AH3-A.B.C.D.E Socket Time Relay

One socket timer, five range groups: AH3-A 1 s to 10 min, B 3 s to 30 min, C 6 s to 60 min, D 1 min to 10 h, E 3 min to 30 h. The mode switch sets the contacts, not the code.

AH3-B socket time relay: a 0–3.0 dial with its red pointer, the UP and ON lamps above it, and two selector blocks beside a 220 VAC label
AH3-B: the letter on the face is the range group from the sheet - B covers 3 s, 30 s, 3 min and 30 min - while the contact arrangement is the -1, -2 or -3 suffix. The two selector blocks under the dial set the multiplier (×10 or ×1), the unit (M or S) and the mode (B or A).
Panel cut-out
46 × 36 mm inside a 50 × 40 mm front; two Ø4.5 mm fixing holes 33 mm apart
Contact rating
5 A at AC 250 V resistive; delayed 2C, delayed 1C or instantaneous 1C by model
Supply
AC 12, 24, 110, 220, 240, 380, 415, 440 V or DC 12, 24 V, 50/60 Hz
Body
49 × 39 × 57.5 mm
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

Working modeMode A or mode B, set on the face: mode A switches one instantaneous changeover, mode B switches the delayed pair plus the instantaneous
Setting rangeA: 1 s, 10 s, 1 min, 10 min; B: 3 s, 30 s, 3 min, 30 min; C: 6 s, 60 s, 6 min, 60 min; D: 1 min, 10 min, 1 h, 10 h; E: 3 min, 30 min, 3 h, 30 h
Contact rating5 A at AC 250 V resistive; delayed 2C, delayed 1C or instantaneous 1C by model
SupplyAC 12, 24, 110, 220, 240, 380, 415, 440 V or DC 12, 24 V, 50/60 Hz
Body49 × 39 × 57.5 mm
Panel cut-out46 × 36 mm inside a 50 × 40 mm front; two Ø4.5 mm fixing holes 33 mm apart
MountingSurface (N) on socket PF-085A with SH-3, or flush (Y) on US-08 or P3G-08
Termination8-pin plug-in, on the socket
Matched socketPF-085A and SH-3 for surface; US-08 or P3G-08 for flush
SettingKnob on the face
IndicationON and UP lamps, two indicators
Repeat accuracy±1 % max
Setting error±10 % max
Voltage error±1 % max
Temperature errorless than ±2 % at 20 °C
Reset time0.1 s max
Powerabout 2 VA at AC, about 2 W at DC
Mechanical life5 × 10⁶ operations
Electrical life1 × 10⁵ operations
Temperature−10 to +55 °C
Humidity45–85 % RH
Weight160 g

Product overview

Part no. SE-AH3industry model AH3-A…E

Also known as: AH3-A time relay · AH3-B time relay · AH3-E time relay · AH3-A.B.C.D.E timer relay

One socket timer, five range groups, and the letter is the whole model code: AH3-A 1 s to 10 min, AH3-B 3 s to 30 min, AH3-C 6 s to 60 min, AH3-D 1 min to 10 h, AH3-E 3 min to 30 h. The contacts are not in the code - the mode switch on the face decides them: A switches one instantaneous changeover, B the delayed pair plus the instantaneous. Body 49 × 39 × 57.5 mm.

Key features

  • A–E is the whole model code; the mode switch sets the contacts
  • AC 12–440 V or DC 12/24 V, 50/60 Hz
  • Surface on PF-085A with SH-3, or flush on US-08 or P3G-08

Works with

The parts that go into the same panel and are usually ordered with it.

The range at a glance

The factory sheet puts both families side by side: the five analogue range groups and the digital version, with the contact table and the accuracy figures. The table further up this page is generated from our own product data; this is the document it was transcribed from, kept for anyone who wants to see the whole array at once.

Factory specification sheet: AH3-A to E and AH3-DM, with ranges, contacts, accuracy and weight
AH3-A…E / AH3-DM — specification sheetOpen the drawing

The model code, both axes

The letter is the whole model code. Five of them, one per range group, and nothing else is appended - there is no contact digit in the code.

The letter sets the range group

A1 s, 10 s, 1 min, 10 min
B3 s, 30 s, 3 min, 30 min
C6 s, 60 s, 6 min, 60 min
D1 min, 10 min, 1 h, 10 h
E3 min, 30 min, 3 h, 30 h

The mode switch sets the contacts

Aone instantaneous changeover
Bthe delayed pair plus the instantaneous

AH3-DM is not a variant of this family: it is a separate digital instrument, 0.01 s to 99 h, with its own page. The sheet prints both families side by side only because they share the body and the socket.

Wiring and timing

The same eight-pin body in both mounting forms. Power lands on pins 2 and 7; the changeover contacts come out on 8-5, 8-6, 1-4 and 1-3; the ON and UP lamps have their own pair.

AH3 and AH3-DM wiring and timing diagrams in mode A and mode B
AH3 / AH3-DM — mode A and mode BOpen the drawing

The sheet's own contact table: mode A carries one instantaneous changeover at 5 A; mode B carries the delayed pair, the instantaneous and a second delayed, all at 5 A. Which set is live is fixed by the mode switch on the face, A or B, so read the chart before wiring.

Outline dimensions

The body is 49 × 39 × 57.5 mm and the front bezel 50 × 40 mm, so the cut-out is 46 × 36 mm. Two Ø4.5 mm holes, 33 mm apart, take the fixing screws. With the socket fitted the depth runs to 82 mm.

AH3 and AH3-DM outline drawing: front, side and fixing holes
AH3 / AH3-DM — dimensions in mmOpen the drawing

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Related guides

Related models

All Timer Relays

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.