Technical Guides · 2026-11-25
How to Wire a Floatless Level Relay and Stop False Triggering
Most level relay faults are probe faults, not relay failures. This guide explains how electrode sensing decides that a tank is wet, how the common, low and high electrodes set the pump band, why foam, condensation, cable noise and low-conductivity water cause false switching, and gives a wiring and diagnosis sequence with worked numbers.
A floatless level relay is the least expensive way to hold a tank between two levels, and almost every failure blamed on the relay is a probe problem. The relay is a comparator: it decides whether the resistance between two stainless rods sits below a threshold. Foam, condensation, scale, a probe cable run beside a contactor or water with almost no dissolved solids all change that resistance, and the pump follows.
This guide covers the electrode arrangement, the wiring sequence and the false-triggering cases we see most often on C61F-GP, AFS, 61F-G, DF-96 and SSRC-04 installations, with the numbers needed to place the probes.
Before wiring: isolate and lock off every supply feeding the panel, the pump and any immersed probe, then verify dead at the terminals. The sensing circuit is deliberately low voltage, but a probe lead on a miswired unit can carry mains, and switching the control side does not isolate the pump circuit. Work to the terminal diagram on the actual unit label — numbering differs between families and revisions.
How an electrode relay decides that the tank is wet
The relay applies a small AC voltage across a pair of electrodes and measures the resulting current. Dry air is an open circuit; liquid between the rods is a resistor of a few hundred ohms to a few tens of kilohms. When that resistance falls below the sensitivity threshold, the input changes state and the output relay follows.
The sensing supply is isolated from the mains and kept low: the DF-96D sheet lists a detection voltage below 10 V and a consumption of 2 W or less. That protects the probe circuit, not the installer: a probe lead crossed with a 220 V conductor is at 220 V.
AC sensing is used because a DC current electrolyses the water. One electrode evolves oxygen, the other hydrogen, the rods polarise and the reading drifts within days. Alternating the polarity every half cycle cancels most of that transfer.
Common, low and high: what each electrode does
A single-level unit needs two electrodes: common and level. A pump-duty unit needs three, and the third is what stops short-cycling. The common electrode — the reference — is the return for both level electrodes. It must stay immersed below the low electrode, and it is the one everyone forgets when a tank is cleaned.
The low and high electrodes set the band. For fill duty the pump starts when the low electrode goes dry and stops when the high electrode becomes wet; for drain duty the logic inverts. Some bodies are marked for one duty, some carry a changeover switch, and the same three rods can be wired either way — the diagram for the exact model decides.
Without the band, a single trip point restarts the pump a few millimetres below the stop level, and it cycles until the contactor or the motor fails.
False triggering: symptom, cause, first check
| Symptom | Likely cause | First check |
| Reads wet in an empty tank | Condensation or a conductive dust film bridges the holder or terminal block | Disconnect the probe leads: the relay should read dry. Still wet means the panel, not the tank |
| Drops out when the pump starts | Probe cable shares a conduit or tray with pump and contactor cable; induced voltage looks like a wet signal | Separate the runs, use screened cable, earth the screen at the panel end only |
| Reads wet only at high level | Foam or floating debris bridges the high electrode | Stilling well, or move the probe away from the inlet and the agitation |
| Short-cycles at the top of the band | Band volume smaller than the pump moves in its minimum run time | Size the band from Q × t (worked below) |
| Works on mains water, fails on RO water | Conductivity so low that probe resistance sits above the threshold | Set sensitivity with the rods in the real liquid, or change sensor type |
| Intermittent on a metal tank | The tank wall, not the liquid, completes the circuit through a scratch in the lining or a bonded holder | Insulate the holder from the shell and keep the reference rod in the liquid |
| Pump runs dry with a low probe fitted | Low electrode above the suction mouth, scaled over, or wired for the opposite duty | Check rod length and duty before replacing the relay |
Probe placement and sizing the band
Four rules cover most installations. Put the low electrode at least 100 mm above the suction mouth so the pump cannot draw air, and the high electrode at least 50 mm below the overflow so the overflow stays a backup. Keep neighbouring rods 50 mm apart so a water film or foam cannot bridge them, and in a metal tank keep every rod 50 mm from the wall unless the holder is insulated.
Then size the band so the pump runs long enough to cool and starts rarely enough to survive:
V = Q × t ÷ 60, with Q the pump flow in m³/h and t the minimum run time in minutes.
Worked example: a 3 m³/h pump that should run for at least 3 minutes needs V = 3 × 3 ÷ 60 = 0.15 m³, or 150 litres between the electrodes. In a 1.2 m diameter cylindrical tank the surface area is π × 0.6² = 1.13 m², so the band height is 0.15 ÷ 1.13 = 0.133 m, about 130 mm. A 50 mm gap chosen because it looked tidy holds 57 litres and gives a 1.1 minute cycle — exactly the short-cycling the installer was trying to avoid.
With a live inlet, size on the net flow. At 2 m³/h entering and a 3 m³/h pump, the drawdown is 1 m³/h and the same 150 litre band lasts 9 minutes.
Wiring sequence
The sequence assumes a three-electrode relay switching a pump contactor; only the terminal numbering changes.
- Isolate and lock off the panel, the pump and the probe supply, then verify dead at every terminal you will touch.
- Read the terminal map from the unit label. The SSRC-04 puts U, L, B and NC along the top and A1, A2, C and NO below; the C61F-GP is an eight-pin plug-in body whose numbers come from the socket. Never transfer a numbering between families.
- Mount the relay on DIN rail and bring the probe cable in through its own gland, away from the contactor and motor tray. Cross unavoidable runs at right angles.
- Use screened probe cable and earth the screen at the panel end only; earthing both ends makes a loop that carries the interference the screen was fitted to stop.
- Bond the tank and pump frame to the panel protective earth. In a plastic tank fit a stainless reference electrode instead — there is no other return.
- Cut each rod so its tip sits at the specified level and keep every joint above the highest water level; the 0.3 mm² probe lead must not end in the liquid.
- Wire the relay supply through a fuse or MCB rated for the control circuit and confirm the supply against the label: these families cover 12 and 24 V AC/DC, 110, 220 and 380 V AC depending on model.
- Switch the pump contactor coil through the output contact. The 5 A at 250 V AC rating is a control-circuit rating: use an interposing relay for a large coil, and never put the motor on the level relay contact.
- Put the low-level contact in series with the pump control circuit as a dry-run interlock, so a failed probe cannot leave the pump running against an empty tank.
- Test dry first: with the tank empty the pump must not start. Then fill by hand and confirm it starts at the low electrode and stops at the high one; record both levels against the tank gauge.
- Set sensitivity for reliable switching with margin, not at maximum — maximum is what makes condensation and foam count as water.
Water quality and the sensitivity limit
Between two rods the resistance is roughly R = ρ × d ÷ A, with ρ the resistivity of the liquid, d the spacing and A the wetted area. Resistivity follows conductivity: 200 µS/cm is 50 Ω·m and 800 µS/cm is 12.5 Ω·m.
Take 50 mm spacing and a 5 mm rod immersed 100 mm, so A = π × 0.005 × 0.1 = 1.57 × 10⁻³ m².
| Liquid | Resistivity | Estimated probe resistance |
| Mains water, 800 µS/cm | 12.5 Ω·m | 0.4 kΩ |
| Mains water, 200 µS/cm | 50 Ω·m | 1.6 kΩ |
| RO permeate or condensate, 10 µS/cm | 1,000 Ω·m | 32 kΩ |
| Deionised water, 1 µS/cm | 10,000 Ω·m | 320 kΩ |
Field geometry is not a pair of parallel plates, so read these as orders of magnitude; the useful part is the three-decade spread. Mains water sits comfortably inside a 5–50 kΩ window such as the SSRC-04 dial. RO permeate and condensate sit at the top edge, where a scaled rod or a long cable tips the reading over. Deionised water is outside any electrode relay: use a float or a capacitive sensor rather than maximum sensitivity, which also makes condensation look like water.
Metal tanks, plastic tanks and the earth return
In a plastic tank the only return path is the reference electrode, so all three rods must be present and the reference must reach below the lowest level. Lose it during a clean-out and the relay reads dry while the tank overflows.
In a metal tank the shell is earthed and often touches the liquid, which adds a second and uncontrolled return path. A scratched liner, a holder bonded to the shell or a rod touching the wall can make the relay read wet regardless of level, or read a level higher than the truth. Fit an insulated holder and keep every rod clear of the wall. Bonding the shell to protective earth is a safety measure, not a substitute for the reference electrode.
A five-minute diagnosis that separates relay from field
Divide the loop in two. Disconnect all probe leads at the relay: the output should return to the dry state. If it does not, the relay or its supply is the fault and the tank is irrelevant. Then bridge common to the level terminal through a 10 kΩ resistor: the output should change state, which proves the input stage and the output contact. Finally reconnect one electrode at a time — the electrode that changes the reading while it is still dry is the one being bridged by condensation, scale or a wrong connection.
That order matters: replacing a relay before disconnecting the probes is the most common wasted part in this family, and the new one fails the same way.
Which body for which panel
| Family | Body | Contacts | Supply | Contact rating | Note |
| C61F-GP | 50 × 40 × 79 mm | 1 NO + 1 NC | 12/24 V AC/DC, 110/220/380 V AC | 5 A at 250 V AC | Plug-in body, socket on DIN rail |
| AFS-1 | 50 × 40 × 72 mm | 1 NO + 1 NC | 12/24 V AC/DC, 110/220/380 V AC | 5 A at 250 V AC | Shortest body of the plug-in group |
| 61F-G | 127 × 85 × 75 mm | 2 NO + 2 NC | 110 or 220 V AC | 5 A at 250 V AC | Second contact set for alarm or standby |
| 61F-G1 | 135 × 127 × 75 mm | 3 NO + 3 NC | 110 or 220 V AC | 5 A at 250 V AC | Pump, alarm and standby in one body |
| DF-96A / DF-96B | 126 × 88 × 54 mm | 1 NO + 1 NC | 12/24 V AC/DC, 220/380 V AC | 5 A at 250 V AC | Screw terminals, rail or screw fixing |
| SSRC-04 | 35 × 48 × 90 mm | High and low level, 10 A output | 190–260 V AC | 10 A | 5–50 kΩ sensitivity dial, IP20 |
The SSRC-04 is the odd one: 10 A output and a front sensitivity dial suit a small pump on variable water, but its 190–260 V AC supply window keeps it off a 24 V control bus. Choose 61F-G or 61F-G1 when the alarm must be independent of the pump, because separate contact sets avoid sharing one contact between a coil and a signal. Treat the 5 A rating as a control-circuit rating throughout.
Choosing the right level relay for your tank
Strong Electric supplies the C61F-GP, 61F-G, 61F-G1, AFS-1, DF-96A/B and DF-96D level relays, the SSRC-04 controller, the stainless probes and the PS electrode rod sets in 304, 316 and titanium. The liquid level controllers category lists the whole range.
For a selection check, send the tank size and material, the liquid and its conductivity, the pump flow and head, the control voltage and the duty — or contact us with a photo of the existing holder.