Temperature Controllers

E5C2 / E5C4 Series Analogue-Set Temperature Controller

E5C2 and E5C4 analogue-set controllers set on a dial or thumbwheel, ±1°C accuracy, a 10A relay and a 48×48 front for a 45×45mm cutout.

E5C4 above with its three-digit thumbwheel, E5C2 below with the pointer dial
E5C4 on top with its thumbwheel and three-digit readout, E5C2 below with the pointer dial and the 0 to 400 scale.
Panel size
48×48mm (1/16 DIN)
Panel cutout
45×45mm
Control output
Relay only
Supply voltage
220VAC, 50/60Hz
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesE5C2 / E5C4 Series (analogue-set panel-mount temperature controller)
ModelsE5C2 (time-proportioning) and E5C4 (ON/OFF position control), each with or without a socket base; Pt100 build available on E5C4
Setting methodE5C2 sets on a rotary knob against a printed dial scale, with no display. E5C4 sets on a three-digit thumbwheel beneath a digital window that reads the measured value; a screwdriver trimmer marked RES sits to the right of the digits. The two fronts are not interchangeable — state the model when ordering
Control methodE5C2 time-proportioning (PID); E5C4 ON/OFF position control
InputK thermocouple as standard; Pt100 on the E5C4 build
Temperature rangeE5C2 0–400°C (0–200°C build also offered); E5C4 0–399°C or 0–999°C
Control outputRelay only
Relay contact rating10A contact, 800W resistive load
Alarm outputNone
Supply voltage220VAC, 50/60Hz
Accuracy±1°C
Parameter retentionSetpoint held after power-off
Panel size48×48mm (1/16 DIN)
Panel cutout45×45mm
Dimensions (depth)86mm behind the bezel; 107mm including the socket base
MountingPanel mount, snap-in clip; the base version also mounts on DIN rail
CertificationCE

Product overview

Part no. SE-E5C2

Also known as: Omron E5C2 · E5C2 temperature controller · E5C2 On/Off dial temperature controller · E5C2 controlador de temperatura

E5C2 and E5C4 are the small analogue-set controllers: the setpoint is turned or dialled in on the front rather than typed into a menu, and the whole instrument fits a 48×48mm front on a 45×45mm cutout. E5C2 sets on a pointer dial and controls by time proportioning, which holds a temperature smoothly on a small heater; E5C4 sets on a three-digit thumbwheel beside a digital readout and switches ON/OFF, which suits a solenoid, a fan or a heater with its own thermostat. Both use a 10A relay, and a Pt100 version is available on E5C4.

Key features

  • Pointer dial on E5C2, three-digit thumbwheel beside a digital readout on E5C4
  • E5C2 time proportioning, E5C4 ON/OFF position control
  • ±1°C accuracy, 10A relay output
  • 48×48mm front, 45×45mm cutout
  • K thermocouple standard; Pt100 version available on E5C4
  • Socket-base version mounts on DIN rail as well as in a panel
  • 220VAC supply
  • CE marked

Works with

The parts that go into the same panel and are usually ordered with it.

Terminal connections and wiring

Eight terminals: supply on 7 and 8, the sensor on 1 and 2 — with 3 as the third wire on Pt100 versions — and a changeover relay on 4, 5 and 6. The contact is dry, so the live is looped from 7 to 4 and the load is taken off 5: 4 is the common, 5 closes on heating and 6 is the normally-closed side.

E5C2 / E5C4220VAC supply7 live · 8 neutralHeating elementThermocouple−+jumper87654321NL
LiveNeutralSensor signal

Wiring notes

  • 7 and 8 take the 220VAC supply. The link from 7 to 4 is not optional on a heating version — without it the common of the relay is floating and the contact switches nothing.
  • On K type, the red lead is positive and goes to 1, the other to 2. On Pt100 the red goes to 3 and the remaining two to 1 and 2 — that is what makes it a three-wire measurement rather than a two-wire one.
  • 5 is the heating contact and 6 the cooling one. Only one of them can be used at a time: the relay rests on 6 and pulls in on 5.
  • The contact is rated 5A at 250 VAC. Above that, or on any inductive load, let 5 drive a contactor coil instead of the load itself.

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the E5C2 / E5C4 need?

48×48mm (1/16 DIN). The cut-out is 45×45mm

Which sensors can the E5C2 / E5C4 read?

K thermocouple as standard; Pt100 on the E5C4 build

What output options does the E5C2 / E5C4 have?

Relay only

What supply voltage does the E5C2 / E5C4 need?

220VAC, 50/60Hz

How accurate is the E5C2 / E5C4?

±1°C

Does the E5C2 / E5C4 have alarm outputs?

None

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.