Temperature Controllers
TC7-W W1G-2 program controller
The 96 mm bezel in the W1G-2 version. Thirty-two program segments, a 0.1 °C display and a choice of thermocouple or RTD input; relay plus solid-state, two outputs in one version.

- Output
- Relay plus solid-state dual output
- Bezel
- 96 × 48 × 75
- Panel cut-out
- 92 × 45
Technical specifications
| Series | TC7 Series (universal-input panel-mount PID temperature controller) |
|---|---|
| Models | TC7-S / TC7-H / TC7-M / TC7-L / TC7-W |
| Order code | W1G-2, read as W + 1 + G + 2: relay and SSR drive output, one alarm, universal input, 100–240VAC/DC supply. W2G-2 adds a second alarm, and a C in the sixth position adds RS485. |
| Display | Two 4-digit LED rows, PV above SV |
| Control method | PID with auto-tuning, plus ON/OFF |
| Program control | 32-segment programmer (PRON 0–32): 0 runs fixed-setpoint control, and 1–32 run setpoint/time pairs SP1–ST1 through SP32–ST32 |
| Ramp rate (SPR) | 0–999.9 °C/min |
| Segment time | 0.1–999.9 minutes or hours, or 1–9999 seconds or minutes, selected by the STCY time-unit digit |
| Timer mode (STCY) | Four independent digits ABCD — start mode, count direction, end action and time unit. Factory default 2020. |
| Start deviation (STTP) | 3°C |
| Hold value (ENSP) | 100 |
| Program status display | SETX in the upper row shows the running segment number; the ALM2 lamp flashes while timing and stays lit when the timer ends |
| Input | K, J, R, S, B, E, N, T thermocouple; Pt100 and Cu50 RTD; 0–20mA and 4–20mA; 0–5V and 1–5V |
| Control output | Relay plus 12VDC SSR drive on every variant, switchable from the front panel; 4–20mA or 0–10V analogue output to order |
| Relay contact rating | 10A contact, 800W resistive load |
| Alarm output | One alarm as standard (ALM1); the W2G-2 code adds ALM2 |
| Soft start | Output held to 25% of full power for the soft-start window, so a cold heater is not switched on at 100% and the element is not thermally shocked |
| Temperature unit | °C or °F, selected on the front panel |
| Communication | RS485 Modbus RTU to order (C in the order code) |
| Supply voltage | 100–240VAC/DC, 50/60Hz; 24VAC/DC on the 4 supply code |
| Accuracy | ±0.5°C |
| Display resolution | 0.1°C |
| Panel size | 48×48 / 48×96 / 72×72 / 96×96 / 96×48mm |
| Panel cutout | 45×45 / 45×92 / 68×68 / 92×92 / 92×45mm |
| Dimensions (depth) | 75mm behind the bezel |
| Housing | ABS case with a perforated top and side vents |
| Mounting | Panel mount, base-bolt clamp |
| Certification | CE |
| Typical applications | Ovens, incubators, injection moulding machines, greenhouses, agricultural drying rooms and general machine temperature control |
Product overview
Part no. SE-TC7
Also known as: TC7 temperature controller · TC7 PID controller · TC7 controlador de temperatura
The TC7 is the programmer in the range: 32 segments, each pairing a setpoint with a segment time, run back to back at an adjustable ramp rate so an oven or furnace follows a heating profile instead of sitting at one temperature. Segment 0 switches the programmer off and leaves a plain fixed-setpoint PID controller, so the same instrument covers both jobs. Underneath the programmer sits one universal input board — K, J, R, S, B, E, N and T thermocouples, Pt100 and Cu50 RTDs, 0–20mA and 4–20mA current loops, 0–5V and 1–5V signals — so a single part number covers a machine that mixes sensor types. Every variant carries a relay output and a 12VDC SSR drive together and switches between them from the keypad, and the 25% soft start holds the first seconds of heating down so a cold element is not hit at full power. Five bezel sizes run from 48×48 to 96×48mm, all 75mm deep.
Ordering code
TC7-W W1G-2
The 96 mm bezel in the W1G-2 version. Thirty-two program segments, a 0.1 °C display and a choice of thermocouple or RTD input; relay plus solid-state, two outputs in one version.
| Order code | TC7-W W1G-2 |
|---|---|
| Bezel (mm) | 96 × 48 × 75 |
| Cut-out (mm) | 92 × 45 |
| Output | Relay plus solid-state dual output |
| Output terminals | as marked on the case |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: Relay plus solid-state dual output: the relay carries a contactor and the SSR drive carries a solid state relay
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Key features
- 32-segment programmer: each segment pairs a setpoint with a segment time, and up to 32 run back to back as a single heating profile
- Ramp rate in °C per minute on every segment, so the profile climbs at a controlled slope instead of stepping to the setpoint
- Programmable timer: start on temperature, on the keypad or at power-on; count up or down; finish by cutting the heating output, holding at the ENSP value or holding the last segment setpoint
- Segment 0 turns the programmer off and leaves a fixed-setpoint PID controller
- Universal input: K, J, R, S, B, E, N, T thermocouple, Pt100 and Cu50 RTD, 0–20mA and 4–20mA, 0–5V and 1–5V
- Relay output and 12VDC SSR drive fitted together, switchable from the keypad
- PID with auto-tuning, plus ON/OFF for simple on-off loads
- 25% soft start protects a cold heater from full-power inrush
- Five bezel sizes — 48×48, 48×96, 72×72, 96×96 and 96×48mm — all 75mm deep
- RS485 Modbus RTU to order for PLC or SCADA integration
Works with
The parts that go into the same panel and are usually ordered with it.
32-segment program control
The TC7 runs a heating profile, not just a setpoint. A profile is a list of segments — climb to this temperature in this many minutes, hold it for this long, then move on — and the controller walks the list on its own.
32program segments
0–999.9 °C/min
ramp rate per segment
0 = fixed setpoint
PRON 0–32. Each of the 32 segments holds a setpoint and a segment time, so one instrument can run a full ramp-and-hold cycle without an external PLC.
- Each segment pairs a setpoint (SP) with a segment time (ST), and segment 0 switches the programmer off and leaves a fixed-setpoint controller.
- Ramp rate (SPR) sets how fast a segment climbs, in °C per minute. Leave it at 0 and the controller steps straight to the segment setpoint instead of ramping.
- Start mode decides when the clock starts: on the keypad, once the measured value reaches the setpoint minus the start deviation (STTP), or at power-on.
- End action decides what happens after the last segment: cut the heating output, hold at the hold value (ENSP), or hold the last segment setpoint.
- While a program runs, the upper row shows SETX with the running segment number and the ALM2 lamp flashes; it stays lit once the timer ends.
STCY — four digits, four decisions
The timer behaviour is packed into one four-digit setting, ABCD. The factory default is 2020: temperature start, count up, hold at the last segment setpoint, minutes in 0.1 steps.
- AStart modethousands
- 2Temperature start — timing begins once PV reaches SP − STTP3Key and temperature combined4Power-on startotherKey start
- BCount directionhundreds
- 1Count down from the set time to zerootherCount up from zero to the set time
- CEnd actiontens
- 1Heating output off2Hold at the ENSP valueotherHold the last segment setpoint
- DTime unitunits
- 00.1–999.9 minutes10.1–999.9 hours21–9999 seconds31–9999 minutes
DefaultsSTTP start deviation 3°C · ENSP hold value 100
Ordering & Selection Guide
Specified as TC7-[bezel] followed by output, alarm, input, supply, and RS485 — e.g. TC7-S W1G2C (48×48mm, relay + SSR, 1 alarm, universal input, 100–240VAC/DC, RS485).
Bezel size
- S
- 48×48×75mm · 45×45mm cutout
- H
- 48×96×75mm · 45×92mm cutout
- M
- 72×72×75mm · 68×68mm cutout
- L
- 96×96×75mm · 92×92mm cutout
- W
- 96×48×75mm · 92×45mm cutout
Control output
- W
- Relay contact and SSR drive, fitted together and switched from the keypad
Alarm outputs
- 1
- One alarm relay
- 2
- Two alarm relays
Input type
- G
- Universal: thermocouple K, E, J, N, T, S, R, B; RTD Pt100 and Cu50; 0–20mA and 4–20mA; 0–5V and 1–5V
Supply voltage
- 2
- 100–240VAC/DC
- 4
- 24VAC/DC
Communication
- —
- No RS485
- C
- RS485 Modbus RTU
Worked example
48×48mm bezel, relay plus SSR drive, one alarm, universal input, 100–240VAC/DC supply, RS485 Modbus RTU.
- Shorthand “W1G-2” means output W, 1 alarm, universal input G, 100–240VAC/DC supply 2.
- Code 2 in supply is 100–240VAC/DC; code 4 is 24VAC/DC. Trailing C adds RS485 Modbus RTU.
Wiring and control loop
The TC7 switches the heating load two ways from the same instrument: a 10A relay contact that switches the load directly, and a 12VDC SSR drive that fires an external solid-state relay for longer life on resistive heaters. A universal input takes the thermocouple or RTD, one or two alarm relays flag a fault, and the optional RS485 port drops the instrument onto a Modbus RTU network.
The relay contact is rated 10A / 800W resistive. Size the load and any external SSR so the switched current stays within that rating; keep the heater well below the limit for long-term reliability.
Dimensions and panel cutout
Five bezel sizes share the same 75mm depth behind the panel and a base-bolt clamp. Pick the face that fits the cutout you already have; the depth and mounting method are identical across the family.
| Model | Face (mm) | Cutout (mm) | Depth |
|---|---|---|---|
| TC7-S | 48 × 48 | 45 × 45 | 75mm |
| TC7-H | 48 × 96 | 45 × 92 | 75mm |
| TC7-M | 72 × 72 | 68 × 68 | 75mm |
| TC7-L | 96 × 96 | 92 × 92 | 75mm |
| TC7-W | 96 × 48 | 92 × 45 | 75mm |
Applications and version
A panel-mount PID controller with a 32-segment programmer suits any process that needs a ramp-and-hold temperature profile rather than a single setpoint — ageing ovens, incubators, plastic injection and agricultural drying among them.
Typical uses
- Curing ovens and industrial ovens
- Incubators and environmental chambers
- Plastic injection moulding machines
- Greenhouses and controlled cultivation
- Agricultural drying rooms
- General machine temperature control
What the version gives you
- Dual 4-digit LED: process value above, setpoint below, with °C/°F, OUT, AT and alarm lamps
- Relay and SSR drive switchable from the keypad — pick the switching method without opening the case
- 32-segment programmer runs a full ramp-and-hold cycle on its own, with no external PLC
- 25% soft start limits inrush so a cold heater is not shocked at switch-on
- Universal input covers the common thermocouples, RTDs and analogue signals in one instrument
- Optional RS485 Modbus RTU for setpoint writing and data logging from a PLC or SCADA
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the TC7 need?
48×48 / 48×96 / 72×72 / 96×96 / 96×48mm. The cut-out is 45×45 / 45×92 / 68×68 / 92×92 / 92×45mm
Which sensors can the TC7 read?
K, J, R, S, B, E, N, T thermocouple; Pt100 and Cu50 RTD; 0–20mA and 4–20mA; 0–5V and 1–5V
What output options does the TC7 have?
Relay plus 12VDC SSR drive on every variant, switchable from the front panel; 4–20mA or 0–10V analogue output to order
What supply voltage does the TC7 need?
100–240VAC/DC, 50/60Hz; 24VAC/DC on the 4 supply code
How accurate is the TC7?
±0.5°C, at 0.1°C resolution
Does the TC7 have alarm outputs?
One alarm as standard (ALM1); the W2G-2 code adds ALM2
Related guides
TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guide Product Updates · 2024-02-05REX-C Series PID Temperature Controller: Input Codes, Output Codes and Panel Data
A specification and commissioning reference for the REX-C family: how the input and output code letters work, panel and cutout dimensions for each model, PID setting ranges and…
Read guide Product Updates · 2024-02-04CH Series PID Temperature Controller: Sizes, Input and Output Codes, Alarm Modes
Panel dimensions, cutouts, input and output option codes, alarm mode selection and commissioning notes for the CH (REX-CH) short-body PID temperature controller family.
Read guideRelated models
All Temperature Controllers
TC7-D / TC7-R Dial Temperature Controller — thumbwheel or knob, 0–400°C
SE-TC7-D
75mm behind the bezel
View details
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View details
TC4W Digital PID Temperature Controller
SE-TC4W
96×48mm (1/8 DIN) · 92×45mm · 75mm total, 71mm behind the panel
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.