Technical Guides · 2026-11-23

How Time Relay Modes Work: On-Delay, Off-Delay, Star-Delta and Cycle

Most timer problems are mode problems, not failures. This guide explains what starts and resets each of the four common timing modes, compares the ST3P, DH48S, H3Y and AH3 families by mode and contact rating, and gives a wiring and setting sequence that catches the usual mistakes.

A timer relay makes an action happen at the right moment after something else. Yet many "faulty" timers are correctly wired units set to the wrong mode: the coil energizes, nothing happens, and the unit comes back as dead — when in fact it is an on-delay unit waiting for a signal that never dropped, or a cycle unit doing exactly what it was told.

The four modes that matter on a factory panel — on-delay, off-delay, cycle (repeating) and star-delta changeover — differ by two things only: what starts the timing period, and what the contacts do during and after it. Answer those two questions and the model code becomes a straightforward choice. This guide explains each mode, places the ST3P, DH48S, H3Y and AH3 families, and gives a wiring sequence that catches common errors before they reach a machine.

Important: All wiring must be carried out by a qualified electrician with the supply isolated, locked off and verified dead. The relay markings and the diagram supplied with the exact model take priority over this guide. A timer is a control device, not a safety device: where a function must stop hazardous motion, use a hard-wired interlock or a certified safety relay, not a timer contact alone.

What starts the clock: the only two questions that matter

Every timer mode is described by two questions. First, what starts the timing period — applying power to the coil, removing it, or an external trigger? Second, what does the output contact do during the period and after it? Nearly every field complaint comes from assuming the first answer when the unit on the shelf answers it differently.

Hold those two questions in mind and the model codes stop looking arbitrary. An on-delay unit starts timing when the coil is energized and changes contact only after the set time. An off-delay unit changes when the coil is released and holds that state for the set time before returning. A cycle unit repeats a timed on/off period while power is applied. Everything else — knob, display, contact count — is detail.

On-delay: power up, then act

On-delay is the default mode in most panels. The coil energizes, the indicator runs, and the delayed contact stays at rest until the set time elapses. Then the changeover contact moves: normally open closes, normally closed opens. Remove coil power and the contact returns immediately.

The ST3PA is a typical on-delay unit with changeover contacts, a 0.05 s to 24 h setting range in steps A–G, and an AC 250 V, 3 A resistive contact rating. The AH3-1, AH3-2 and AH3-3 are also on-delay: AH3-1 single-pole changeover, AH3-2 double-pole, and AH3-3 adds one instantaneous changeover beside the delayed one. If an immediate contact must seal a start button while the delayed contact starts a second stage, that instantaneous contact is the reason to choose AH3-3 or the ST3PC rather than a separate relay.

Because the timer starts on coil energization, the trigger must stay present. A momentary pushbutton that releases after half a second will never complete a ten-second delay — the coil drops out, the timer resets, and next time it starts from zero. Either seal the pushbutton through an auxiliary contact or use a latched signal.

Off-delay: the contact drops out late

Off-delay does the opposite. The coil energizes and the contact changes over at once; when the coil drops out, the contact holds its energized position for the set time and then returns. This is the mode for keeping a load running briefly after a stop: cooling fans after a heater shuts down, a lamp held on while a person clears a machine, or a pump clearing a line.

The ST3PF is a true off-delay unit in the ST3P family, with a single delayed changeover or a two-contact build, rated AC 250 V, 3 A and DC 28 V, 5 A. Do not substitute an on-delay relay wired through a normally closed contact. The two differ if the supply fails mid-delay: an off-delay unit holds its stored energy and completes the delay; a reconfigured on-delay unit simply resets.

The ST3PK is a signal-off variant that times from an external control signal rather than from loss of coil power. It suits sensor-triggered timing but is not a drop-out timer. The ST3PG in the same family is the interval timer: it is triggered like an on-delay unit and gives one timed period before returning. Read the working-mode row before ordering — on-delay, interval, signal-off delay and off-delay are four distinct entries, not four names for one function.

Cycle and repeating timers

A cycle timer repeats a timed output while it has power. It suits intermittent duty that must run unattended: a warning beacon, a periodic lubrication pulse, or a process alternating two states. The on and off periods may be set independently on digital units or linked in a fixed ratio on simple analog ones.

The ST3P-R is a repeating-cycle relay with one delayed contact and switch-selected range pairs: 6 s / 60 s, 10 s / 10 min, 30 s / 6 min or 60 s / 60 min. The DH48S family goes further: the DH48S-S is a cycle unit with pause and reset, the DH48S-S-2Z adds a second delayed contact, and the DH48S digital range covers 0.1 s to 99 h 59 m on the S version and 0.01 s to 99 h 99 m on other variants, with ±0.5% setting error and ±0.3% repeat accuracy.

Cycle timers are sometimes used where one delayed action would do. For a one-shot action, a cycle unit leaves the output in whatever state the supply was removed in, which can surprise on the next start. Use on-delay or off-delay for a single timed event; reserve cycle mode for duty that genuinely repeats.

Star-delta changeover timers

Star-delta starting reduces voltage across each winding during acceleration. The motor starts in star, runs for a set time, then changes to delta for full voltage. The timer holds the star contactor long enough to reach safe speed, then allows a clean changeover. The critical detail is dead time between the two contactors: they must never be energized together, or the supply is shorted through the transition.

The TRD-N is a dedicated star-delta changeover timer. It takes an AC 110, 220 or 240 V supply at 50/60 Hz, has a seconds dial for run time, and provides a fixed 0.1 s change interval between star and delta. Its contacts are rated 250 V AC, 5 A resistive and switch the contactor coils, not the motor current. A general on-delay timer can serve in some panels, but lacks the built-in change interval and changeover logic.

Set the dial from the motor's acceleration time under load, then measure the current at changeover. A motor that has not reached speed when delta is applied will draw a current spike close to the locked-rotor value; a motor left in star too long will overheat. If the transition is rough, increase the dead time before blaming the timer.

Mode comparison at a glance

Use this table as a first filter. It describes behaviour, not a specific order code; check the family table below and the data sheet before buying.

Four timer modes on the same start signal signal on signal off time On-delay contact moves after the set time start output contact t Off-delay contact moves at once, releases late start output contact t Cyclic repeats while the coil is held coil output contact t on / t off Star-delta the two contactors are never closed together start star delta 0.1 s energised released set time t
The same start and stop signal through four modes. On-delay waits out the set time before the contact moves; off-delay moves it at once and releases it late; cycle repeats while the coil is held; star-delta separates the star and delta contactors by the fixed 0.1 s change interval so they never close together.
ModeWhat starts timingContact during delayContact after delayTypical use
On-delayCoil energizedResting positionChanges over and holds while coil is energizedSequenced start, time-based stages
Off-delayCoil de-energizedChanged over immediatelyReturns after the set timeFan run-on, delayed drop-out
Signal-off delayExternal signal releasedFollows the signalReturns after the set timeSensor-triggered hold
Cycle / repeatingSupply appliedAlternates on and offRepeats until supply is removedBeacons, periodic pulses
Star-delta changeoverSupply appliedStar contactor heldSwitches to delta after a dead timeReduced-voltage motor starting

Matching the mode to the product family

The figures below come from the Strong Electric canonical product data. They show where each family sits; use the exact model suffix to confirm contacts, supply voltage and socket before ordering.

Family / exampleMode availableContactsContact ratingSetting range
ST3PAOn-delayChangeover, as the mode requiresAC 250 V, 3 A resistive0.05 s to 24 h, ranges A–G
ST3PFOff-delaySingle delayed changeover or two-contact buildAC 250 V, 3 A; DC 28 V, 5 ASee model data
ST3P-RCycle, repeatingOne delayed contactAC 250 V, 3 A resistive6 s/60 s to 60 s/60 min pairs
DH48S digitalSingle delay, two group, cycle, instantaneous + delayOne or two delayed contactsAC 250 V, 3 A resistive0.01 s to 99 h
H3Y-2On-delay, two delayed contactsTwo delayed contactsAC 250 V, 3 A resistive1 s to 60 min steps
AH3-1 / -2 / -3On-delaySPDT, DPDT, or SPDT plus instantaneous5 A at AC 250 V; 5 A at DC 28 V1 s to 60 min steps
TRD-NStar-delta changeoverContacts for contactor coils250 V AC, 5 A resistiveDial in seconds, 0.1 s change

Note the accuracy difference. Analog knob units quote a ±10% setting error on H3Y and AH3 ranges and around ±0.5% on ST3P and DH48S, with repeat accuracy near ±0.3%. Where a process needs repeatable timing to a few percent, prefer a digital unit and verify with a stopwatch rather than trust the dial.

Wiring and setting sequence

The sequence below assumes a timer switching one or more contactor coils, which is the normal arrangement. Timer contacts are not intended to carry motor or heater current directly.

  1. Confirm the supply on the relay label. The ST3P and H3Y families are offered across AC 12–380 V and DC 12–24 V; the AH3-1 range lists 110, 220 or 380 VAC and 12 or 24 VAC/DC. The wrong coil voltage is the most common cause of a timer that never powers up.
  2. Confirm the mode row in the data table. On-delay, off-delay and signal-off delay are separate variants even when the front label shows only a family name.
  3. Fit the matching socket. ST3P and AH3 units use PF083A, PF085A or US-08 sockets; the H3Y-2 uses PYF08A or PY08. Check the pin count before ordering a spare.
  4. Wire the coil supply through a fused, switched feed. Where the timer output seals its own supply, include a stop contact in series so the circuit can be broken.
  5. Wire the delayed contact in series with the contactor coil, not in the motor or heater circuit. Check the coil holding current and inrush against the contact rating — AC 250 V, 3 A resistive on ST3P and H3Y, 5 A on AH3 and TRD-N.
  6. For a star-delta start, wire the star and delta contactor coils through the appropriate timer contacts and add a mechanical or electrical interlock between the two contactors. The 0.1 s change in the TRD-N is not a substitute for an interlock.
  7. Set the time with the supply off. On digital units enter the value on the front panel; on knob units choose the range switch first and then the dial.
  8. Power up with the load disconnected or mechanically safe. Time the changeover with a stopwatch and compare it with the set value, allowing for the quoted setting error.
  9. Reconnect the load and observe one full cycle, measuring the current at changeover on a star-delta start or checking that the coil drops out at the right moment on an off-delay.

Five mistakes that mimic a failed timer

  • Trigger shorter than the delay. A momentary start signal that disappears before the count completes resets an on-delay unit. Seal the signal or use a latching contact.
  • Wrong mode for the duty. An on-delay unit asked to hold a fan on after a stop command will never do it. Match the mode to the event that starts the timing.
  • Contact carrying the wrong load. A 3 A resistive contact derates sharply when switching an inductive coil without suppression. Fit an interposing relay or a coil suppression module where inrush is high.
  • No dead time in a star-delta changeover. If the star and delta contactor coils can overlap, the timer is the least of the problems. Wire the interlock first.
  • Reading the setting error as a fault. A ±10% setting error means a 60 s knob setting may complete somewhere near 54 to 66 s even when the unit is healthy. Verify with a stopwatch before replacing it.

Support

Choose the timer by mode first, then by contact arrangement, supply voltage and setting range. Strong Electric supplies the ST3PA on-delay, ST3PF off-delay, ST3P-R cycle, DH48S digital and TRD-N star-delta timers, plus AH3 and H3Y. For a selection check, send the supply voltage, mode, contacts, set time and load, or contact Strong Electric directly.

Questions this guide answers

My on-delay timer never changes over. Is it broken?
Usually not. An on-delay relay starts timing only while its coil stays energized. If the trigger is a brief pulse that disappears before the set time, the relay resets and starts again on the next pulse. Hold the coil energized for longer than the delay, or seal the signal through an auxiliary contact, and the contact will change over.
Can I use an on-delay relay for off-delay duty?
Only with a different wiring arrangement and an always-energized coil, and even then the behaviour on power loss is not the same. A true off-delay unit such as the ST3PF holds its contact after the trigger drops out and is the correct choice for fan run-on or delayed drop-out duty.
What is the difference between off-delay and signal-off delay?
An off-delay relay times from the moment its coil loses power. A signal-off delay unit, such as the ST3PK variant of the ST3P family, times from an external control signal instead. Both delay the return of the contact, but the event that starts the timing is different, so read the working-mode row before ordering.
How long should the star-delta changeover delay be?
Long enough for the motor to accelerate in star and for the star contactor to drop out before the delta contactor closes. The TRD-N timer gives a fixed 0.1 s change interval between the two states. Set the main dial from the motor's loaded acceleration time, then check the current at changeover rather than copying a value from a data sheet.
Can a timer relay switch a contactor coil directly?
Yes, when the coil holding and inrush currents fit inside the contact rating. ST3P and H3Y units are rated AC 250 V, 3 A resistive and the AH3 and TRD-N contacts 5 A at AC 250 V. Add an interposing relay if the coil inrush is close to the rating.
Why does my cycle timer drift over a long run?
A knob-set timer is not a clock. Repeat accuracy is around ±0.3% and setting error can reach ±0.5% of the set time on ST3P and DH48S units, and ±10% on H3Y and some AH3 ranges. A ten-minute cycle can therefore drift by seconds. Use a digital unit and re-check the setting with a stopwatch when the interval has to be repeatable.

More in Technical Guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.