Temperature Controllers

TC5-S, Pt100 RTD, dual output

The 48 × 48 mm (1/16 DIN) body with a pt100 rtd and dual output.

TC5 temperature controller, 4-digit dual-row LED: PV and SV, with °F / °C marks
TC5: 4-digit dual-row LED: PV and SV, with °F / °C marks; 48×48 / 48×96 / 96×48 / 72×72 / 96×96mm; Thermocouple K/J/E/T/N/S/R/B.
Output
Pt100 RTD, dual output
Bezel
48 × 48
Panel cut-out
45 × 45
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesTC5 Series (panel-mount PID temperature controller)
ModelsTC5S / TC5H / TC5W / TC5M / TC5L
Display4-digit dual-row LED: PV and SV, with °F / °C marks
Control methodPID control and ON/OFF (hysteresis) control
Program controlTC5P version only: 32-segment programmer with ramp rate (SPR), segment time and timer mode (STCY). Confirm the model code when ordering.
InputThermocouple K/J/E/T/N/S/R/B; RTD Pt100, Cu50; linear 0–20mA, 4–20mA, 0–5V, 1–5V
Control outputRelay + SSR drive (W), voltage output (1U/2U), current output (1A/2A), SCR trigger (T/P)
Alarm output0, 1 or 2 alarms (code 0 / 1 / 2)
CommunicationRS485 Modbus RTU optional (code C)
Supply voltage100–240VAC, 50/60Hz
Power consumptionMax. 8VA
Accuracy±0.5%FS or ±1.0%FS
Alarm rangefreely settable across the full range
Sampling period100ms
Relay lifeMechanical >2,500,000 operations; electrical >100,000 operations
Dielectric strength2000VAC, 50/60Hz, 1 minute
Memory retentionApprox. 10 years
Operating environment0–50℃; 30–85% RH, no corrosive gas
Panel size48×48 / 48×96 / 96×48 / 72×72 / 96×96mm
Panel cutout45×45 / 45×92 / 92×45 / 68×68 / 92×92mm
Dimensions (depth)75mm body + 4mm bezel

Product overview

Part no. SE-TC5

Also known as: Autonics TC5 · TC5 temperature controller · TC5 PID controller · TC5 controlador de temperatura

TC5 Series PID Temperature Controller is a high-performance digital temperature controller with a clear white LED display, 100ms high-speed sampling period and ±0.5% display accuracy. It supports multiple input types, including thermocouple, RTD, linear current and linear voltage signals, making it suitable for a wide range of industrial temperature control applications.

Ordering code

TC5-S, Pt100 RTD, dual output

The 48 × 48 mm (1/16 DIN) body with a pt100 rtd and dual output.

Order codeTC5-S, Pt100 RTD, dual output
Bezel (mm)48 × 48
Cut-out (mm)45 × 45
OutputPt100 RTD, dual output
Output terminalsper the case diagram
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: Two outputs on one instrument: a relay contact and an SSR drive, both fitted on the dual-output build

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
1TC54-digit dual-row LED, white and green
2S48 × 48 mm (1/16 DIN) bezel, 45 × 45mm cut-out
inputPt100Sensor the controller is set up for
outputdualRelay contact plus SSR drive, both fitted
Output terminals: per the case diagram·Two outputs on one instrument: a relay contact and an SSR drive, both fitted on the dual-output build

Key features

  • White LED display with clear PV/SV indication
  • 100ms high-speed sampling period
  • ±0.5% display accuracy
  • Supports thermocouple, RTD, current and voltage input
  • ON/OFF and PID control modes
  • TC5P version adds a 32-segment programmer with ramp rate, segment time and hold control
  • Relay / SSR drive output available
  • Optional 4–20mA or 0–10V analog output
  • Optional RS485 Modbus RTU communication
  • Wide-range supply: 100–240VAC, 50/60Hz
  • Multiple DIN panel sizes available
  • Suitable for industrial heating and automation systems

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

The TC5 is specified with the same seven positions: TC, then the type digit, the size, the output, the alarm count, the input, the power supply and an optional communication code. The type digit names the family — 5 for the white and green display, 4 for the red and green — so a TC5 version starts TC5, and the last position takes C when the RS485 port is fitted.

FormatTC[4/5]-[SIZE][OUTPUT][ALARM][INPUT]-[POWER]*[COMM.]

TCSeries
5Product type
MSize
WOutput specification
1Alarm output
TInput specification
2Power supply
CCommunication

Product type

4
4-digit dual-row LED, red and green (TC4)
5
4-digit dual-row LED, white and green (TC5)

Size

S
DIN W48 × H48 mm
H
DIN W48 × H96 mm
W
DIN W96 × H48 mm
M
DIN W72 × H72 mm
L
DIN W96 × H96 mm

Output specification

R
Relay contact output
S
SSR solid-state relay output
W
Relay contact + SSR output
1U
Voltage controlled output
2U
Temperature variable voltage output
1A
Current controlled output
2A
Temperature variable current output
1T
SCR zero-crossing output
2T
SCR phase-shift output

Alarm output

0
No alarm
1
One alarm
2
Two alarms

Input specification

T
Thermocouple (K, E, J)
R
Thermal resistance (Pt100, Cu50)
T/R
Thermocouple (K, E, J) / thermal resistance (Pt100, Cu50)
A
Linear current (0–20 mA, 4–20 mA)
U
Linear voltage (0–5 V, 0–10 V)

Power supply

Blank
220 VAC, 50/60 Hz
2
100–240 VAC/DC
4
24 VAC/DC

Communication

Blank
No communication
C
RS485 Modbus RTU — TC5 only

Examples

TC4-S-R0T-2TC4, 48 × 48 mm, relay output, no alarm, thermocouple input, 100–240 VAC/DC, no RS485
TC5-M-W1T-2*CTC5, 72 × 72 mm, relay plus SSR output, one alarm, thermocouple input, 100–240 VAC/DC, RS485
  • The size letters follow the DIN face: S is 48×48mm, H 48×96mm, W 96×48mm, M 72×72mm and L 96×96mm.
  • A blank power position is 220 VAC; 2 is 100–240 VAC/DC and 4 is 24 VAC/DC. A blank communication position means no RS485.
  • The star before the communication code is the supplier's own separator, not part of the model number. On the TC5 the code is C for RS485 Modbus RTU, and it is left out when the port is not fitted.

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

TC5-S

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

TC5-H

48 × 96mm (1/8 DIN) · cut-out 45 × 92mm

TC5-W

96 × 48mm (1/8 DIN) · cut-out 92 × 45mm

TC5-L

96 × 96mm (1/4 DIN) · cut-out 92 × 92mm

Panel and keys

Four digits per row. Four lamps in two columns — OUT1 above AT on the left, ALM2 above ALM1 on the right — with the °F and °C marks printed between the rows. Four keys: set, shift, decrease, increase.

Panel marking
PV
Measured value (PV)
SV
Setpoint (SV)
OUT1
Control output indicator (OUT1)
AT
Auto-tuning indicator (AT)
ALM1 / ALM2
Alarm indicators (ALM1 / ALM2)
°F / °C
Unit marks, printed between the rows
SET
Set key
◁
Shift key
∨
Decrease key
∧
Increase key

Panel dimensions

Four sizes, one depth: 75mm to the back of the case, 71mm of it behind the panel line. The front changes with the size, the clearance behind the panel does not.

ModelPanel (mm)Cut-out (mm)Total depthBody depth
TC5-S48 × 4845 × 4575mm71mm
TC5-H48 × 9645 × 9275mm71mm
TC5-M72 × 7268 × 6875mm71mm
TC5-L96 × 9692 × 9275mm71mm

Wiring

One sheet, six panels: the TC5-S and the TC5-H / M / L bodies, each with a contactor, a solid-state relay and an alarm beacon arrangement, and the terminal reference for both block layouts below. The two layouts number the same functions differently, so read the reference that matches your bezel.

TC5 series · dual-output wiring diagrams

TC5 series · dual-output wiring diagrams

Relay output is 4 common → 3 normally open on the TC5-S and 13 → 12 on the H / M / L bodies, with a 2–4 jumper on the contactor sheet and 9–13 on the H / M / L one. The alarm contacts are 6–7 on the TC5-S and 10–11 on the H / M / L bodies; the beacon circuit takes its live through the 2–7 jumper on the TC5-S and the 9–10 jumper on the H / M / L bodies. The SSR drive is 12 VDC and needs no mains jumper. The two rear terminal diagrams at the foot of the sheet show the block as it faces you from behind.

Download the sheet (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the TC5 need?

48×48 / 48×96 / 96×48 / 72×72 / 96×96mm. The cut-out is 45×45 / 45×92 / 92×45 / 68×68 / 92×92mm

Which sensors can the TC5 read?

Thermocouple K/J/E/T/N/S/R/B; RTD Pt100, Cu50; linear 0–20mA, 4–20mA, 0–5V, 1–5V

What output options does the TC5 have?

Relay + SSR drive (W), voltage output (1U/2U), current output (1A/2A), SCR trigger (T/P)

What supply voltage does the TC5 need?

100–240VAC, 50/60Hz

How accurate is the TC5?

±0.5%FS or ±1.0%FS

Does the TC5 have alarm outputs?

0, 1 or 2 alarms (code 0 / 1 / 2)

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.