REX-C series
REX-C900 96 × 96 mm (1/4 DIN) 220VAC digital PID temperature controller
96 × 96 mm (1/4 DIN) bezel, 92 × 92mm cut-out. 110mm deep. Three output stages are ordered in this bezel, each with its own order code.
Download manual (PDF) · 12 pages
Ordering & Selection Guide
Five positions. The bezel is the model number itself, then the control mode, the input and its range, the output, and the alarm pair.
| Position | Order code | What it selects |
|---|---|---|
| 1 | REX-C100 / C400 / C700 / C900 | Case size: 48 × 48, 48 × 96, 72 × 72 or 96 × 96mm |
| 2 | F | Control mode: F reverse acting for heating, D direct acting for cooling |
| 3 | K02 | Input and its range: K02 is a K thermocouple over 0–400 °C; other letters select J, R, S, B, E, N, T, Pt100, Cu50 or a linear signal |
| 4 | M / V / 8 / g | Output stage: M relay 250VAC 3A, V SSR drive switching 0/12 V DC, 8 current 4–20mA, g zero-crossing trigger pulse for an external triac |
| 5 | *AN | Alarm pair: the first letter is alarm 1 and the second is alarm 2, each one of N none, A deviation high, B deviation low, C deviation both ways, D band, E deviation high held, F deviation low held, G deviation both ways held, H process high, J process low, K process high held, L process low held; the letters after the first may also set the input option (N multiple inputs, B alarm 2 fitted, N-DA K input only, N-24VAC or N-24VDC for a low-voltage supply) |
Technical specifications
| Accuracy | ±0.5 %FS ±1 °C |
|---|---|
| Supply voltage | 220VAC 50/60Hz, 10VA |
| Control method | PID with autotuning, or ON/OFF |
| Indication | Dual 4-digit 7-segment LED, PV red above SV green |
| Setting method | Front-panel membrane keys |
| Alarms | Two relay outputs, N or A to L selectable |
| Operating environment | 0–50 °C, 30–85 %RH, no condensation |
Output types
| Position | Output | Load |
|---|---|---|
| M | Electromagnetic relay | Contact rating 3A at 250VAC. Switches a contactor coil or a small heater directly. The terminal pair is printed on the case diagram and differs between models. |
| V | SSR drive SE-SSR-DA | Voltage pulse 0–12VDC for an external solid state relay. The load current becomes the relay's rating. |
| 8 | Current output | 4–20mA analogue output for an SCR power regulator, a recorder or a PLC input. |
| g | Triac, zero crossing | Zero-crossing trigger pulse for a thyristor module; used on older panels and rebuilt furnaces. |
Inputs and the probe that suits each
| Order code | Output | Range | Probe |
|---|---|---|---|
| K | Thermocouple | 0–1372 °C (K02 setting: 0–400 °C) | SE-TC-WRNK236 |
| J | Thermocouple | 0–750 °C | — |
| E | Thermocouple | 0–1000 °C | SE-TC-RING |
| N | Thermocouple | 0–1300 °C | — |
| T | Thermocouple | −200–400 °C | — |
| R | Thermocouple | −50–1769 °C | — |
| S | Thermocouple | 0–1769 °C | — |
| B | Thermocouple | −50–1769 °C | — |
| Pt100 | RTD | −199.9–649.0 °C | SE-RTD-PT100 |
| Cu50 | RTD | −50.0–150.0 °C | SE-RTD-CU50 |
| 0–5V / 1–5V | Linear | 0.0–100.0 (scaled) | — |
| 0–20mA / 4–20mA | Linear | 0.0–100.0 (scaled) | — |
Order codes of this bezel
| No | Order code | Output | Terminals |
|---|---|---|---|
| 1 | REX-C900FK02-M*AN | Built-in electromechanical relay, 250VAC 3A, dry contact | on the case diagram |
| 2 | REX-C900FK02-V*AN | Voltage pulse output, 0–12VDC, for an external solid state relay | on the case diagram |
| 3 | REX-C900FK02-8*AN | Analogue current output, 4–20mA (0–10mA on request) | on the case diagram |
Dimensions
General arrangement: bezel, the two bodies behind the panel, and the panel cut-out. The full sheet is sent with the quotation.
Works with
The parts that go into the same panel and are usually ordered with it.