Technical Guides · 2026-11-23
How Time Relay Modes Work: On-Delay, Off-Delay, Star-Delta and Cycle
Most timer problems are mode problems, not failures. This guide explains what starts and resets each of the four common timing modes, compares the ST3P, DH48S, H3Y and AH3 families by mode and contact rating, and gives a wiring and setting sequence that catches the usual mistakes.
A timer relay makes an action happen at the right moment after something else. Yet many "faulty" timers are correctly wired units set to the wrong mode: the coil energizes, nothing happens, and the unit comes back as dead — when in fact it is an on-delay unit waiting for a signal that never dropped, or a cycle unit doing exactly what it was told.
The four modes that matter on a factory panel — on-delay, off-delay, cycle (repeating) and star-delta changeover — differ by two things only: what starts the timing period, and what the contacts do during and after it. Answer those two questions and the model code becomes a straightforward choice. This guide explains each mode, places the ST3P, DH48S, H3Y and AH3 families, and gives a wiring sequence that catches common errors before they reach a machine.
Important: All wiring must be carried out by a qualified electrician with the supply isolated, locked off and verified dead. The relay markings and the diagram supplied with the exact model take priority over this guide. A timer is a control device, not a safety device: where a function must stop hazardous motion, use a hard-wired interlock or a certified safety relay, not a timer contact alone.
What starts the clock: the only two questions that matter
Every timer mode is described by two questions. First, what starts the timing period — applying power to the coil, removing it, or an external trigger? Second, what does the output contact do during the period and after it? Nearly every field complaint comes from assuming the first answer when the unit on the shelf answers it differently.
Hold those two questions in mind and the model codes stop looking arbitrary. An on-delay unit starts timing when the coil is energized and changes contact only after the set time. An off-delay unit changes when the coil is released and holds that state for the set time before returning. A cycle unit repeats a timed on/off period while power is applied. Everything else — knob, display, contact count — is detail.
On-delay: power up, then act
On-delay is the default mode in most panels. The coil energizes, the indicator runs, and the delayed contact stays at rest until the set time elapses. Then the changeover contact moves: normally open closes, normally closed opens. Remove coil power and the contact returns immediately.
The ST3PA is a typical on-delay unit with changeover contacts, a 0.05 s to 24 h setting range in steps A–G, and an AC 250 V, 3 A resistive contact rating. The AH3-1, AH3-2 and AH3-3 are also on-delay: AH3-1 single-pole changeover, AH3-2 double-pole, and AH3-3 adds one instantaneous changeover beside the delayed one. If an immediate contact must seal a start button while the delayed contact starts a second stage, that instantaneous contact is the reason to choose AH3-3 or the ST3PC rather than a separate relay.
Because the timer starts on coil energization, the trigger must stay present. A momentary pushbutton that releases after half a second will never complete a ten-second delay — the coil drops out, the timer resets, and next time it starts from zero. Either seal the pushbutton through an auxiliary contact or use a latched signal.
Off-delay: the contact drops out late
Off-delay does the opposite. The coil energizes and the contact changes over at once; when the coil drops out, the contact holds its energized position for the set time and then returns. This is the mode for keeping a load running briefly after a stop: cooling fans after a heater shuts down, a lamp held on while a person clears a machine, or a pump clearing a line.
The ST3PF is a true off-delay unit in the ST3P family, with a single delayed changeover or a two-contact build, rated AC 250 V, 3 A and DC 28 V, 5 A. Do not substitute an on-delay relay wired through a normally closed contact. The two differ if the supply fails mid-delay: an off-delay unit holds its stored energy and completes the delay; a reconfigured on-delay unit simply resets.
The ST3PK is a signal-off variant that times from an external control signal rather than from loss of coil power. It suits sensor-triggered timing but is not a drop-out timer. The ST3PG in the same family is the interval timer: it is triggered like an on-delay unit and gives one timed period before returning. Read the working-mode row before ordering — on-delay, interval, signal-off delay and off-delay are four distinct entries, not four names for one function.
Cycle and repeating timers
A cycle timer repeats a timed output while it has power. It suits intermittent duty that must run unattended: a warning beacon, a periodic lubrication pulse, or a process alternating two states. The on and off periods may be set independently on digital units or linked in a fixed ratio on simple analog ones.
The ST3P-R is a repeating-cycle relay with one delayed contact and switch-selected range pairs: 6 s / 60 s, 10 s / 10 min, 30 s / 6 min or 60 s / 60 min. The DH48S family goes further: the DH48S-S is a cycle unit with pause and reset, the DH48S-S-2Z adds a second delayed contact, and the DH48S digital range covers 0.1 s to 99 h 59 m on the S version and 0.01 s to 99 h 99 m on other variants, with ±0.5% setting error and ±0.3% repeat accuracy.
Cycle timers are sometimes used where one delayed action would do. For a one-shot action, a cycle unit leaves the output in whatever state the supply was removed in, which can surprise on the next start. Use on-delay or off-delay for a single timed event; reserve cycle mode for duty that genuinely repeats.
Star-delta changeover timers
Star-delta starting reduces voltage across each winding during acceleration. The motor starts in star, runs for a set time, then changes to delta for full voltage. The timer holds the star contactor long enough to reach safe speed, then allows a clean changeover. The critical detail is dead time between the two contactors: they must never be energized together, or the supply is shorted through the transition.
The TRD-N is a dedicated star-delta changeover timer. It takes an AC 110, 220 or 240 V supply at 50/60 Hz, has a seconds dial for run time, and provides a fixed 0.1 s change interval between star and delta. Its contacts are rated 250 V AC, 5 A resistive and switch the contactor coils, not the motor current. A general on-delay timer can serve in some panels, but lacks the built-in change interval and changeover logic.
Set the dial from the motor's acceleration time under load, then measure the current at changeover. A motor that has not reached speed when delta is applied will draw a current spike close to the locked-rotor value; a motor left in star too long will overheat. If the transition is rough, increase the dead time before blaming the timer.
Mode comparison at a glance
Use this table as a first filter. It describes behaviour, not a specific order code; check the family table below and the data sheet before buying.
| Mode | What starts timing | Contact during delay | Contact after delay | Typical use |
| On-delay | Coil energized | Resting position | Changes over and holds while coil is energized | Sequenced start, time-based stages |
| Off-delay | Coil de-energized | Changed over immediately | Returns after the set time | Fan run-on, delayed drop-out |
| Signal-off delay | External signal released | Follows the signal | Returns after the set time | Sensor-triggered hold |
| Cycle / repeating | Supply applied | Alternates on and off | Repeats until supply is removed | Beacons, periodic pulses |
| Star-delta changeover | Supply applied | Star contactor held | Switches to delta after a dead time | Reduced-voltage motor starting |
Matching the mode to the product family
The figures below come from the Strong Electric canonical product data. They show where each family sits; use the exact model suffix to confirm contacts, supply voltage and socket before ordering.
| Family / example | Mode available | Contacts | Contact rating | Setting range |
| ST3PA | On-delay | Changeover, as the mode requires | AC 250 V, 3 A resistive | 0.05 s to 24 h, ranges A–G |
| ST3PF | Off-delay | Single delayed changeover or two-contact build | AC 250 V, 3 A; DC 28 V, 5 A | See model data |
| ST3P-R | Cycle, repeating | One delayed contact | AC 250 V, 3 A resistive | 6 s/60 s to 60 s/60 min pairs |
| DH48S digital | Single delay, two group, cycle, instantaneous + delay | One or two delayed contacts | AC 250 V, 3 A resistive | 0.01 s to 99 h |
| H3Y-2 | On-delay, two delayed contacts | Two delayed contacts | AC 250 V, 3 A resistive | 1 s to 60 min steps |
| AH3-1 / -2 / -3 | On-delay | SPDT, DPDT, or SPDT plus instantaneous | 5 A at AC 250 V; 5 A at DC 28 V | 1 s to 60 min steps |
| TRD-N | Star-delta changeover | Contacts for contactor coils | 250 V AC, 5 A resistive | Dial in seconds, 0.1 s change |
Note the accuracy difference. Analog knob units quote a ±10% setting error on H3Y and AH3 ranges and around ±0.5% on ST3P and DH48S, with repeat accuracy near ±0.3%. Where a process needs repeatable timing to a few percent, prefer a digital unit and verify with a stopwatch rather than trust the dial.
Wiring and setting sequence
The sequence below assumes a timer switching one or more contactor coils, which is the normal arrangement. Timer contacts are not intended to carry motor or heater current directly.
- Confirm the supply on the relay label. The ST3P and H3Y families are offered across AC 12–380 V and DC 12–24 V; the AH3-1 range lists 110, 220 or 380 VAC and 12 or 24 VAC/DC. The wrong coil voltage is the most common cause of a timer that never powers up.
- Confirm the mode row in the data table. On-delay, off-delay and signal-off delay are separate variants even when the front label shows only a family name.
- Fit the matching socket. ST3P and AH3 units use PF083A, PF085A or US-08 sockets; the H3Y-2 uses PYF08A or PY08. Check the pin count before ordering a spare.
- Wire the coil supply through a fused, switched feed. Where the timer output seals its own supply, include a stop contact in series so the circuit can be broken.
- Wire the delayed contact in series with the contactor coil, not in the motor or heater circuit. Check the coil holding current and inrush against the contact rating — AC 250 V, 3 A resistive on ST3P and H3Y, 5 A on AH3 and TRD-N.
- For a star-delta start, wire the star and delta contactor coils through the appropriate timer contacts and add a mechanical or electrical interlock between the two contactors. The 0.1 s change in the TRD-N is not a substitute for an interlock.
- Set the time with the supply off. On digital units enter the value on the front panel; on knob units choose the range switch first and then the dial.
- Power up with the load disconnected or mechanically safe. Time the changeover with a stopwatch and compare it with the set value, allowing for the quoted setting error.
- Reconnect the load and observe one full cycle, measuring the current at changeover on a star-delta start or checking that the coil drops out at the right moment on an off-delay.
Five mistakes that mimic a failed timer
- Trigger shorter than the delay. A momentary start signal that disappears before the count completes resets an on-delay unit. Seal the signal or use a latching contact.
- Wrong mode for the duty. An on-delay unit asked to hold a fan on after a stop command will never do it. Match the mode to the event that starts the timing.
- Contact carrying the wrong load. A 3 A resistive contact derates sharply when switching an inductive coil without suppression. Fit an interposing relay or a coil suppression module where inrush is high.
- No dead time in a star-delta changeover. If the star and delta contactor coils can overlap, the timer is the least of the problems. Wire the interlock first.
- Reading the setting error as a fault. A ±10% setting error means a 60 s knob setting may complete somewhere near 54 to 66 s even when the unit is healthy. Verify with a stopwatch before replacing it.
Support
Choose the timer by mode first, then by contact arrangement, supply voltage and setting range. Strong Electric supplies the ST3PA on-delay, ST3PF off-delay, ST3P-R cycle, DH48S digital and TRD-N star-delta timers, plus AH3 and H3Y. For a selection check, send the supply voltage, mode, contacts, set time and load, or contact Strong Electric directly.