4 | Factory set to multi-speed step 2 (F2.16). |
| S5 | Digital input 5 | Factory set to external reset (F2.17). |
| GND | Analogue common | Zero potential for AVI and ACI. |
| AVI | 0–10V input | Speed reference, input resistance above 50kΩ. |
| 10V | Reference supply | +10V for a potentiometer, 10mA maximum. |
| ACI | 4–20mA input | Speed reference, 100Ω input resistance. |
| A0 | Analogue output | What it reports is set by F2.10. |
| RA · RB · RC | Relay output | Contact rating AC 250V/3A, DC 24V/2A; function set by F2.20. |
Braking resistor
Where the load has to stop quickly or is overhauled, a resistor goes across P and B. The value is set by the drive, not chosen freely: too low draws too much current through the brake switch, too high does nothing.
| Version | Resistor power | Resistance |
|---|---|---|
| 0.75kW 220V | 100W | 200Ω |
| 1.5kW 220V | 300W | 100Ω |
| 2.2kW 220V | 300W | 100Ω |
| 3.0kW 220V | 500W | 100Ω |
| 4.0kW 220V | 500W | 75Ω |
| 5.5kW 220V | 1000W | 75Ω |
| 0.75kW 380V | 100W | 750Ω |
| 1.5kW 380V | 300W | 400Ω |
| 2.2kW 380V | 300W | 250Ω |
| 3.0kW 380V | 300W | 250Ω |
| 4.0kW 380V | 500W | 150Ω |
| 5.5kW 380V | 800W | 100Ω |
| 7.5kW 380V | 1000W | 75Ω |
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
Related models
All Variable Frequency Drives
H710 Series Full Vector Variable Frequency Drive
SE-VFD-H710
The H710 is the full-vector member of the range: it closes the loop on motor speed rather than holding a voltage-to-frequency ratio open, so torque…
View details
320 Series Universal Inverter
SE-VFD-320
The 320 takes the 360 and hardens it: the same compact format, with the hardware upgraded where the 360 was pressed hardest. For the machine builders…
View details
720 Series High-Performance Inverter
SE-VFD-720
The 720 is the 710 reworked: the same current vector control, with the software algorithm and the hardware selection revisited. It runs from the…
View details
800 Series Inverter for Single-Phase Capacitor Motors
SE-VFD-800
The drive for the motors that were never meant to be driven: a single-phase capacitor motor connects straight to the two-phase output, with the…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.