Insulation Monitors
DAR-60 Certified Monitor for Control Circuits
The certified control-circuit version, with its response time published against system capacitance, the figure a certification body asks for.

- DC system voltage measured
- 0–60 VDC
- Measurement accuracy
- ≤1 V across 10–60 VDC
- Auxiliary supply
- 10–30 VDC; 120 mA at 12 V or 55 mA at 24 V, ≤1.5 W
- Insulation resistance range
- 0 kΩ–1 MΩ across a 10–60 VDC system
Technical specifications
| Product | DC insulation monitor for unearthed systems |
|---|---|
| DC system voltage measured | 0–60 VDC |
| Measurement accuracy | ≤1 V across 10–60 VDC |
| Auxiliary supply | 10–30 VDC; 120 mA at 12 V or 55 mA at 24 V, ≤1.5 W |
| Insulation resistance range | 0 kΩ–1 MΩ across a 10–60 VDC system |
| Insulation accuracy, Cy² 0–0.5 µF | ≤60 kΩ: ≤3 kΩ · 60–200 kΩ: ≤5 % · 200 kΩ–1 MΩ: ≤15 % (≤10 % at 30–60 V) · 1–2 MΩ: ≤30 % (≤20 %) |
| Response time | ≤1.5 s at 0 µF, 2.5 s at 0.5 µF, 4 s at 2 µF, 5 s at 5 µF |
| Earth-switch operations | 50 × 10⁵ |
| Alarm relay | 400 VAC / 600 VDC, 4 A, <100 mΩ at 10 mA 30 mV, 1000 MΩ at 500 VDC |
| Storage / working temperature | −55 to 90 °C / −40 to 75 °C |
Product overview
Part no. SE-GYIM-DAR-2industry model GYIM-DAR
Also known as: DAR-60 Certified Insulation Monitor
The certified control-circuit version. Along with its larger sibling it is the only unit in the range whose response time is published against the capacitance of the system — which is the figure a certification body asks for.
Key features
- Certified version for control circuits
- Response time published against system capacitance
- Alarm relay figures stated in the table
- Same case and terminals as the DAR
Works with
The parts that go into the same panel and are usually ordered with it.
Dimensions

Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
Over-Temperature Protection and Interlock Wiring for Industrial Heating Equipment
A controller alarm tells an operator that something is wrong; it does not stop the heater. This guide shows how to add an independent limit controller, a normally-closed safety…
Read guide Technical Guides · 2026-08-27How to Wire CH102, CH402, CH702 and CH902 PID Temperature Controllers
A practical wiring guide for CH102, CH402, CH702 and CH902 PID temperature controllers, covering power, AC contactor and SSR control, thermocouple and Pt100 sensors, alarms and…
Read guide Technical Guides · 2026-08-25TEL96-9001 Temperature Controller Wiring Guide: Direct Heater and AC Contactor Methods
Terminal-by-terminal wiring for the TEL96-9001 ON/OFF temperature controller: K-type thermocouple connection, direct heater switching up to 1500 W, AC contactor control, 220 VAC…
Read guideRelated models
All Insulation Monitors
SZIM-DAR Certified DC Insulation Monitor
SE-GYIM-DAR
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
SZID Vehicle-Grade Insulation Monitor, AC and DC
SE-GYID-INSULATION
A different animal from the rest: it does not close a relay, it publishes the resistance as a value for a battery management system to read. Sealed…
View details
UB1K DC Insulation Monitor
SE-UB1K
The kilovolt version: 100 to 1000 VDC floating systems, read pole to earth at 1 kΩ to 10 MΩ, with the alarm relay and the buzzer on the same board.…
View details
UBCH1 Boxed DC Insulation Monitoring Device
SE-UBCH1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.