Insulation Monitors
SZIM-DAR Certified DC Insulation Monitor
SZIM-DAR certified DC insulation monitor, the certified version, with the face, setting and response that belong to this unit alone in the table below.

- DC system voltage measured
- 0–1000 VDC
- DC measurement accuracy
- ±2 V from 0 to 400 VDC, ±0.5 % from 400 to 1000 VDC
- Auxiliary supply
- 10–30 VDC; 120 mA at 12 V or 55 mA at 24 V, ≤1.5 W
- Insulation resistance range
- 0 kΩ–10 MΩ across a 100–1000 VDC system
Technical specifications
| Product | DC insulation monitor for unearthed systems |
|---|---|
| DC system voltage measured | 0–1000 VDC |
| DC measurement accuracy | ±2 V from 0 to 400 VDC, ±0.5 % from 400 to 1000 VDC |
| Auxiliary supply | 10–30 VDC; 120 mA at 12 V or 55 mA at 24 V, ≤1.5 W |
| Insulation resistance range | 0 kΩ–10 MΩ across a 100–1000 VDC system |
| Insulation accuracy, Cy² 0–0.8 µF | ≤60 kΩ: ≤3 kΩ · 60 kΩ–1 MΩ: ≤5 % |
| Insulation accuracy, Cy² 0.8–2.5 µF | ≤60 kΩ: ≤6 kΩ · 60 kΩ–1 MΩ: ≤20 % |
| First reading after switch-on | 0.7–1.4 s |
| Reading refresh after a change | 0.7–2.5 s |
| Earth-switch operations | 50 × 10⁵ |
| Alarm relay | 400 VAC / 600 VDC, 4 A, <100 mΩ, 1000 MΩ at 500 VDC |
| Storage / working temperature | −55 to 90 °C / −40 to 75 °C |
Product overview
Part no. SE-GYIM-DARindustry model GYIM-DAR
Also known as: SZIM-DAR Certified DC insulation monitor
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it is the cut-out it needs.
Key features
- The face, the setting and the response of this version, listed in its own table
- One version per page, because these differ between them
- Photograph and drawing where the factory has supplied one
Works with
The parts that go into the same panel and are usually ordered with it.
Dimensions

Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related models
All Insulation Monitors
DAR-60 Certified Monitor for Control Circuits
SE-GYIM-DAR-2
The certified control-circuit version. Along with its larger sibling it is the only unit in the range whose response time is published against the…
View details
SZID Vehicle-Grade Insulation Monitor, AC and DC
SE-GYID-INSULATION
A different animal from the rest: it does not close a relay, it publishes the resistance as a value for a battery management system to read. Sealed…
View details
UB1K DC Insulation Monitor
SE-UB1K
The kilovolt version: 100 to 1000 VDC floating systems, read pole to earth at 1 kΩ to 10 MΩ, with the alarm relay and the buzzer on the same board.…
View details
UBCH1 Boxed DC Insulation Monitoring Device
SE-UBCH1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.