AC Contactors

CJX2-F Three Pole Contactor

The F frames in three poles: 115 A to 330 A in AC-3, with the contact groups and star-delta kits that match each frame size.

CJX2-F contactor, AC-3 rated current at up to 440 V, AC-1 rated current at 40 °C…
CJX2-F: AC-3 rated current at up to 440 V, AC-1 rated current at 40 °C…; Circuits up to 660 V working voltage and 800 A rated current, 50 or 60 Hz.
Use
Circuits up to 660 V working voltage and 800 A rated current, 50 or 60 Hz; frequent starting and remote switching
Combination
Pairs with auxiliary contact groups, air delay heads, mechanical interlocks, star-delta starters and thermal overload relays
Contacts
Main contacts normally open, three or four per frame according to the model
Insulation
Rated insulation voltage 1000 V, rated impulse withstand 8 kV, rated operational voltage 1000 V
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesCJX2-F large capacity contactor, three pole
UseCircuits up to 660 V working voltage and 800 A rated current, 50 or 60 Hz; frequent starting and remote switching
CombinationPairs with auxiliary contact groups, air delay heads, mechanical interlocks, star-delta starters and thermal overload relays
ContactsMain contacts normally open, three or four per frame according to the model
InsulationRated insulation voltage 1000 V, rated impulse withstand 8 kV, rated operational voltage 1000 V
StandardIEC 60947-4-1, GB 14048.4 and EN 60947-4-1
FrequencyAC-1, AC-2 and AC-3 at 1200 or 600 operations an hour; AC-4 at 300
FuseSCPD fuse fitted as listed per frame
RatingsAC-3 rated current at up to 440 V, AC-1 rated current at 40 °C, and conventional thermal current, with AC-3 power tabulated at 220/240, 380/400, 415, 440, 500, 660/690 and 1000 V
CJX2-F115115 A in AC-3 · 200 A in AC-1 · Ith 200 A · 30 kW at 220/240 V · 55 kW at 380/400 V · 59 kW at 415 V · 59 kW at 440 V · 75 kW at 500 V · 80 kW at 660/690 V · 65 kW at 1000 V · screw Φ6 · 10 N·m · fuse RT16-2 250 A
CJX2-F150150 A in AC-3 · 250 A in AC-1 · Ith 250 A · 40 kW at 220/240 V · 75 kW at 380/400 V · 80 kW at 415 V · 80 kW at 440 V · 90 kW at 500 V · 100 kW at 660/690 V · 65 kW at 1000 V · screw Φ8 · 18 N·m · fuse RT16-2 355 A
CJX2-F185185 A in AC-3 · 275 A in AC-1 · Ith 275 A · 55 kW at 220/240 V · 90 kW at 380/400 V · 100 kW at 415 V · 100 kW at 440 V · 110 kW at 500 V · 110 kW at 660/690 V · 100 kW at 1000 V · screw Φ8 · 18 N·m · fuse RT16-3 425 A
CJX2-F225225 A in AC-3 · 315 A in AC-1 · Ith 315 A · 63 kW at 220/240 V · 110 kW at 380/400 V · 110 kW at 415 V · 110 kW at 440 V · 129 kW at 500 V · 129 kW at 660/690 V · 100 kW at 1000 V · screw Φ10 · 35 N·m · fuse RT16-3 500 A
CJX2-F265265 A in AC-3 · 350 A in AC-1 · Ith 350 A · 75 kW at 220/240 V · 132 kW at 380/400 V · 140 kW at 415 V · 140 kW at 440 V · 160 kW at 500 V · 160 kW at 660/690 V · 147 kW at 1000 V · screw Φ10 · 35 N·m · fuse RT16-3 630 A
CJX2-F330330 A in AC-3 · 400 A in AC-1 · Ith 400 A · 100 kW at 220/240 V · 160 kW at 380/400 V · 180 kW at 415 V · 200 kW at 440 V · 200 kW at 500 V · 220 kW at 660/690 V · 160 kW at 1000 V · screw Φ10 · 35 N·m · fuse RT16-4 800 A
CJX2-F400400 A in AC-3 · 500 A in AC-1 · Ith 450 A · 110 kW at 220/240 V · 200 kW at 380/400 V · 220 kW at 415 V · 250 kW at 440 V · 257 kW at 500 V · 280 kW at 660/690 V · 185 kW at 1000 V · 35 · fuse RT16-4 800 A
CJX2-F500500 A in AC-3 · 700 A in AC-1 · Ith 630 A · 147 kW at 220/240 V · 250 kW at 380/400 V · 280 kW at 415 V · 295 kW at 440 V · 355 kW at 500 V · 335 kW at 660/690 V · 335 kW at 1000 V · Φ10, 35 · fuse RT16-4 1000 A
CJX2-F630630 A in AC-3 · 1000 A in AC-1 · Ith 800 A · 220 kW at 220/240 V · 335 kW at 380/400 V · 375 kW at 415 V · 400 kW at 440 V · 400 kW at 500 V · 450 kW at 660/690 V · 450 kW at 1000 V · Φ12, 58 · fuse RT16-4 1250 A
CJX2-F780780 A in AC-3 · 1600 A in AC-1 · Ith 1000 A · 220 kW at 220/240 V · 400 kW at 380/400 V · 425 kW at 415 V · 425 kW at 440 V · 450 kW at 500 V · 475 kW at 660/690 V · 475 kW at 1000 V · Φ12, 58 · fuse RT16 1250 A
CJX2-F800800 A in AC-3 · 1600 A in AC-1 · Ith 1000 A · 220 kW at 220/240 V · 400 kW at 380/400 V · 425 kW at 415 V · 450 kW at 440 V · 450 kW at 500 V · 475 kW at 660/690 V · 450 kW at 1000 V · Φ12, 58 · fuse RT16 1250 A

Product overview

Part no. SE-CJX2-F-2

Also known as: Chint CJX2-F · CJX2-F contactor · CJX2-F AC contactor

The large F frame in three poles, for the circuits that carry a whole machine rather than a motor: a hundred and fifteen to three hundred and thirty amps in AC-3, up to a thousand volts, with matching auxiliary groups, delay heads and star-delta kits.

Key features

  • 115 A to 330 A in AC-3
  • Up to 1000 V rated operational voltage
  • Star-delta and interlock kits available

Works with

The parts that go into the same panel and are usually ordered with it.

Supply & OEM

Available with your logoMOQ 20 units·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Related models

All AC Contactors

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.