Temperature Controllers

CD701FK02-8*AN — CD701 with analogue current output

The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.

CD701 PID temperature controller, 72 square front
CD701: the 72 square member, dual display and the five keys.
Output
Analogue current output, 4–20mA (0–10mA on request)
Bezel
72 × 72
Panel cut-out
68 × 68
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

BodyLong case only, 100mm behind the panel
InputThermocouple K, J, R, S, B, E, N, T and W5Re/W26Re; RTD Pt100, JPt100 and Cu50; linear 0–5V, 1–5V, 0–20mA, 4–20mA. Ranges: K 0–1372, R 0–1700, S 0–1769, B 0–1820, WRe 0–2320, Pt100 and JPt100 −199.9–649 °C
SeriesCD series panel-mount PID temperature controller
ModelsCD101 / CD401 / CD701 / CD901
Panel sizes48×48×82, 48×96×75, 72×72×73 and 96×96×66 mm
Panel cutouts45×45, 45×92, 68×68 and 92×92 mm
Range0–1370 °C
ControlPID with autotuning, heating or cooling action chosen by code
Alarm outputsno alarm, upper and lower deviation, upper, or lower, per relay
Main outputrelay contact, SSR drive or 4–20 mA, chosen by code
Supply100–240 VAC, 220 V nominal
Accuracy±1 °C
Response timeone second
Front protectionIP44
Mountingpanel, plastic case

Product overview

Part no. SE-CD

Also known as: CD temperature controller · CD PID controller

The CD is the plainest controller in the range and the cheapest way to hold a setpoint. A single instrument, a bezel for every panel size, and a version for each job: a K thermocouple or a Pt100 into a dual output, alarm contacts, or a current signal. Nothing to configure beyond the setpoint and the tuning it does itself.

Ordering code

CD701FK02-8*AN

The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.

Order codeCD701FK02-8*AN
Bezel (mm)72 × 72
Cut-out (mm)68 × 68
OutputAnalogue current output, 4–20mA (0–10mA on request)
Output terminalson the case diagram
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue input

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
1CD70172 × 72 mm bezel on a 68 × 68mm panel cut-out
2FControl mode: reverse acting, the usual choice for heating
3K02Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50
48Analogue current output, 4–20mA (0–10mA on request)
5*ANAlarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead
Output terminals: on the case diagram·A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue input

Key features

  • The face, the setting and the response of this version, listed in its own table
  • One version per page, because these differ between them
  • Photograph and drawing where the factory has supplied one

Downloads

Download manual (PDF)11 pages · 420 KB

Works with

The parts that go into the same panel and are usually ordered with it.

Four bezels on one instrument

The model number tells you the panel size before anything else: the last two digits run 101, 401, 701, 901 and each one is a different cutout on the same electronics. Choose by the hole the machine already has.

ModelPanel W×H×D (mm)Cutout (mm)
CD10148 × 48 × 82 (1/16 DIN front)45 × 45
CD40148 × 96 × 75 (1/8 DIN front)45 × 92
CD70172 × 72 × 7368 × 68
CD90196 × 96 × 66 (1/4 DIN front)92 × 92

Ordering & Selection Guide

Six positions after CD: panel size, control action, input & range, main output, then alarm codes (hyphen before output, star before alarms).

CD701①②③F④K02⑤−M⑥*A⑦B⑧

①②③ · Panel size (mm)

101
48×48×82 · cut-out 45×45
401
48×96×75 · cut-out 45×92
701
72×72×73 · cut-out 68×68
901
96×96×66 · cut-out 92×92

④ · Control action

F
PID with autotuning, reverse — heating
D
PID with autotuning, direct — cooling

⑤ · Input type and range

K02
K thermocouple
E02
E thermocouple
D10
Pt100 RTD
P10
Cu50 RTD

⑥ · Main output

M
Relay contact (RELAY)
V
Voltage pulse (SSR drive)
8
Current output 4–20 mA
Show alarm codes (⑦⑧ · 12 options: N, A–L)
N
No alarm configured
A
Upper deviation
B
Lower deviation
C
Upper and lower deviation
D
Deviation band
E
Upper deviation, hold action
F
Lower deviation, hold action
G
Upper and lower deviation, hold action
H
Process high (absolute)
J
Process low (absolute)
K
Process high, hold action
L
Process low, hold action

Worked example

CD701FK02-MAB

72×72×73 on a 68×68 cut-out, reverse action for heating, K thermocouple input, relay output, an upper deviation alarm on the first relay and a lower deviation alarm on the second.

What each bezel is ordered as

Every size comes in the same four versions, so two decisions describe the instrument completely: the panel size, and the version fitted to it. The input is fixed at the factory and cannot be changed later.

  • K thermocouple, dual outputTwo independent outputs on one instrument
  • Pt100, dual outputThe same, for an RTD sensor rather than a thermocouple
  • Two alarm outputsWhere the machine has to signal out-of-band running
  • 4–20 mA outputRecording or a second controller in the loop

Against the CH series

The CD is the simpler of the two: four bezels rather than five, a one-second response and a relay output, and no communication option in the listing. Where a machine needs the fifth size, a faster sampling loop or Modbus, the CH series is the one to quote.

CDCH
Bezelsfour, 48 to 96 squarefive, including the 48 × 48 CH102
Responseone secondhalf-second sampling period
Accuracyconfirmed per order±0.5% or ±1.0% of span
Communicationnot offered in the listingnone on CH either; REX and TC4 carry it
Where it winsthe cheapest way to hold a setpointtighter loop on fast loads

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

CD101

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

CD401

48 × 96mm (1/8 DIN) · cut-out 45 × 92mm

CD501

96 × 48mm (1/8 DIN) · cut-out 92 × 45mm

CD701

72 × 72mm · cut-out 68 × 68mm

CD901

96 × 96mm (1/4 DIN) · cut-out 92 × 92mm

Input codes and measuring ranges

Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.

③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
InputCode and measuring range
KThermocouple
K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C
JThermocouple
J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C
RThermocouple (accuracy not guaranteed over 0–399 °C)
R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C
SThermocouple (accuracy not guaranteed over 0–399 °C)
S01 0–1600 °CS02 0–1769 °C
BThermocouple (accuracy not guaranteed over 0–399 °C)
B01 400–1800 °CB02 0–1769 °C
EThermocouple
E01 0–800 °CE02 0–1000 °C
NThermocouple
N01 1–1300 °CN02 0–1300 °C
TThermocouple (accuracy held from −199 to 100 °C)
T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C
PT100RTD
D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C
Cu50RTD
P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C
0–5VDCStandard signal
401 0.0–100.0
1–5VDCStandard signal
601 0.0–100.0
0–20mAStandard signal, 250 Ω resistor across the terminals
701 0.0–100.0
4–20mAStandard signal, 250 Ω resistor across the terminals
801 0.0–100.0

Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.

Wiring

The range on one sheet, body by body: a contactor arrangement, a solid state relay arrangement and an alarm light for each, with the electrician's diagram and the terminal reference beside them. The circuit repeats; the terminal numbers do not, so read the panel that matches your case.

CD series · wiring, schematics and terminal references

CD series · wiring, schematics and terminal references

Check the jumper before powering up: 2–4 on the contactor version, 2–8 on the alarm version, and none on the SSR version, where 7 (+) and 3 (−) carry a 12 VDC drive rather than a contact. On the relay versions the common sits on 2, so the supply terminal feeding it is the one that must be linked.

Download the sheet (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the CD need?

48×48×82, 48×96×75, 72×72×73 and 96×96×66 mm. The cut-out is 45×45, 45×92, 68×68 and 92×92 mm

Which sensors can the CD read?

K thermocouple or Pt100

What output options does the CD have?

relay contact, SSR drive or 4–20 mA, chosen by code

What supply voltage does the CD need?

100–240 VAC, 220 V nominal

How accurate is the CD?

±1 °C

Does the CD have alarm outputs?

no alarm, upper and lower deviation, upper, or lower, per relay