Phase Failure Relay vs Voltage Protector: A Selection and Wiring Guide
A phase relay catches missing phases and wrong rotation; a voltage protector catches sags, surges and generator swings. This guide compares the duties, matches XJ3-G, XJ3-D, RST25, JVM, AVP and SZ-3LVA models to each fault, and gives a wiring and commissioning sequence that puts the output contact in series with the contactor coil.
Lose one supply leg and a three-phase motor keeps turning while the other two lines carry more current. Swap two phases and the pump runs backwards. Let the voltage drift and all three phases stay present while the winding heats anyway. These faults need different remedies, but they are often grouped under "motor protection". A phase-failure relay and an over/under-voltage protector are not interchangeable.
This guide maps Strong Electric models to each duty using published specifications and shows the wiring sequence that makes the protection real. The decisive point is at the output: these relays carry a small control current, and the contact sits in series with the contactor coil.
Isolate and lock off the supply; verify zero voltage at the relay and contactor. Output contacts below suit small resistive control loads, never motor current. Terminal numbers differ, so use the diagram for the exact model. A protector that re-closes automatically is not a restart interlock; add a deliberate reset where the machine must stay stopped.

What a phase relay actually catches
A phase relay checks phase presence and order, not load current. When one line opens, a running motor still turns but the remaining lines carry more current. From power balance, each carries about √3, or 1.73, times its balanced current: 10 A per phase becomes roughly 17 A in two live legs, beyond what a 10 A thermal setting tolerates for long.
Two phases swapped at a changeover or during cable work reverse every motor on the circuit. A sequence relay blocks the contactor until the order is corrected.
It does not watch voltage level. The XJ3-G version C covers phase failure and sequence; versions D and E add voltage unbalance, not an over- or under-voltage trip. A steady 320 V on a 380 V system with balanced phases can run for a long time without response. That is a different fault.
What a voltage protector adds
A voltage protector watches supply level, and often current, and drops the load when either leaves an acceptable window: brownouts, sags, sustained over-voltage and unstable generator supply.
The XJ3-D covers a 380 V three-phase system: under-voltage AC 300-380 V with a 2-9 s adjustable delay, over-voltage AC 380-460 V with a 1.5-4 s delay, plus phase failure and wrong sequence in one unit. The delays ride through short dips.
The JVM-2 is a three-phase 220 V AC, 50/60 Hz monitor with two dials setting 5 to 20 percent either side of rated voltage and one normally open output. It belongs ahead of a contactor, not in place of an overload.
AVP-63A and its single-phase siblings add an adjustable 1-63 A over-current setting; SZ-3LVA shows each phase and carries the same 1-63 A window. These protect one load, not just the incoming supply.
Side-by-side comparison
The quickest way to narrow the choice is to ask which fault you are trying to prevent.
| Question | Phase relay | Voltage protector |
| Missing one phase | Core duty | Combined models such as XJ3-D |
| Reversed phase order | Core duty, blocks start | Combined models such as XJ3-D |
| Voltage unbalance | XJ3-G versions D and E | XJ3-D and three-phase displays |
| Low voltage | Not covered | Adjustable under-voltage window |
| High voltage | Not covered | Adjustable over-voltage window |
| Over-current | Not covered | AVP and SZ-3LVA: 1-63 A |
| Typical output | One NO + one NC, or one NO | One NO + one NC, or one NO |
If the supply is stable and the only risk is a lost phase or reversed rotation, a phase relay is simpler. If the supply wanders on a feeder or generator, the voltage window decides. A combined XJ3-D covers both where the panel has room.
Matching a model to the fault
Published specifications decide what a relay can do. This table follows canonical Motor Protection and Voltage Relays data; contact ratings are resistive at 250 V AC, for a control contact rather than an inductive load.
| Model | Protection | Adjustment | Output | Best fit |
| XJ3-G | C: phase failure and sequence; D/E: plus unbalance | None listed | 1 NO + 1 NC; 3 A; 82 × 45 × 106 mm | Three-phase 380 V, 50 Hz motor |
| XJ3-D | Over/under-voltage, phase failure, wrong sequence | Under 300-380 V / 2-9 s; over 380-460 V / 1.5-4 s | 1 NO + 1 NC; 3 A; 70 × 45 × 113 mm | 380 V system needing both duties |
| RST25 | Phase sequence only | None listed | 1 NO; 3 A; 75 × 45 × 75 mm | Compact panel, rotation risk only |
| JVM-1 | Phase failure and sequence | None listed | 1 NO; 3 A; 78 × 50 × 92 mm | 380 V 50/60 Hz monitoring |
| JVM-2 | Adjustable voltage window | 5 to 20 percent either side | 1 NO; 3 A; 78 × 50 × 92 mm | Three-phase 220 V supply |
| MK-05 | Current-sensing protection | Sensitivity 5-50 kΩ | 250 V AC, 5 A; 75 × 45 × 75 mm | Pump or fan protection by current |
| SZ-3LVA | Three-phase voltage and current | Under 140-210 V; over 240-300 V; 1-63 A | 1 VA or less; 91 × 102 × 52 mm | One load with per-phase display |
Two details catch people out: XJ3-G variants are not interchangeable, and AVP/SZ-3LVA windows are specified for 230-300 V supplies, not a 380 V board. For the full family see motor protection and voltage relays.
Wiring the output through the contactor coil
Every model above has a small control contact. The relay senses incoming three phases; its output contact sits in series with the start/stop circuit and the contactor coil. The contactor carries motor current.
- Isolate, lock off and confirm zero voltage at the incoming terminals and coil.
- Check coil current against the 3 A or 5 A resistive contact rating before wiring.
- Land L1, L2 and L3 sensing conductors on the supply side of the main contactor. Load-side sensing removes the relay's own supply when the contactor opens.
- Wire one output contact in series with the stop button, overload auxiliary contact and coil A1; return A2 to the control supply. Motor power stays through the main poles.
- Set voltage limits and delays, or confirm the phase-only model needs no setting. Record them on the panel schedule.
- Energise with the motor uncoupled and confirm the contactor pulls in on a healthy supply.
- Simulate a fault: remove one sensing fuse, swap two phases with the supply isolated, and move the supply outside the set voltage window. The contactor must drop out and stay out.
After testing, restore wiring and measure coil voltage at A1 to A2. A relay that trips but cannot re-energise the contactor usually has a sensing or coil-supply problem.
Setting thresholds and proving the trip
Start from the supply the motor was designed for. On a 380 V system using the XJ3-D, the under-voltage range is AC 300-380 V with a 2 to 9 s delay and the over-voltage range is AC 380-460 V with a 1.5 to 4 s delay. Set the low limit above the lowest starting voltage and the high limit below the insulation's continuous rating; if motor data is missing, use the nameplate tolerance with a margin.
The delay matters as much as the limit. A 2-second under-voltage delay drops a contactor for a disturbance a 9-second delay would ride through. Frequent short dips favour a longer delay; a generator that sags under load favours a short one.
A constant-power load draws more current as voltage falls, approximately I2 ≈ I1 × (V1 / V2): 10 A at 380 V becomes roughly 11.9 A at 320 V. Heating also depends on torque and slip, so measure running current where the number matters. Record each setting and date in the panel log.
Selection and wiring mistakes to avoid
- Buying a phase relay to solve a voltage problem. An XJ3-G version C will not react to a steady 320 V supply.
- Confusing the XJ3-G variants. Version C covers phase failure and sequence; D and E add unbalance.
- Sensing downstream of the contactor. The relay loses its own supply when the contactor opens.
- Switching the motor through the output contact. The published rating is 3 A at 250 V AC resistive on most models.
- Applying single-phase windows to a three-phase board. AVP is specified at AC 230-300 V; SZ-3LVA is the three-phase member.
- Treating a relay as a restart interlock. Many protectors re-close automatically; build reset into the control circuit.
Before handover, measure continuity through the output with a healthy supply and the motor stopped. A contact that never changes state means miswiring or the wrong voltage version.
Contact Strong Electric for a selection check
Send us the supply arrangement, motor voltage and full-load current, the symptoms and whether the panel is fed from the grid or a generator. We will confirm which of the XJ3-G, XJ3-D, RST25, JVM-2 or SZ-3LVA suits the fault. See the motor protection range and the contact page.