Temperature Controllers
CD401FK02-8*AN — CD401 with analogue current output
The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.

- Output
- Analogue current output, 4–20mA (0–10mA on request)
- Bezel
- 48 × 96
- Panel cut-out
- 45 × 92
Technical specifications
| Body | Long case only, 100mm behind the panel |
|---|---|
| Input | Thermocouple K, J, R, S, B, E, N, T and W5Re/W26Re; RTD Pt100, JPt100 and Cu50; linear 0–5V, 1–5V, 0–20mA, 4–20mA. Ranges: K 0–1372, R 0–1700, S 0–1769, B 0–1820, WRe 0–2320, Pt100 and JPt100 −199.9–649 °C |
| Series | CD series panel-mount PID temperature controller |
| Models | CD101 / CD401 / CD701 / CD901 |
| Panel sizes | 48×48×82, 48×96×75, 72×72×73 and 96×96×66 mm |
| Panel cutouts | 45×45, 45×92, 68×68 and 92×92 mm |
| Range | 0–1370 °C |
| Control | PID with autotuning, heating or cooling action chosen by code |
| Alarm outputs | no alarm, upper and lower deviation, upper, or lower, per relay |
| Main output | relay contact, SSR drive or 4–20 mA, chosen by code |
| Supply | 100–240 VAC, 220 V nominal |
| Accuracy | ±1 °C |
| Response time | one second |
| Front protection | IP44 |
| Mounting | panel, plastic case |
Product overview
Part no. SE-CD
Also known as: CD temperature controller · CD PID controller
The CD is the plainest controller in the range and the cheapest way to hold a setpoint. A single instrument, a bezel for every panel size, and a version for each job: a K thermocouple or a Pt100 into a dual output, alarm contacts, or a current signal. Nothing to configure beyond the setpoint and the tuning it does itself.
Ordering code
CD401FK02-8*AN
The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.
| Order code | CD401FK02-8*AN |
|---|---|
| Bezel (mm) | 48 × 96 |
| Cut-out (mm) | 45 × 92 |
| Output | Analogue current output, 4–20mA (0–10mA on request) |
| Output terminals | on the case diagram |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue input
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Reading this order code
How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.
| Position | Reads | Meaning |
|---|---|---|
| 1 | CD401 | 48 × 96 mm (1/8 DIN) bezel on a 45 × 92mm panel cut-out |
| 2 | F | Control mode: reverse acting, the usual choice for heating |
| 3 | K02 | Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50 |
| 4 | 8 | Analogue current output, 4–20mA (0–10mA on request) |
| 5 | *AN | Alarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead |
Key features
- The face, the setting and the response of this version, listed in its own table
- One version per page, because these differ between them
- Photograph and drawing where the factory has supplied one
Downloads
Works with
The parts that go into the same panel and are usually ordered with it.
Four bezels on one instrument
The model number tells you the panel size before anything else: the last two digits run 101, 401, 701, 901 and each one is a different cutout on the same electronics. Choose by the hole the machine already has.
| Model | Panel W×H×D (mm) | Cutout (mm) |
|---|---|---|
| CD101 | 48 × 48 × 82 (1/16 DIN front) | 45 × 45 |
| CD401 | 48 × 96 × 75 (1/8 DIN front) | 45 × 92 |
| CD701 | 72 × 72 × 73 | 68 × 68 |
| CD901 | 96 × 96 × 66 (1/4 DIN front) | 92 × 92 |
Ordering & Selection Guide
Six positions after CD: panel size, control action, input & range, main output, then alarm codes (hyphen before output, star before alarms).
①②③ · Panel size (mm)
- 101
- 48×48×82 · cut-out 45×45
- 401
- 48×96×75 · cut-out 45×92
- 701
- 72×72×73 · cut-out 68×68
- 901
- 96×96×66 · cut-out 92×92
④ · Control action
- F
- PID with autotuning, reverse — heating
- D
- PID with autotuning, direct — cooling
⑤ · Input type and range
- K02
- K thermocouple
- E02
- E thermocouple
- D10
- Pt100 RTD
- P10
- Cu50 RTD
⑥ · Main output
- M
- Relay contact (RELAY)
- V
- Voltage pulse (SSR drive)
- 8
- Current output 4–20 mA
Show alarm codes (⑦⑧ · 12 options: N, A–L)
- N
- No alarm configured
- A
- Upper deviation
- B
- Lower deviation
- C
- Upper and lower deviation
- D
- Deviation band
- E
- Upper deviation, hold action
- F
- Lower deviation, hold action
- G
- Upper and lower deviation, hold action
- H
- Process high (absolute)
- J
- Process low (absolute)
- K
- Process high, hold action
- L
- Process low, hold action
Worked example
CD701FK02-MAB
72×72×73 on a 68×68 cut-out, reverse action for heating, K thermocouple input, relay output, an upper deviation alarm on the first relay and a lower deviation alarm on the second.
What each bezel is ordered as
Every size comes in the same four versions, so two decisions describe the instrument completely: the panel size, and the version fitted to it. The input is fixed at the factory and cannot be changed later.
- K thermocouple, dual outputTwo independent outputs on one instrument
- Pt100, dual outputThe same, for an RTD sensor rather than a thermocouple
- Two alarm outputsWhere the machine has to signal out-of-band running
- 4–20 mA outputRecording or a second controller in the loop
Against the CH series
The CD is the simpler of the two: four bezels rather than five, a one-second response and a relay output, and no communication option in the listing. Where a machine needs the fifth size, a faster sampling loop or Modbus, the CH series is the one to quote.
| CD | CH | |
|---|---|---|
| Bezels | four, 48 to 96 square | five, including the 48 × 48 CH102 |
| Response | one second | half-second sampling period |
| Accuracy | confirmed per order | ±0.5% or ±1.0% of span |
| Communication | not offered in the listing | none on CH either; REX and TC4 carry it |
| Where it wins | the cheapest way to hold a setpoint | tighter loop on fast loads |
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
Input codes and measuring ranges
Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
| Input | Code and measuring range |
|---|---|
| KThermocouple | K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C |
| JThermocouple | J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C |
| RThermocouple (accuracy not guaranteed over 0–399 °C) | R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C |
| SThermocouple (accuracy not guaranteed over 0–399 °C) | S01 0–1600 °CS02 0–1769 °C |
| BThermocouple (accuracy not guaranteed over 0–399 °C) | B01 400–1800 °CB02 0–1769 °C |
| EThermocouple | E01 0–800 °CE02 0–1000 °C |
| NThermocouple | N01 1–1300 °CN02 0–1300 °C |
| TThermocouple (accuracy held from −199 to 100 °C) | T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C |
| PT100RTD | D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C |
| Cu50RTD | P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C |
| 0–5VDCStandard signal | 401 0.0–100.0 |
| 1–5VDCStandard signal | 601 0.0–100.0 |
| 0–20mAStandard signal, 250 Ω resistor across the terminals | 701 0.0–100.0 |
| 4–20mAStandard signal, 250 Ω resistor across the terminals | 801 0.0–100.0 |
Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.
Wiring
The range on one sheet, body by body: a contactor arrangement, a solid state relay arrangement and an alarm light for each, with the electrician's diagram and the terminal reference beside them. The circuit repeats; the terminal numbers do not, so read the panel that matches your case.
CD series · wiring, schematics and terminal references
Check the jumper before powering up: 2–4 on the contactor version, 2–8 on the alarm version, and none on the SSR version, where 7 (+) and 3 (−) carry a 12 VDC drive rather than a contact. On the relay versions the common sits on 2, so the supply terminal feeding it is the one that must be linked.
Documents for this family
- Strong Electric CH CD Instruction Manual420 KB · 2026-11-16
- CD series wiring307 KB · 2026-11-18
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the CD need?
48×48×82, 48×96×75, 72×72×73 and 96×96×66 mm. The cut-out is 45×45, 45×92, 68×68 and 92×92 mm
Which sensors can the CD read?
K thermocouple or Pt100
What output options does the CD have?
relay contact, SSR drive or 4–20 mA, chosen by code
What supply voltage does the CD need?
100–240 VAC, 220 V nominal
How accurate is the CD?
±1 °C
Does the CD have alarm outputs?
no alarm, upper and lower deviation, upper, or lower, per relay
Related guides
TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guide Product Updates · 2024-02-05REX-C Series PID Temperature Controller: Input Codes, Output Codes and Panel Data
A specification and commissioning reference for the REX-C family: how the input and output code letters work, panel and cutout dimensions for each model, PID setting ranges and…
Read guide Product Updates · 2024-02-04CH Series PID Temperature Controller: Sizes, Input and Output Codes, Alarm Modes
Panel dimensions, cutouts, input and output option codes, alarm mode selection and commissioning notes for the CH (REX-CH) short-body PID temperature controller family.
Read guideRelated models
All Temperature Controllers
REX-C100/C400/C700/C900 Digital PID Temperature Controller
SE-C100
REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and…
View details
C700 Digital Temperature Controller, 72 × 72mm Panel Frame | Strong Electric
SE-C700
72×72mm · 68×68mm · 24mm overall, 20mm of it behind the panel
View details
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.