Temperature Controllers

CH402FK02-M*AN — CH402 with built-in electromechanical relay

The version to order when the controller only has to close a contactor coil, or a small heater under 3A.

CH temperature controller, dual LED display for PV and SV, CH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902…
CH: Dual LED display for PV and SV; CH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902 96×96mm; Thermocouple K, J, R, S, B, E, N, T and W5Re/W26Re.
Output
Built-in electromechanical relay, 250VAC 3A, dry contact
Bezel
48 × 96
Panel cut-out
45 × 92
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesCH (REX-CH) Series short-body PID temperature controller
ModelsCH102 / CH402 / CH502 / CH702 / CH902
InputThermocouple K, J, R, S, B, E, N, T and W5Re/W26Re; RTD Pt100, JPt100 and Cu50; linear 0–5V, 1–5V, 0–20mA, 4–20mA. Ranges: K 0–1372, R 0–1700, S 0–1769, B 0–1820, WRe 0–2320, Pt100 and JPt100 −199.9–649 °C
DisplayDual LED display for PV and SV
Control methodPID control and ON/OFF (hysteresis) control; reverse-acting (F) or direct-acting (D)
Control outputN none; M relay contact; V SSR drive voltage pulse; 8 current output; T SCR zero-crossing; G SCR phase-angle pulse
Alarm outputALM1 and ALM2; N none or selectable A–L modes (deviation, band, absolute value and standby variants)
Supply voltage220VAC, 50/60Hz
Accuracy±0.5%FS or ±1.0%FS
Sampling period0.5s
Alarm rangefreely settable across the full range
Operating environment0–50℃; 30–85% RH, no corrosive gas
Panel sizeCH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902 96×96mm
Panel cutoutCH102 45×45; CH402 45×92; CH502 92×45; CH702 68×68; CH902 92×92mm
Dimensions (body)Two bodies under the same model number: short case 78mm and long case 100mm behind the panel
Body optionsCH short case 78mm; CD long case 100mm, ordered as CD101 / CD401 / CD501 / CD701 / CD901

Product overview

Part no. SE-CH102industry model CH102

Also known as: RKC CH102 · CH series PID temperature controller · CH102 temperature controller · controlador de temperatura CH

CH Series PID temperature controllers are designed for stable and accurate temperature control in industrial equipment such as injection molding machines, packaging machines, industrial ovens, heat sealing machines and extrusion equipment. The series includes CH102, CH402, CH502, CH702 and CH902 models, supporting PID control, auto-tuning, relay/SSR output, dual alarm, K/E/PT100 input and optional MV+AN customized output functions.

Ordering code

CH402FK02-M*AN

The version to order when the controller only has to close a contactor coil, or a small heater under 3A.

Order codeCH402FK02-M*AN
Bezel (mm)48 × 96
Cut-out (mm)45 × 92
OutputBuilt-in electromechanical relay, 250VAC 3A, dry contact
Output terminals3 – 4
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
1CH40248 × 96 mm (1/8 DIN) bezel on a 45 × 92mm panel cut-out
2FControl mode: reverse acting, the usual choice for heating
3K02Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50
4MBuilt-in electromechanical relay, 250VAC 3A, dry contact
5*ANAlarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead
Output terminals: 3 – 4·Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR

Key features

  • High-contrast dual LED display for real-time process and setpoint values
  • PID auto-tuning for precise control
  • Multiple form factors to fit various panel configurations
  • Reliable and cost-effective for OEM and industrial use

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

Six positions after CH: panel size, control action, input & range, main output, then alarm codes. Every size shares the same code positions.

CH702①F②K02③−M④A⑤B⑥

① · Panel size (mm)

102
48×48×82 · cut-out 45×45
402
48×96×75 · cut-out 45×92
502
96×48×75 · cut-out 92×45
702
72×72×73 · cut-out 68×68
902
96×96×73 · cut-out 92×92

② · Control action

F
PID, reverse action — heating
D
PID, direct action — cooling

③ · Input type and range

K02
K thermocouple
E02
E thermocouple
D10
Pt100 RTD
P10
Cu50 RTD

④ · Main output

M
Relay contact (RELAY)
V
Voltage pulse (SSR drive)
8
Current output 4–20mA (control)
Show alarm codes (⑤⑥ · 12 options: N, A–L)
N
No alarm configured
A
Deviation high (upper)
B
Deviation low (lower)
C
Deviation high and low
D
Deviation band
E
Deviation high, hold action
F
Deviation low, hold action
G
Deviation high and low, hold action
H
Process high (absolute)
J
Process low (absolute)
K
Process high, hold action
L
Process low, hold action

Worked example

CH702FK02-MAB

72×72×73 on a 68×68 cut-out, reverse action for heating, K thermocouple input, relay output, an upper deviation alarm on the first relay and a lower deviation alarm on the second.

Output types and what goes with them

OutputRatingOrder with it
Electromagnetic relay3 A at 250 VAC, resistive—
SSR drive, 12 VDCDrives a solid state relay; the module carries the loadSSR-DA single phase 10–40 A
Current output, 4–20 mAInto a controller or recorder input—
SCR / triac, zero-crossPhase-angle or zero-cross firingBDTY SCR voltage regulator

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

CH102

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

CH402

48 × 96mm (1/8 DIN) · cut-out 45 × 92mm

CH502

96 × 48mm (1/8 DIN) · cut-out 92 × 45mm

CH702

72 × 72mm · cut-out 68 × 68mm

CH902

96 × 96mm (1/4 DIN) · cut-out 92 × 92mm

Input codes and measuring ranges

Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.

③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
InputCode and measuring range
KThermocouple
K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C
JThermocouple
J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C
RThermocouple (accuracy not guaranteed over 0–399 °C)
R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C
SThermocouple (accuracy not guaranteed over 0–399 °C)
S01 0–1600 °CS02 0–1769 °C
BThermocouple (accuracy not guaranteed over 0–399 °C)
B01 400–1800 °CB02 0–1769 °C
EThermocouple
E01 0–800 °CE02 0–1000 °C
NThermocouple
N01 1–1300 °CN02 0–1300 °C
TThermocouple (accuracy held from −199 to 100 °C)
T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C
PT100RTD
D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C
Cu50RTD
P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C
0–5VDCStandard signal
401 0.0–100.0
1–5VDCStandard signal
601 0.0–100.0
0–20mAStandard signal, 250 Ω resistor across the terminals
701 0.0–100.0
4–20mAStandard signal, 250 Ω resistor across the terminals
801 0.0–100.0

Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.

Panel and keys

The CH702 front panel puts the measured value (PV) above the setpoint (SV), with five status lamps — AT, OUT1, OUT2, ALM1, ALM2 — between the displays and the keys. Four keys sit along the bottom: SET, shift (R/S), decrease and increase. The diagram calls out each control.

CH702 front panel: PV and SV displays, AT/OUT1/OUT2/ALM1/ALM2 indicators and SET, shift, decrease and increase keys
CH702 front-panel layout with each display, indicator and key called outOpen full diagram
Panel marking
PV
Process value (PV), upper display row
SV
Set value (SV), lower display row
AT
Auto-tuning indicator (AT)
OUT1 / OUT2
Control output indicators (OUT1 / OUT2)
ALM1 / ALM2
Alarm output indicators (ALM1 / ALM2)
SET
SET key — opens parameters and confirms edits
R/S
Shift key (R/S) — moves between digits
∨
Decrease key
∧
Increase key

Panel dimensions

Five panel sizes, each with its own cut-out and its own depth. The total depth includes the front bezel; the body depth is what has to fit behind the panel line, and that is the figure to design the enclosure around.

ModelPanel (mm)Cut-out (mm)Total depthBody depth
CH10248 × 4845 × 4582mm73mm
CH40248 × 9645 × 9275mm66mm
CH50296 × 4892 × 4575mm66mm
CH70272 × 7268 × 6873mm64mm
CH90296 × 9692 × 9273mm64mm

Wiring

One sheet for the whole range, body by body: each case gets a contactor arrangement, a solid state relay arrangement and an alarm light, with the terminal reference printed beside it. The circuit is the same idea every time; the terminal numbers are not, so read the panel that matches your case.

CH series · wiring and terminal references

CH series · wiring and terminal references

The jumper is the part to check before powering up: the contactor version links the supply terminal to the relay common, the alarm version links it to the alarm common, and the SSR version links nothing because its output pair is a 12 VDC drive rather than a contact. Sensor leads keep their colours on every body — red to the signal terminal, blue to its pair.

Download the sheet (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the CH need?

CH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902 96×96mm. The cut-out is CH102 45×45; CH402 45×92; CH502 92×45; CH702 68×68; CH902 92×92mm

Which sensors can the CH read?

K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD — 10 selectable ranges (input code, e.g. K02)

What output options does the CH have?

N none; M relay contact; V SSR drive voltage pulse; 8 current output; T SCR zero-crossing; G SCR phase-angle pulse

What supply voltage does the CH need?

220VAC, 50/60Hz

How accurate is the CH?

±0.5%FS or ±1.0%FS

Does the CH have alarm outputs?

ALM1 and ALM2; N none or selectable A–L modes (deviation, band, absolute value and standby variants)

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.