Panel and cutout dimensions, electrical specification, output selection and retrofit checks for the TC4-W horizontal PID temperature controller within the TC4 family.

The TC4-W is the 96 × 48mm horizontal member of the TC4 family. It shares the firmware, parameter set and terminal logic of every other TC4 size — only the bezel, cutout and digit layout differ. Ordering data is on the TC4 series product page.

1. Panel data

ParameterSpecification
Panel size96 × 48mm (horizontal)
Panel cutout92 × 45mm
Depth75mm body + 4mm bezel
Display4-digit dual row LED — red PV, green SV

The horizontal format suits control desks and machine fascias where height is limited but width is available; the TC4-H (48 × 96mm) is the same electronics in the vertical orientation.

2. Electrical specification

ParameterSpecification
Control methodON/OFF, position control, PID with auto-tuning
InputThermocouple K, J, E, T, N, S, R, B; RTD Pt100 and Cu50; linear 0–20mA, 4–20mA, 0–5V, 1–5V
Control outputRelay + SSR drive (W), voltage output, current output, SCR trigger
Alarm output0, 1 or 2 alarms
CommunicationRS485 Modbus RTU optional
Supply100–240VAC or 24VDC, max. 8VA
Accuracy±0.5% FS
Sampling period100ms
Relay lifeMechanical >2,500,000 operations; electrical >100,000 operations
Operating environment-5 to 40°C, 35–85% RH

3. Retrofit checks

  • Measure the existing cutout, not the old bezel. 92 × 45mm takes the TC4-W; 45 × 92mm takes the TC4-H.
  • Confirm 79mm of clearance behind the panel for the body plus wiring.
  • Match the supply: the AC and DC versions are different hardware and cannot be changed later.
  • Record the outgoing controller's input type, output type, setpoint limits and PID values before removal.
  • Check the output stage of the old unit — a relay-wired panel needs a relay or W output; an SSR-driven panel needs the SSR drive.

4. Commissioning

  • Set input type to match the fitted sensor, then confirm the reading rises during heat-up.
  • Set output type to match the wiring, and set the control period: 1–2s for SSR, 20s or more for a contactor.
  • Set the scale high limit and an absolute high alarm below the machine safe limit.
  • Run auto-tune at the working setpoint with the real load; transferring PID values from a different machine rarely holds.
  • With RS485, assign a unique address and match baud rate, parity and stop bits across the bus.

5. FAQ

Is the TC4-W functionally different from other TC4 sizes?

No. Inputs, outputs, accuracy and parameters are identical across TC4S, TC4H, TC4W, TC4M and TC4L.

Can a TC4-W replace a 96 × 48mm REX-C410?

The cutout matches at 92 × 45mm, but terminal numbering differs — re-check the wiring against the TC4 terminal diagram before energising.

Does it support Modbus?

Yes, with the RS485 communication option ordered at the same time as the controller.

Where do I find full model codes?

On the TC4 product page, and in the TC4 series technical manual.