Timer Relays

AH2 Socket Time Relay

A socket time relay in surface (N) and flush (Y) forms, with one delayed plus an instantaneous contact or two delayed.

AH2 socket time relay in its plug-in body, the dial set in seconds and the range stamped on the case
AH2: the dial sets the delay inside the range printed on the case, and the plug-in body needs no panel cut-out. The flush Y form takes the second photograph.
Panel cut-out
61 × 50 mm
Working mode
On-delay
Contacts
One delayed plus one instantaneous changeover, or two delayed
Contact rating
AC 250 V, 3 A; DC 28 V, 5 A
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

Working modeOn-delay
ContactsOne delayed plus one instantaneous changeover, or two delayed
Contact ratingAC 250 V, 3 A; DC 28 V, 5 A
Supply110, 220 or 380 V AC 50/60 Hz; 12 or 24 V AC/DC
BodySocket case, 61 × 50 mm cut-out
Panel cut-out61 × 50 mm
MountingN builds are the exposed type: they mount on the backplate or the DIN rail inside the enclosure, on an 8PFA eight-pin round socket, so the wiring is made and serviced from inside the box. Y builds are the flush type: they sit in a cut-out in the door, on a US-08 or P3G-08 base with its fixing frame, so the knob and the lamps are reachable without opening the door.
Supply tolerance−15% to +10% at AC, −10% to +10% at DC of the rated supply
Power3 W max
SettingKnob
IndicationLED
Repeat accuracy±0.3%, ±0.05 sec
Setting error±0.5%, ±0.05 sec
Termination8 pins
Mechanical life1,000,000 operations
Electrical life1×10^5 operations
Temperature0 to 50 ℃
Humidity95% RH max, non-condensing

Product overview

Part no. SE-AH2

Also known as: AH2 timer relay · AH2 time relay · AH2 relé temporizador

A socket timer in two mounting forms, the same split as the ASTP: the N version sits on a surface socket, the Y version mounts flush on the panel front behind its own bezel. Contacts follow the code - one delayed plus one instantaneous, or two delayed.

Key features

  • On-delay
  • AC 250 V, 3 A; DC 28 V, 5 A
  • Panel or DIN rail

Works with

The parts that go into the same panel and are usually ordered with it.

Models in this series

The N code mounts on a surface socket; the Y codes mount flush on the panel front. Within the Y group, Y2 carries two delayed contacts where Y carries one delayed and one instantaneous.

Model numberContactsDelay timeVoltageBody (mm)Cutout / mounting
AH2-NOn-delay SPDT instantaneous SPDT1s/3s/6s/10s/30s/60s/3m/6m/30m/60mAC 110/220/380 V, 12/24 V AC/DC93 × 58 × 8861 × 50
AH2-YOn-delay SPDT instantaneous SPDT1s/3s/6s/10s/30s/60s/3m/6m/30m/60mAC 110/220/380 V, 12/24 V AC/DC93 × 58 × 8861 × 50
AH2-Y2On-delay DPDT1s/3s/6s/10s/30s/60s/3m/6m/30m/60mAC 110/220/380 V, 12/24 V AC/DC93 × 58 × 8861 × 50

Which one, within the series

  • Pick the contact arrangement the panel needs, then the delay range that covers the duty

Shared by the series

  • Contact rating is AC 250 V, 3 A resistive across the family
  • Timing accuracy of one percent or better
  • Supply is AC 12–380 V or DC 12–24 V on the same unit where the sheet allows it
  • Panel or socket mounting, with a 35 mm rail adapter where the body allows it

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Related guides

Related models

All Timer Relays

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.