Temperature Controllers
CH402FK02-8*AN — CH402 with analogue current output
The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.

- Output
- Analogue current output, 4–20mA (0–10mA on request)
- Bezel
- 48 × 96
- Panel cut-out
- 45 × 92
Technical specifications
| Series | CH (REX-CH) Series short-body PID temperature controller |
|---|---|
| Models | CH102 / CH402 / CH502 / CH702 / CH902 |
| Input | Thermocouple K, J, R, S, B, E, N, T and W5Re/W26Re; RTD Pt100, JPt100 and Cu50; linear 0–5V, 1–5V, 0–20mA, 4–20mA. Ranges: K 0–1372, R 0–1700, S 0–1769, B 0–1820, WRe 0–2320, Pt100 and JPt100 −199.9–649 °C |
| Display | Dual LED display for PV and SV |
| Control method | PID control and ON/OFF (hysteresis) control; reverse-acting (F) or direct-acting (D) |
| Control output | N none; M relay contact; V SSR drive voltage pulse; 8 current output; T SCR zero-crossing; G SCR phase-angle pulse |
| Alarm output | ALM1 and ALM2; N none or selectable A–L modes (deviation, band, absolute value and standby variants) |
| Supply voltage | 220VAC, 50/60Hz |
| Accuracy | ±0.5%FS or ±1.0%FS |
| Sampling period | 0.5s |
| Alarm range | freely settable across the full range |
| Operating environment | 0–50℃; 30–85% RH, no corrosive gas |
| Panel size | CH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902 96×96mm |
| Panel cutout | CH102 45×45; CH402 45×92; CH502 92×45; CH702 68×68; CH902 92×92mm |
| Dimensions (body) | Two bodies under the same model number: short case 78mm and long case 100mm behind the panel |
| Body options | CH short case 78mm; CD long case 100mm, ordered as CD101 / CD401 / CD501 / CD701 / CD901 |
Product overview
Part no. SE-CH102industry model CH102
Also known as: RKC CH102 · CH series PID temperature controller · CH102 temperature controller · controlador de temperatura CH
CH Series PID temperature controllers are designed for stable and accurate temperature control in industrial equipment such as injection molding machines, packaging machines, industrial ovens, heat sealing machines and extrusion equipment. The series includes CH102, CH402, CH502, CH702 and CH902 models, supporting PID control, auto-tuning, relay/SSR output, dual alarm, K/E/PT100 input and optional MV+AN customized output functions.
Ordering code
CH402FK02-8*AN
The version to order when the heater is controlled by an SCR power regulator, or when the set point has to be sent to a PLC.
| Order code | CH402FK02-8*AN |
|---|---|
| Bezel (mm) | 48 × 96 |
| Cut-out (mm) | 45 × 92 |
| Output | Analogue current output, 4–20mA (0–10mA on request) |
| Output terminals | 3 (+) – 4 (−) |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue input
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Reading this order code
How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.
| Position | Reads | Meaning |
|---|---|---|
| 1 | CH402 | 48 × 96 mm (1/8 DIN) bezel on a 45 × 92mm panel cut-out |
| 2 | F | Control mode: reverse acting, the usual choice for heating |
| 3 | K02 | Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50 |
| 4 | 8 | Analogue current output, 4–20mA (0–10mA on request) |
| 5 | *AN | Alarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead |
Key features
- High-contrast dual LED display for real-time process and setpoint values
- PID auto-tuning for precise control
- Multiple form factors to fit various panel configurations
- Reliable and cost-effective for OEM and industrial use
Works with
The parts that go into the same panel and are usually ordered with it.
Ordering & Selection Guide
Six positions after CH: panel size, control action, input & range, main output, then alarm codes. Every size shares the same code positions.
① · Panel size (mm)
- 102
- 48×48×82 · cut-out 45×45
- 402
- 48×96×75 · cut-out 45×92
- 502
- 96×48×75 · cut-out 92×45
- 702
- 72×72×73 · cut-out 68×68
- 902
- 96×96×73 · cut-out 92×92
② · Control action
- F
- PID, reverse action — heating
- D
- PID, direct action — cooling
③ · Input type and range
- K02
- K thermocouple
- E02
- E thermocouple
- D10
- Pt100 RTD
- P10
- Cu50 RTD
④ · Main output
- M
- Relay contact (RELAY)
- V
- Voltage pulse (SSR drive)
- 8
- Current output 4–20mA (control)
Show alarm codes (⑤⑥ · 12 options: N, A–L)
- N
- No alarm configured
- A
- Deviation high (upper)
- B
- Deviation low (lower)
- C
- Deviation high and low
- D
- Deviation band
- E
- Deviation high, hold action
- F
- Deviation low, hold action
- G
- Deviation high and low, hold action
- H
- Process high (absolute)
- J
- Process low (absolute)
- K
- Process high, hold action
- L
- Process low, hold action
Worked example
CH702FK02-MAB
72×72×73 on a 68×68 cut-out, reverse action for heating, K thermocouple input, relay output, an upper deviation alarm on the first relay and a lower deviation alarm on the second.
Output types and what goes with them
| Output | Rating | Order with it |
|---|---|---|
| Electromagnetic relay | 3 A at 250 VAC, resistive | — |
| SSR drive, 12 VDC | Drives a solid state relay; the module carries the load | SSR-DA single phase 10–40 A |
| Current output, 4–20 mA | Into a controller or recorder input | — |
| SCR / triac, zero-cross | Phase-angle or zero-cross firing | BDTY SCR voltage regulator |
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
Input codes and measuring ranges
Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
| Input | Code and measuring range |
|---|---|
| KThermocouple | K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C |
| JThermocouple | J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C |
| RThermocouple (accuracy not guaranteed over 0–399 °C) | R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C |
| SThermocouple (accuracy not guaranteed over 0–399 °C) | S01 0–1600 °CS02 0–1769 °C |
| BThermocouple (accuracy not guaranteed over 0–399 °C) | B01 400–1800 °CB02 0–1769 °C |
| EThermocouple | E01 0–800 °CE02 0–1000 °C |
| NThermocouple | N01 1–1300 °CN02 0–1300 °C |
| TThermocouple (accuracy held from −199 to 100 °C) | T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C |
| PT100RTD | D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C |
| Cu50RTD | P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C |
| 0–5VDCStandard signal | 401 0.0–100.0 |
| 1–5VDCStandard signal | 601 0.0–100.0 |
| 0–20mAStandard signal, 250 Ω resistor across the terminals | 701 0.0–100.0 |
| 4–20mAStandard signal, 250 Ω resistor across the terminals | 801 0.0–100.0 |
Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.
Panel and keys
The CH702 front panel puts the measured value (PV) above the setpoint (SV), with five status lamps — AT, OUT1, OUT2, ALM1, ALM2 — between the displays and the keys. Four keys sit along the bottom: SET, shift (R/S), decrease and increase. The diagram calls out each control.
- PV
- Process value (PV), upper display row
- SV
- Set value (SV), lower display row
- AT
- Auto-tuning indicator (AT)
- OUT1 / OUT2
- Control output indicators (OUT1 / OUT2)
- ALM1 / ALM2
- Alarm output indicators (ALM1 / ALM2)
- SET
- SET key — opens parameters and confirms edits
- R/S
- Shift key (R/S) — moves between digits
- ∨
- Decrease key
- ∧
- Increase key
Panel dimensions
Five panel sizes, each with its own cut-out and its own depth. The total depth includes the front bezel; the body depth is what has to fit behind the panel line, and that is the figure to design the enclosure around.
| Model | Panel (mm) | Cut-out (mm) | Total depth | Body depth |
|---|---|---|---|---|
| CH102 | 48 × 48 | 45 × 45 | 82mm | 73mm |
| CH402 | 48 × 96 | 45 × 92 | 75mm | 66mm |
| CH502 | 96 × 48 | 92 × 45 | 75mm | 66mm |
| CH702 | 72 × 72 | 68 × 68 | 73mm | 64mm |
| CH902 | 96 × 96 | 92 × 92 | 73mm | 64mm |
Wiring
One sheet for the whole range, body by body: each case gets a contactor arrangement, a solid state relay arrangement and an alarm light, with the terminal reference printed beside it. The circuit is the same idea every time; the terminal numbers are not, so read the panel that matches your case.
CH series · wiring and terminal references
The jumper is the part to check before powering up: the contactor version links the supply terminal to the relay common, the alarm version links it to the alarm common, and the SSR version links nothing because its output pair is a 12 VDC drive rather than a contact. Sensor leads keep their colours on every body — red to the signal terminal, blue to its pair.
Documents for this family
- Strong Electric CH CD Instruction Manual420 KB · 2026-11-16
- CH series wiring306 KB · 2026-11-18
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the CH need?
CH102 48×48; CH402 48×96; CH502 96×48; CH702 72×72; CH902 96×96mm. The cut-out is CH102 45×45; CH402 45×92; CH502 92×45; CH702 68×68; CH902 92×92mm
Which sensors can the CH read?
K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD — 10 selectable ranges (input code, e.g. K02)
What output options does the CH have?
N none; M relay contact; V SSR drive voltage pulse; 8 current output; T SCR zero-crossing; G SCR phase-angle pulse
What supply voltage does the CH need?
220VAC, 50/60Hz
How accurate is the CH?
±0.5%FS or ±1.0%FS
Does the CH have alarm outputs?
ALM1 and ALM2; N none or selectable A–L modes (deviation, band, absolute value and standby variants)
Related guides
How to Wire CH102, CH402, CH702 and CH902 PID Temperature Controllers
A practical wiring guide for CH102, CH402, CH702 and CH902 PID temperature controllers, covering power, AC contactor and SSR control, thermocouple and Pt100 sensors, alarms and…
Read guide Product Updates · 2025-04-11TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guide Technical Guides · 2025-04-11TCR Controller Selection for a Packaging Tunnel Dryer
An illustrative application note on selecting a TCR Series controller for a packaging tunnel dryer, including sensor, relay-load and over-temperature protection checks.
Read guideRelated models
All Temperature Controllers
REX-C100/C400/C700/C900 Digital PID Temperature Controller
SE-C100
REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and…
View details
C700 Digital Temperature Controller, 72 × 72mm Panel Frame | Strong Electric
SE-C700
72×72mm · 68×68mm · 24mm overall, 20mm of it behind the panel
View details
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.