SSR Heat Sink Selection Table

The heat an SSR dissipates at 10 to 100 A, the heat sink thermal resistance that keeps the junction inside its limit, and what happens when the sink is missing or the panel runs hot.

The sum that decides the sink

An SSR is a pair of thyristors in series, and it drops about 1.6 V however much current flows. The heat is the current times the drop, and the sink has to carry that heat away fast enough to keep the junction below 125 °C:

Rth(sink) <= (125 °C − ambient) / (1.6 V × current) − Rth(junction to case)

With a 40 °C panel and 0.3 °C/W junction to case, a 40 A relay needs about 1.2 °C/W from the sink. That is a finned block of roughly 120 by 100 mm, not the small plate that ships with a 10 A unit.

Relay current Heat in the relay Heat sink at or below Typical profile
10 A16 W5.0 °C/WPlate 80 × 50 mm
15 A24 W3.0 °C/WPlate 100 × 60 mm
25 A40 W2.0 °C/WFinned 100 × 80 mm
40 A64 W1.2 °C/WFinned 120 × 100 mm
60 A96 W0.8 °C/WFinned 150 × 120 mm, fan assisted
80 A128 W0.6 °C/WFinned 200 × 120 mm, fan assisted
100 A160 W0.45 °C/WFinned 250 × 120 mm, forced air

What goes wrong without one

A relay bolted to a panel with no sink carries a fraction of its rating, and it fails in a way that looks like a control fault: it switches for a few weeks, then latches on. The junction reached its limit, the die degraded, and the output shorted. Before replacing the relay, measure the sink temperature after an hour at load — anything above 80 °C means the sink is undersized or the paste is missing.

Mounting, in order

  • Clean both faces, apply a thin even film of thermal paste, and tighten to the torque on the relay sheet.
  • Mount the sink vertically so convection helps; horizontal fins lose roughly a third of their rating.
  • Keep the relay out of the hot air rising off a heater or a transformer.
  • Above 60 A, add a fan and a thermostat, or move to a larger relay run well below its rating.

Sinks and relays: SSR heat sinks, SSR-DA series.

Questions this guide answers

Will a 40 A relay really make 64 W of heat?
Yes. An SSR drops about 1.6 V across its output devices whatever the load, so the loss is the current times that drop: 40 A times 1.6 V is 64 W. That is why the same relay is rated 40 A on a sink and a fraction of it without one.
What if the panel runs at 55 °C?
Derate. Above 40 °C ambient, allow about 1 % of current per °C, or fit the next size of sink, or add forced air. A relay chosen exactly at its rating at 40 °C is over its junction limit at 55 °C.
Does thermal paste matter?
It is the difference between the relay case and the sink. Without paste the interface adds roughly 0.5 °C/W, which on a 40 A relay is another 30 °C of junction temperature.

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.