PID Tuning Quick Reference

Where to start the three terms on a heat press, an extruder, an oven or a kiln, and what to change when the loop overshoots, sits low, or hunts.

Start here, then adjust

These are starting values for a loop that is otherwise healthy: sensor in contact with the load, output correctly sized, cycle time sensible. They are not optimum for any particular machine, and every one of them assumes the process is heating only, which most temperature loops are.

Loop Proportional band Integral time Derivative time
Small mass, fast: hot runner nozzle, soldering iron, small platen2 to 4 %20 to 60 s0 to 20 s
Heat press, extrusion barrel, small oven3 to 8 %60 to 180 s10 to 30 s
Large mass, slow: kiln, furnace, oil tank, drying tunnel5 to 15 %180 to 600 s30 to 90 s
Very inert, long lag: large autoclave, tunnel with heavy load10 to 20 %600 to 1200 s60 to 150 s

What each term does

  • Proportional band sets how far the output moves for a given error. Too narrow and the loop cycles; too wide and it responds sluggishly and sits low.
  • Integral time removes the offset the proportional term leaves. Too short and the loop hunts; too long and it takes forever to arrive.
  • Derivative time reacts to the rate of change, which is what stops an overshoot on a slow plant. On a noisy reading it amplifies the noise, so leave it at zero until the reading is clean.
What you see What to change
Overshoots the set point on start-up and comes back slowlyWiden the proportional band before touching the integral; on a slow loop add derivative
Sits a few degrees below the set point and never arrivesShorten the integral time. A wide band with integral off leaves a permanent offset
Slow oscillation of constant amplitude, period of minutesLengthen the integral time; the loop is hunting around the set point
Fast oscillation, period of secondsWiden the band, remove derivative, or check that the output is not a relay pulsing a large heater
Reading jumps around while the heater output is steadyThis is the sensor, not the tuning: loose probe, unshielded lead near a drive, or a thermocouple in contact with a live surface
Output cycles on and off with a period of one to two secondsSet the output cycle time up to 10 to 20 s for a relay, or switch to SSR drive for fast cycling

Cycle time is part of the tune

A relay output switching a 3 kW heater should cycle over 10 to 20 seconds; faster and the contact wears out, slower and the band has to be wide enough to hide the ripple. An SSR drive output can cycle in one second, which lets the band stay narrow. If the reading oscillates with a period of a second or two, the cycle time is the problem, not the PID terms.

Controllers with autotune and manual PID entry: TC4, TC5, CH series.

Questions this guide answers

Should I just press autotune?
Autotune is a good start on a loop that can be run at full power for a few cycles without spoiling product. It is a poor choice on a loaded oven or a press with material in it, because the tune is done on a different plant from the one that runs. Start from the table, then autotune, then adjust.
Why does my loop sit 5 °C below set point?
Integral is too slow or switched off. Proportional-only control always leaves an offset; the integral term is what removes it. Shorten the integral time in steps of about 30 % and watch the next two cycles.