CH series · short body
CH702 72 × 72 mm 220VAC digital PID temperature controller
72 × 72 mm bezel, 68 × 68mm cut-out. Short case 78mm or long case 100mm, chosen on the order. Three output stages are ordered in this bezel, each with its own order code.
Download manual (PDF) · 11 pages
Body: short case 78mm or long case 100mm, on the same model number · see CD701
Ordering & Selection Guide
Five positions. The bezel is the model number itself, then the control mode, the input and its range, the output, and the alarm pair.
| Position | Order code | What it selects |
|---|---|---|
| 1 | CH102 / CH402 / CH502 / CH702 / CH902 | Case size: 48 × 48, 48 × 96, 96 × 48, 72 × 72 or 96 × 96mm, 78mm behind the panel |
| 2 | F | Control mode: F reverse acting for heating, D direct acting for cooling |
| 3 | K02 | Input and its range: K02 is a K thermocouple over 0–400 °C; other letters select J, R, S, B, E, N, T, Pt100, Cu50 or a linear signal |
| 4 | M / V / 8 | Output stage: M relay 250VAC 3A, V SSR drive, 8 current 4–20mA |
| 5 | *AN | Alarm pair: the first letter is alarm 1 and the second is alarm 2, each one of N none, A upper deviation, B lower deviation, C either side of the set point, D deviation band, E upper deviation held, F lower deviation held, G either side held, H process high, J process low, K process high held, L process low held |
Technical specifications
| Accuracy | ±0.5 %FS ±1 °C |
|---|---|
| Supply voltage | 220VAC 50/60Hz, 10VA |
| Control method | PID with autotuning, or ON/OFF |
| Indication | Dual 4-digit LED, PV above SV |
| Setting method | Front-panel membrane keys |
| Alarms | One relay output, A/B/C selectable |
| Body depth | 78mm behind the panel |
| Operating environment | 0–50 °C, 30–85 %RH, no condensation |
Output types
| Position | Output | Load |
|---|---|---|
| M | Electromagnetic relay | Contact rating 3A at 250VAC. Switches a contactor coil or a small heater directly. The terminal pair is printed on the case diagram and differs between models. |
| V | SSR drive SE-SSR-DA | Voltage pulse for an external solid state relay; the load current becomes the relay's rating. The terminal pair is printed on the case diagram. |
| 8 | Current output | 4–20mA analogue output for an SCR power regulator or a PLC input. The terminal pair is printed on the case diagram. |
Terminal numbers here follow the diagram printed on the side of the instrument. If the unit you receive carries a different numbering, the diagram on the case takes precedence over this page.
Inputs and the probe that suits each
| Order code | Output | Range | Probe |
|---|---|---|---|
| K | Thermocouple | 0–1372 °C (K02: 0–400 °C) | SE-TC-WRNK236 |
| J | Thermocouple | 0–750 °C | — |
| E | Thermocouple | 0–1000 °C | SE-TC-RING |
| N | Thermocouple | 0–1300 °C | — |
| T | Thermocouple | −199.9–400.0 °C | — |
| R | Thermocouple | 0–1700 °C | — |
| S | Thermocouple | 0–1769 °C | — |
| B | Thermocouple | 0–1820 °C | — |
| Pt100 | RTD | −199.9–649.0 °C | SE-RTD-PT100 |
| Cu50 | RTD | −50.0–150.0 °C | SE-RTD-CU50 |
| WRe | Thermocouple (W5Re/W26Re) | 0–2320 °C | — |
| JPt100 | RTD (Japanese Pt100 curve) | −199.9–649.0 °C | SE-RTD-PT100 |
| 0–5V / 1–5V | Linear | scaled | — |
| 0–20mA / 4–20mA | Linear | scaled | — |
Order codes of this bezel
| No | Order code | Output | Terminals |
|---|---|---|---|
| 1 | CH702FK02-M*AN | Built-in electromechanical relay, 250VAC 3A, dry contact | on the case diagram |
| 2 | CH702FK02-V*AN | Voltage pulse output, 0–12VDC, for an external solid state relay | on the case diagram |
| 3 | CH702FK02-8*AN | Analogue current output, 4–20mA (0–10mA on request) | on the case diagram |
Dimensions
General arrangement: bezel, the two bodies behind the panel, and the panel cut-out. The full sheet is sent with the quotation.
Wiring
Terminal numbers as printed on the case, with the supply, the input and the output stage for this bezel size.
Works with
The parts that go into the same panel and are usually ordered with it.