TC4-W PID Temperature Controller: Panel Data, Outputs and Retrofit Notes
Panel and cutout dimensions, electrical specification, output selection and retrofit checks for the TC4-W horizontal PID temperature controller within the TC4 family.
The TC4-W is the 96 × 48mm horizontal member of the TC4 family. It shares the firmware, parameter set and terminal logic of every other TC4 size — only the bezel, cutout and digit layout differ. Ordering data is on the TC4 series product page.
1. Panel data
| Parameter | Specification |
| Panel size | 96 × 48mm (horizontal) |
| Panel cutout | 92 × 45mm |
| Depth | 75mm body + 4mm bezel |
| Display | 4-digit dual row LED — red PV, green SV |
The horizontal format suits control desks and machine fascias where height is limited but width is available; the TC4-H (48 × 96mm) is the same electronics in the vertical orientation.
2. Electrical specification
| Parameter | Specification |
| Control method | ON/OFF, position control, PID with auto-tuning |
| Input | Thermocouple K, J, E, T, N, S, R, B; RTD Pt100 and Cu50; linear 0–20mA, 4–20mA, 0–5V, 1–5V |
| Control output | Relay + SSR drive (W), voltage output, current output, SCR trigger |
| Alarm output | 0, 1 or 2 alarms |
| Communication | RS485 Modbus RTU optional |
| Supply | 100–240VAC or 24VDC, max. 8VA |
| Accuracy | ±0.5% FS |
| Sampling period | 100ms |
| Relay life | Mechanical >2,500,000 operations; electrical >100,000 operations |
| Operating environment | -5 to 40°C, 35–85% RH |
3. Retrofit checks
- Measure the existing cutout, not the old bezel. 92 × 45mm takes the TC4-W; 45 × 92mm takes the TC4-H.
- Confirm 79mm of clearance behind the panel for the body plus wiring.
- Match the supply: the AC and DC versions are different hardware and cannot be changed later.
- Record the outgoing controller's input type, output type, setpoint limits and PID values before removal.
- Check the output stage of the old unit — a relay-wired panel needs a relay or W output; an SSR-driven panel needs the SSR drive.
4. Commissioning
- Set input type to match the fitted sensor, then confirm the reading rises during heat-up.
- Set output type to match the wiring, and set the control period: 1–2s for SSR, 20s or more for a contactor.
- Set the scale high limit and an absolute high alarm below the machine safe limit.
- Run auto-tune at the working setpoint with the real load; transferring PID values from a different machine rarely holds.
- With RS485, assign a unique address and match baud rate, parity and stop bits across the bus.
5. FAQ
Is the TC4-W functionally different from other TC4 sizes?
No. Inputs, outputs, accuracy and parameters are identical across TC4S, TC4H, TC4W, TC4M and TC4L.
Can a TC4-W replace a 96 × 48mm REX-C410?
The cutout matches at 92 × 45mm, but terminal numbering differs — re-check the wiring against the TC4 terminal diagram before energising.
Does it support Modbus?
Yes, with the RS485 communication option ordered at the same time as the controller.
Where do I find full model codes?
On the TC4 product page, and in the TC4 series technical manual.
Retrofit questions: sales@strong-ele.com.