Timer Relays
DH48S Series Digital Time Relay
DH48S digital time relay: on-delay, cycle and two-group versions with a 0.1s–99h59m (DH48S-S) / 0.01s–99h99m (DH48S-1Z, -2Z, -2ZH) range, 5A contacts and 48×48mm panel or 35mm DIN rail mounting.

- Panel cut-out
- 45×45mm
- Control output
- 3 A at 250 V AC; 5 A at 28 V DC, resistive
- Product series
- DH48S digital time relay
- Type
- Digital display time relay, single or two group
Technical specifications
| Product series | DH48S digital time relay |
|---|---|
| Type | Digital display time relay, single or two group |
| Models | DH48S-S (cycle) / DH48S-1Z (single delay) / DH48S-2Z (two group) / DH48S-2ZH (one instantaneous, one delay) / DH48S-S-2Z (two group cycle) |
| Delay range | 0.1s–99h59m (DH48S-S) / 0.01s–99h99m (DH48S-1Z, -2Z, -2ZH) |
| Display | Four-digit LED, two groups (T1 / T2) with a settable time unit |
| Time unit | 0.1s, s, 0.1min, min, 0.1h, h — switched on the front panel |
| Control output | 3 A at 250 V AC; 5 A at 28 V DC, resistive |
| Supply | AC 36 / 110 / 220 / 380V, DC 12 / 24V — fixed when ordering |
| Supply tolerance | 85–110% of the rated voltage |
| Accuracy | ≤1 % of the set time |
| Power | ≤5W |
| Mechanical life | ≥1,000,000 operations |
| Electrical life | ≥100,000 operations |
| Insulation resistance | 100MΩ at DC500V |
| Dielectric strength | BCC 1500VAC, BOC 1000VAC |
| Mounting | 48×48mm panel cut-out or 35mm DIN rail socket |
| Panel cut-out | 45×45mm |
| Front bezel | 48×48mm (1/16 DIN) |
| Depth | 83mm behind the panel |
| Weight | ≈150g; 185g with the socket |
| Operating temperature | −10…+50°C |
| Humidity | 35–85% RH, no condensation |
| Altitude | below 2000m |
| Load limit | Resistive loads up to 800W at 220VAC switch directly; above that, or for any 380V load, the relay drives a contactor instead |
| Setting | Dial switch |
| Indication | 8-segment 4-digital display |
| Repeat accuracy | ±0.3%, ±0.05 sec |
| Setting error | ±0.5%, ±0.05 sec |
| Termination | 8 pins |
| Matched socket | PF083A , PF083A-E |
Product overview
Part no. SE-DH48S
Also known as: DH48S timer relay · DH48S time relay · DH48S relé temporizador
DH48S is a digital time relay for panel builders who need a settable delay without a PLC: four digits on the front set the time, a switch selects the unit from 0.1s to an hour, and the output is a 5A changeover contact. Five versions cover the jobs a timer usually gets — a single on-delay, a repeating cycle, two independent delays, or one instantaneous contact alongside a delayed one. The range runs from 0.1s–99h59m (DH48S-S) / 0.01s–99h99m (DH48S-1Z, -2Z, -2ZH), so the same meter covers a 2-second conveyor start and a 4-hour curing cycle.
Key features
- Five versions from one meter: single delay, cycle, two-group, instantaneous plus delay, and two-group cycle
- Front-panel time units — 0.1s, s, 0.1min, min, 0.1h, h — so a short delay and a long one are entered the same way
- 5A changeover contact: resistive loads up to 800W at 220VAC switch directly
- Reset and pause inputs on the single-group versions, so a start button and a hold button wire straight in
- 48×48mm bezel on a 45×45mm cut-out, with a 35mm DIN rail socket available so the relay can be swapped without rewiring
- Mechanical life of 1,000,000 operations and electrical life of 100,000 at rated load
- Supply fixed at order: AC 36V, 110V, 220V or 380V, or DC 12V or 24V
Works with
The parts that go into the same panel and are usually ordered with it.
Ordering & Selection Guide
Ordering a DH48S takes two lines: the function, carried in the model number after the hyphen, and the supply voltage, chosen separately because the same function exists on seven supplies. Neither can be inferred from the other.
| Part | What it selects |
|---|---|
| DH48S | Series: digital time relay, 48×48mm |
| S | Repeating cycle |
| 1Z | Single on-delay |
| 2Z | Two independent delays |
| 2ZH | One instantaneous group, one delayed |
| S-2Z | Two-group cycle |
| Part | What it selects |
|---|---|
| AC36V | 36VAC, 50/60Hz |
| AC110V | 110VAC, 50/60Hz |
| AC220V | 220VAC, 50/60Hz — default version |
| AC380V | 380VAC, 50/60Hz |
| DC12V | 12VDC |
| DC24V | 24VDC |
| AC/DC24V | 24V AC or DC, no polarity |
Worked example
DH48S-1Z · AC220V
A single on-delay from 0.01s to 99h59m on 220VAC. Ordering “DH48S-1Z” alone leaves the voltage undefined, and the factory ships 220VAC by default.
Five versions at a glance
All five share the same 48×48mm body, 45×45mm cut-out, and 8-pin base.
| Model | Function | Time range | Output | Inputs / use |
|---|---|---|---|---|
| DH48S-S | Cycle (repeating) | 0.1s – 99h | 1 changeover (NO + NC) | Reset & pause inputs |
| DH48S-1Z | Single on-delay | 0.01s – 99h59m | 1 changeover (NO + NC) | Reset & pause inputs |
| DH48S-2Z | Two independent delays | 0.01s – 99h59m | 2 changeover groups | No reset or pause |
| DH48S-2ZH | 1 instantaneous + 1 delayed | 0.01s – 99h59m | Instant NO/NC + delayed NO/NC | Fan/auxiliary with load |
| DH48S-S-2Z | Two-group cycle | 0.1s – 99h | 2 changeover groups | Alternating on/off duty |
Setting the time on the panel
Every DH48S version sets its time the same way: pick the unit with the red digit, then raise or lower the digits with + and −. What differs is how many digits there are and what they mean — the cycle version splits them into an off interval and an on interval.
| Version | Range | Units | What the digits mean |
|---|---|---|---|
| DH48S-S | 0.1S – 99H | 0.1S / S / 0.1M / M / 0.1H / H | T1 = off interval, T2 = on interval; repeats until power is removed |
| DH48S-1Z | 0.01S – 99H99M | S / M / H | one time, four digits; output closes once when it elapses |
| DH48S-2Z | 0.01S – 99H99M | S / M / H | two independent times, one per output group |
| DH48S-2ZH | 0.01S – 99H99M | S / M / H | one delayed group plus one instantaneous group |
| DH48S-S-2Z | 0.1S – 99H | 0.1S / S / 0.1M / M / 0.1H / H | two alternating cycle groups |
Setting a time, in order
- 1Press and hold SET until the display flashes: the relay is now in setting mode, not in timing.
- 2Use the unit key to pick S, M or H — or, on the cycle version, one of the six steps from 0.1S to H.
- 3Set the digits with + and −. On the cycle version T1 is how long the output stays off and T2 how long it stays on; on the delay version the four digits are one time.
- 4Press SET again to store. The value is held without power, so a power cut does not reset it.
- Set the unit before the number. 3600 reads 36.00s or 36.00h depending on the unit step, and a machine that waits an hour instead of 36 seconds is nearly always this.
- The cycle version repeats indefinitely once powered — it does not need a start signal, and it will keep switching until the supply is removed.
Terminal assignment (8-pin base)
Top row: 6-5-4-3 · Bottom row: 7-8-1-2. Supply on 2 & 7; output common on 8.
| Pins | Function | Versions |
|---|---|---|
| 2 – 7 | Supply (L on 7, N on 2) | All |
| 8 – 6 | Output contact (NO) | All |
| 2 – 5 | Second output (opposite to 6) | S, 1Z |
| 8 – 5 | Output contact (NC) | 2Z, 2ZH |
| 7 – 8 | Jumper from live to contact common | All |
| 1 – 3 | Reset input (dry contact only) | S, 1Z |
| 1 – 4 | Pause input (dry contact only) | S, 1Z |
| 1–3 / 1–4 | Second output group | 2Z, S-2Z |
| 1–3 / 1–4 | Instantaneous NO / NC | 2ZH |
Wiring, by version
The supply lands on terminals 2 and 7 with 7–8 jumpered; the output contact is 8–6 normally open, 8–5 normally closed. What changes between versions is terminals 1, 3 and 4 — reset and pause on -S and -1Z, the second group on -2Z, the instantaneous contacts on -2ZH. Terminals are grouped by function: supply and control on the left of the case, outputs on the right.
Red is live, blue is neutral, green is control. Dashed lines are normally-closed contacts or the 7–8 jumper.
Before you wire it
No mains on pins 1, 3, 4
On S / 1Z versions, pins 1, 3 and 4 are dry control inputs. Applying mains voltage destroys the relay.
Use a contactor above 800W
Switch ≤800W resistive at 220VAC directly. Above 800W or any 380V load, drive a contactor coil.
Fixed supply voltage
Supply voltage is fixed at order (e.g. 220VAC vs 380VAC) — always match the panel control voltage.
Check time unit first
Set the unit switch (s / m / h) before the digits so 3.00s does not run as 3.00h.
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
TEL96-9001 or TEL96-2001: Choosing the Right Oven Temperature Controller
The TEL96 series is a 96 x 96 mm on/off oven temperature controller built around a K-type thermocouple input and a 10 A relay contact. It is made in two versions, the TEL96-9001…
Read guide Technical Guides · 2026-11-23How Time Relay Modes Work: On-Delay, Off-Delay, Star-Delta and Cycle
Most timer problems are mode problems, not failures. This guide explains what starts and resets each of the four common timing modes, compares the ST3P, DH48S, H3Y and AH3…
Read guide Product Updates · 2025-04-11TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guideRelated models
All Timer Relays
DH48S-S Cycle Time Relay
SE-DH48S-S
48 × 48 × 115 mm (1/16 DIN front)
View details
JSS20-48AMS Digital Time Relay
SE-JSS20-48AMS
48 × 48 × 115 mm (1/16 DIN front)
View details
ZN48S Digital Time Relay
SE-ZN48S
The same 48 mm body with the longer scale: hundredths of a second to four figures of hours. ZN48S-1Z carries one delayed contact with pause and…
View details
JSZ3P-R Cycle Time Relay
SE-JSZ3P-R
A repeating timer with two independent settings on the face, so the on time and the off time are each set in hours, minutes and seconds. One delayed…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.