PID Tuning Quick Reference
Where to start the three terms on a heat press, an extruder, an oven or a kiln, and what to change when the loop overshoots, sits low, or hunts.
Start here, then adjust
These are starting values for a loop that is otherwise healthy: sensor in contact with the load, output correctly sized, cycle time sensible. They are not optimum for any particular machine, and every one of them assumes the process is heating only, which most temperature loops are.
| Loop | Proportional band | Integral time | Derivative time |
|---|---|---|---|
| Small mass, fast: hot runner nozzle, soldering iron, small platen | 2 to 4 % | 20 to 60 s | 0 to 20 s |
| Heat press, extrusion barrel, small oven | 3 to 8 % | 60 to 180 s | 10 to 30 s |
| Large mass, slow: kiln, furnace, oil tank, drying tunnel | 5 to 15 % | 180 to 600 s | 30 to 90 s |
| Very inert, long lag: large autoclave, tunnel with heavy load | 10 to 20 % | 600 to 1200 s | 60 to 150 s |
What each term does
- Proportional band sets how far the output moves for a given error. Too narrow and the loop cycles; too wide and it responds sluggishly and sits low.
- Integral time removes the offset the proportional term leaves. Too short and the loop hunts; too long and it takes forever to arrive.
- Derivative time reacts to the rate of change, which is what stops an overshoot on a slow plant. On a noisy reading it amplifies the noise, so leave it at zero until the reading is clean.
| What you see | What to change |
|---|---|
| Overshoots the set point on start-up and comes back slowly | Widen the proportional band before touching the integral; on a slow loop add derivative |
| Sits a few degrees below the set point and never arrives | Shorten the integral time. A wide band with integral off leaves a permanent offset |
| Slow oscillation of constant amplitude, period of minutes | Lengthen the integral time; the loop is hunting around the set point |
| Fast oscillation, period of seconds | Widen the band, remove derivative, or check that the output is not a relay pulsing a large heater |
| Reading jumps around while the heater output is steady | This is the sensor, not the tuning: loose probe, unshielded lead near a drive, or a thermocouple in contact with a live surface |
| Output cycles on and off with a period of one to two seconds | Set the output cycle time up to 10 to 20 s for a relay, or switch to SSR drive for fast cycling |
Cycle time is part of the tune
A relay output switching a 3 kW heater should cycle over 10 to 20 seconds; faster and the contact wears out, slower and the band has to be wide enough to hide the ripple. An SSR drive output can cycle in one second, which lets the band stay narrow. If the reading oscillates with a period of a second or two, the cycle time is the problem, not the PID terms.
Controllers with autotune and manual PID entry: TC4, TC5, CH series.