AC Contactors

LR-D Thermal Overload Relay

Overload relay that plugs onto the contactor: eighteen setting ranges from a tenth of an amp to thirty-eight, with manual or automatic reset.

LR2-D thermal overload relays, three frame sizes
LR-D frames: the relay clips under the contactor, with the trip contact and the reset on the right.
Function
Thermal protection that plugs onto the contactor, with manual or automatic reset
Auxiliary
One normally open and one normally closed contact
Tripping class
Class 10 A
Matching contactor
LR-D13 on CJX2N-09 to 25, LR-D23 on CJX2N-32, LR-D33 on CJX2N-38; LR-K12 on CJX2-K06, K09 and K12
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesLR-D thermal overload relay, with LR-K for the miniature frames
FunctionThermal protection that plugs onto the contactor, with manual or automatic reset
AuxiliaryOne normally open and one normally closed contact
Tripping classClass 10 A
Matching contactorLR-D13 on CJX2N-09 to 25, LR-D23 on CJX2N-32, LR-D33 on CJX2N-38; LR-K12 on CJX2-K06, K09 and K12
LR-D06Setting range 1 to 1.6 A
LR-D07Setting range 1.6 to 2.5 A
LR-D08Setting range 2.5 to 4 A
LR-D10Setting range 4 to 6 A
LR-D12Setting range 5.5 to 8 A
LR-D14Setting range 7 to 10 A
LR-D16Setting range 9 to 13 A
LR-D21Setting range 12 to 18 A
LR-D22Setting range 16 to 24 A
LR-D32Setting range 23 to 32 A
LR-D35Setting range 30 to 38 A
LR-K12 ranges0.1 to 0.16 A, 0.16 to 0.25 A, 0.25 to 0.4 A, 0.4 to 0.63 A, 0.63 to 1 A and 1 to 1.6 A
LR-F53/220Version for the F115 to F225 contactors
LR-F73/330Version for the F265 to F330 contactors

Product overview

Part no. SE-LR-D

Also known as: Schneider LR-D · LR-D thermal overload relay · thermal overload relay

A contactor switches the motor; the thermal relay is what stops it cooking when the load jams. The LR-D range runs from a tenth of an amp to thirty-eight, in eighteen setting ranges, with manual or automatic reset and one changeover contact to drop the coil.

Key features

  • 0.1 A to 38 A setting ranges
  • Manual or automatic reset
  • Plugs onto the CJX2N contactor

Works with

The parts that go into the same panel and are usually ordered with it.

Settings and tripping ranges

Two frame families cover the range: the D13, D23 and D33 blocks that clip straight under a contactor, and the larger D150 to D630 and F53/F73 units with busbar terminals for the heavy end. Protection is IP20 with the cover on, and the trip class is 10A throughout.

Models
LR2-D13 · D23 · D33 · D150 · D200 · D400 · D630 · LR2-F53 · F73
Standard
IEC 60947-4-1
Approvals
CE · CCC
Tripping class
10A
Rated insulation voltage Ui
690 / 1000 V
Rated impulse withstand Uimp
6 / 8 kV
Signalling
Trip indicator
Tightening torque
0.8 N·m
Degree of protection
IP20
Ambient temperature
−5 to +40°C, max 95% humidity
Storage temperature
−40 to +75°C
Max operating altitude
2000 m
Flame resistance
V1
Mounting
Directly under the contactor

LR-D compact series for CJX2 contactors

A shorter frame that clips under the CJX2 range, with the same 1NO+1NC trip contact and a choice of manual or automatic reset. Two blocks cover the setting ranges: D06 to D14 up to 10A, then D16 to D35 through to 38A.

FrameModelSetting range
D06 – D14
LR-D061–1.6
LR-D071.6–2.5
LR-D082.5–4
LR-D104–6
LR-D125.5–8
LR-D147–10
D16 – D35
LR-D169–13
LR-D2112–18
LR-D2216–24
LR-D3223–32
LR-D3530–38

Reset mode, contact arrangement and the contactor each block clips onto, from the manufacturer's sheet.

Selection and ordering

The setting range is what gets ordered, not the motor rating: pick the relay whose range contains the motor's full-load current, and the table gives the fuse that protects it and the contactor it clips onto. Where two relays overlap, the wider one leaves room to adjust after commissioning.

FrameModelRelay setting currentSetting rangeaM fusegG fuseMatched contactor
Frame 13
13LR2-D13010.16A0.10–0.160.252LC1-D09
LR2-D13020.25A0.16–0.250.52LC1-D09
LR2-D13030.40A0.25–0.4012LC1-D09
LR2-D13040.63A0.40–0.6312LC1-D09
LR2-D13051.0A0.63–1.024LC1-D09
LR2-D13061.6A1.0–1.624LC1-D09
LR2-D1306X2.0A1.25–2.046LC1-D09
LR2-D13072.5A1.6–2.546LC1-D09
LR2-D13084.0A2.5–4.0610LC1-D09
LR2-D13106.0A4.0–6.0816LC1-D09
LR2-D13128.0A5.5–8.01220LC1-D09
LR2-D131410A7–101220LC1-D12
LR2-D131613A9–131625LC1-D18
LR2-D132118A12–182035LC1-D18
LR2-D132225A17–252550LC1-D25
Frame 23
23LR2-D235332A23–324063LC1-D32
LR2-D235540A30–404080LC1-D40
Frame 33
33LR2-D335332A23–324063LC1-D32
LR2-D335540A30–4040100LC1-D40
LR2-D335750A37–5063100LC1-D50
LR2-D335965A48–6563100LC1-D65
LR2-D336170A55–7080125LC1-D80
LR2-D336380A63–8080125LC1-D80
LR2-D336593A80–93160160LC1-D95
LR2-D150150A80–150200250LC1-F115–F150
LR2-D200200A120–200315315LC1-F115–F150
LR2-D400400A160–400400630LC1-F225–F400
LR2-D630630A315–630630800LC1-F330–F630

F53 and F73 for the heavy end

The two bar-mounted families take over where the D-series stops. Same ordering rule: the range first, then the fuse, then the contactor it sits on.

ModelSetting rangeaM fusegG fuseMatched contactor
LR2-F53/5030–505080LC1-F115–F185
LR2-F53/8048–8080125LC1-F115–F185
LR2-F53/10060–100100200LC1-F115–F185
LR2-F53/15090–150160250LC1-F115–F185
LR2-F53/220132–220250315LC1-F225–F265
LR2-F73/330200–330400500LC1-F225–F500
LR2-F73/500300–500500800LC1-F225–F500
LR2-F73/630380–630630800LC1-F400–F630

Tripping curve

Time against current, as a multiple of the setting. The solid line is a cold start and the dashed one a hot start; both are for the 10A class. A relay that trips too early on a hot restart is usually set too close to the motor's full-load current.

D family, 10A class
D family, 10A class
F family, 10A class
F family, 10A class

Separate mounting base

A relay does not have to sit under a contactor. The SAZ1 base carries it on 35mm rail or on screws, so an overload can protect a load that is switched elsewhere in the panel.

RelayBase
LR2-13SAZ1-13
LR2-23SAZ1-23
LR2-33SAZ1-33
The SAZ1 base, and the relay clipped onto it
The SAZ1 base, and the relay clipped onto it

Relay dimensions

45mm wide, 63mm high and 70 to 71mm deep for the compact frames, with the depth growing to 52mm at the D09 where the trip contact sits. The heavy families are drawn below at their own scale.

Overall and mounting dimensions, compact frames
Overall and mounting dimensions, compact frames
Overall and mounting dimensions, the D13 to F73 families
Overall and mounting dimensions, the D13 to F73 families

Circuit

Three main poles through 1-2, 3-4 and 5-6, one normally-closed trip contact across 95-96 and one normally-open across 97-98. Wire the trip contact into the contactor coil circuit, not into the load circuit.

Terminal arrangement
Terminal arrangement

Supply & OEM

Available with your logoMOQ 20 units·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Related models

All AC Contactors

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.