Phase Failure Relay vs Voltage Protector: A Selection and Wiring Guide

A phase relay catches missing phases and wrong rotation; a voltage protector catches sags, surges and generator swings. This guide compares the duties, matches XJ3-G, XJ3-D, RST25, JVM, AVP and SZ-3LVA models to each fault, and gives a wiring and commissioning sequence that puts the output contact in series with the contactor coil.

Lose one supply leg and a three-phase motor keeps turning while the other two lines carry more current. Swap two phases and the pump runs backwards. Let the voltage drift and all three phases stay present while the winding heats anyway. These faults need different remedies, but they are often grouped under "motor protection". A phase-failure relay and an over/under-voltage protector are not interchangeable.

This guide maps Strong Electric models to each duty using published specifications and shows the wiring sequence that makes the protection real. The decisive point is at the output: these relays carry a small control current, and the contact sits in series with the contactor coil.

Isolate and lock off the supply; verify zero voltage at the relay and contactor. Output contacts below suit small resistive control loads, never motor current. Terminal numbers differ, so use the diagram for the exact model. A protector that re-closes automatically is not a restart interlock; add a deliberate reset where the machine must stay stopped.

Two DIN-rail three-phase protection devices stacked vertically, a larger phase-failure relay above a smaller voltage protector, photographed on a near-white background

What a phase relay actually catches

A phase relay checks phase presence and order, not load current. When one line opens, a running motor still turns but the remaining lines carry more current. From power balance, each carries about √3, or 1.73, times its balanced current: 10 A per phase becomes roughly 17 A in two live legs, beyond what a 10 A thermal setting tolerates for long.

Two phases swapped at a changeover or during cable work reverse every motor on the circuit. A sequence relay blocks the contactor until the order is corrected.

It does not watch voltage level. The XJ3-G version C covers phase failure and sequence; versions D and E add voltage unbalance, not an over- or under-voltage trip. A steady 320 V on a 380 V system with balanced phases can run for a long time without response. That is a different fault.

What a voltage protector adds

A voltage protector watches supply level, and often current, and drops the load when either leaves an acceptable window: brownouts, sags, sustained over-voltage and unstable generator supply.

The XJ3-D covers a 380 V three-phase system: under-voltage AC 300-380 V with a 2-9 s adjustable delay, over-voltage AC 380-460 V with a 1.5-4 s delay, plus phase failure and wrong sequence in one unit. The delays ride through short dips.

The JVM-2 is a three-phase 220 V AC, 50/60 Hz monitor with two dials setting 5 to 20 percent either side of rated voltage and one normally open output. It belongs ahead of a contactor, not in place of an overload.

AVP-63A and its single-phase siblings add an adjustable 1-63 A over-current setting; SZ-3LVA shows each phase and carries the same 1-63 A window. These protect one load, not just the incoming supply.

Side-by-side comparison

The quickest way to narrow the choice is to ask which fault you are trying to prevent.

QuestionPhase relayVoltage protector
Missing one phaseCore dutyCombined models such as XJ3-D
Reversed phase orderCore duty, blocks startCombined models such as XJ3-D
Voltage unbalanceXJ3-G versions D and EXJ3-D and three-phase displays
Low voltageNot coveredAdjustable under-voltage window
High voltageNot coveredAdjustable over-voltage window
Over-currentNot coveredAVP and SZ-3LVA: 1-63 A
Typical outputOne NO + one NC, or one NOOne NO + one NC, or one NO

If the supply is stable and the only risk is a lost phase or reversed rotation, a phase relay is simpler. If the supply wanders on a feeder or generator, the voltage window decides. A combined XJ3-D covers both where the panel has room.

Matching a model to the fault

Published specifications decide what a relay can do. This table follows canonical Motor Protection and Voltage Relays data; contact ratings are resistive at 250 V AC, for a control contact rather than an inductive load.

ModelProtectionAdjustmentOutputBest fit
XJ3-GC: phase failure and sequence; D/E: plus unbalanceNone listed1 NO + 1 NC; 3 A; 82 × 45 × 106 mmThree-phase 380 V, 50 Hz motor
XJ3-DOver/under-voltage, phase failure, wrong sequenceUnder 300-380 V / 2-9 s; over 380-460 V / 1.5-4 s1 NO + 1 NC; 3 A; 70 × 45 × 113 mm380 V system needing both duties
RST25Phase sequence onlyNone listed1 NO; 3 A; 75 × 45 × 75 mmCompact panel, rotation risk only
JVM-1Phase failure and sequenceNone listed1 NO; 3 A; 78 × 50 × 92 mm380 V 50/60 Hz monitoring
JVM-2Adjustable voltage window5 to 20 percent either side1 NO; 3 A; 78 × 50 × 92 mmThree-phase 220 V supply
MK-05Current-sensing protectionSensitivity 5-50 kΩ250 V AC, 5 A; 75 × 45 × 75 mmPump or fan protection by current
SZ-3LVAThree-phase voltage and currentUnder 140-210 V; over 240-300 V; 1-63 A1 VA or less; 91 × 102 × 52 mmOne load with per-phase display

Two details catch people out: XJ3-G variants are not interchangeable, and AVP/SZ-3LVA windows are specified for 230-300 V supplies, not a 380 V board. For the full family see motor protection and voltage relays.

Wiring the output through the contactor coil

Every model above has a small control contact. The relay senses incoming three phases; its output contact sits in series with the start/stop circuit and the contactor coil. The contactor carries motor current.

  1. Isolate, lock off and confirm zero voltage at the incoming terminals and coil.
  2. Check coil current against the 3 A or 5 A resistive contact rating before wiring.
  3. Land L1, L2 and L3 sensing conductors on the supply side of the main contactor. Load-side sensing removes the relay's own supply when the contactor opens.
  4. Wire one output contact in series with the stop button, overload auxiliary contact and coil A1; return A2 to the control supply. Motor power stays through the main poles.
  5. Set voltage limits and delays, or confirm the phase-only model needs no setting. Record them on the panel schedule.
  6. Energise with the motor uncoupled and confirm the contactor pulls in on a healthy supply.
  7. Simulate a fault: remove one sensing fuse, swap two phases with the supply isolated, and move the supply outside the set voltage window. The contactor must drop out and stay out.

After testing, restore wiring and measure coil voltage at A1 to A2. A relay that trips but cannot re-energise the contactor usually has a sensing or coil-supply problem.

Setting thresholds and proving the trip

Start from the supply the motor was designed for. On a 380 V system using the XJ3-D, the under-voltage range is AC 300-380 V with a 2 to 9 s delay and the over-voltage range is AC 380-460 V with a 1.5 to 4 s delay. Set the low limit above the lowest starting voltage and the high limit below the insulation's continuous rating; if motor data is missing, use the nameplate tolerance with a margin.

The delay matters as much as the limit. A 2-second under-voltage delay drops a contactor for a disturbance a 9-second delay would ride through. Frequent short dips favour a longer delay; a generator that sags under load favours a short one.

A constant-power load draws more current as voltage falls, approximately I2 ≈ I1 × (V1 / V2): 10 A at 380 V becomes roughly 11.9 A at 320 V. Heating also depends on torque and slip, so measure running current where the number matters. Record each setting and date in the panel log.

Selection and wiring mistakes to avoid

  • Buying a phase relay to solve a voltage problem. An XJ3-G version C will not react to a steady 320 V supply.
  • Confusing the XJ3-G variants. Version C covers phase failure and sequence; D and E add unbalance.
  • Sensing downstream of the contactor. The relay loses its own supply when the contactor opens.
  • Switching the motor through the output contact. The published rating is 3 A at 250 V AC resistive on most models.
  • Applying single-phase windows to a three-phase board. AVP is specified at AC 230-300 V; SZ-3LVA is the three-phase member.
  • Treating a relay as a restart interlock. Many protectors re-close automatically; build reset into the control circuit.

Before handover, measure continuity through the output with a healthy supply and the motor stopped. A contact that never changes state means miswiring or the wrong voltage version.

Contact Strong Electric for a selection check

Send us the supply arrangement, motor voltage and full-load current, the symptoms and whether the panel is fed from the grid or a generator. We will confirm which of the XJ3-G, XJ3-D, RST25, JVM-2 or SZ-3LVA suits the fault. See the motor protection range and the contact page.

Questions this guide answers

Can an XJ3-G phase failure relay protect a motor from low voltage?
No. Version C covers phase failure and sequence, and versions D and E add voltage unbalance, but none of them specifies an under-voltage trip window. A steady low supply with all three phases present needs a voltage protector such as the XJ3-D, which has an adjustable under-voltage range.
Should the L1, L2 and L3 sensing wires connect before or after the contactor?
Connect them on the supply side. If sensing is taken from the load side, opening the contactor removes the relay's own supply, so it can never close again to restart the motor. The relay output contact belongs in series with the coil, while the sensing inputs see the incoming three phases.
When would I choose an XJ3-D instead of an RST25?
The RST25 handles phase sequence only, with one normally open contact. The XJ3-D adds over-voltage, under-voltage, phase failure and wrong sequence in one unit, with adjustable voltage windows and delays. Choose the RST25 where rotation direction is the only risk; choose the XJ3-D where the supply itself can drift.
How does a JVM-2 differ from an AVP or SZ-3LVA protector?
The JVM-2 is a three-phase 220 V AC monitor with two dials setting a window 5 to 20 percent either side of rated voltage and one normally open output. AVP and SZ-3LVA combine voltage limits with an adjustable 1-63 A over-current setting, so they protect a specific load rather than just monitor the supply.
Can I switch the motor directly through the relay output contact?
No. The published contact rating on most of these models is 3 A at 250 V AC, resistive. That suits a contactor coil, a lamp or a PLC input, not motor current. Route motor power through the contactor main poles and use the relay contact only in the control circuit.

More in Technical Guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.