Temperature Controllers

TCN4 Series Intelligent Digital PID Temperature Controller | Relay & SSR Output

TCN4 digital temperature controller supports ON/OFF, P, PI and PID control, with relay or SSR drive versions, dual LED display and alarm function for industrial heating. The relay-only version drives a contactor; the SSR-drive version needs a separate solid state relay.

TCN4 temperature controller, dual LED Digital Display, TCN4S 48×48; TCN4M 72×72; TCN4H 48×96; TCN4L 96×96mm
TCN4: Dual LED Digital Display; TCN4S 48×48; TCN4M 72×72; TCN4H 48×96; TCN4L 96×96mm; K, J, S, R, E thermocouple; PT100 and Cu50 RTD.
Panel size
TCN4S 48×48; TCN4M 72×72; TCN4H 48×96; TCN4L 96×96mm
Panel cutout
45×45 / 68×68 / 45×92 / 92×92mm
Output Type
Relay / SSR; 4–20 mA on the 14mA version
Control Output
220V 5A
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

Product NameDigital PID Temperature Controller
SeriesTCN4 Series
ModelsTCN4S / TCN4M / TCN4H / TCN4L
Display TypeDual LED Digital Display
Display ColorRed PV Display / Green SV Display
Display Resolution0.1°C
Control ModeON/OFF, P, PI, PID Control
Temperature range0–400°C, 0–1200°C or 0–1370°C, selectable at order (default 0–400°C)
Input TypeK, J, S, R, E thermocouple; PT100 and Cu50 RTD
Power Supply100–240VAC, 50/60Hz; shipped at 220VAC unless another voltage is ordered
Output TypeRelay / SSR; 4–20 mA on the 14mA version
Control Output220V 5A
Measurement Accuracy±0.5%FS
Working Environment0–50°C, 35%–85%RH
Installation Environment-10°C to +50°C
Alarm FunctionUpper / Lower Limit Alarm
Alarm outputOne alarm on the 14RV and 14mA versions; two alarms on the 24R version
Panel sizeTCN4S 48×48; TCN4M 72×72; TCN4H 48×96; TCN4L 96×96mm
Panel cutout45×45 / 68×68 / 45×92 / 92×92mm
Dimensions (depth)75mm body depth, common to all four sizes
HousingABS, grey
Weight0.145kg (TCN4S) / 0.21kg (TCN4M, TCN4H) / 0.27kg (TCN4L)
Mounting TypePanel Mounting
ApplicationHeating Equipment, Machinery, Automation Systems

Product overview

Part no. SE-TCN4

Also known as: TCN4 temperature controller · TCN4 temperature and process controller · TCN4 controlador de temperatura

TCN4 Series Digital PID Temperature Controller is an economical and reliable temperature control instrument designed for industrial heating and automation applications. It supports ON/OFF, P, PI and PID control modes, dual LED display for PV and SV values, relay or SSR output, alarm function, and multiple input types including thermocouple and RTD sensors. Four panel sizes — 48×48 / 72×72 / 48×96 / 96×96 mm — share a 75 mm case depth, and the measuring range is selectable at order from 0–400°C, 0–1200°C, 0–1370°C.

Key features

  • Dual LED display for PV and SV values
  • ON/OFF, P, PI and PID control modes
  • Relay output and SSR output available
  • Upper and lower temperature alarm function
  • Supports thermocouple and RTD input
  • Wide power supply: 100–240VAC, 50/60Hz; shipped at 220VAC unless another voltage is ordered
  • Multiple sizes available: TCN4S, TCN4M, TCN4H, TCN4L
  • Selectable range 0–400°C, 0–1200°C, 0–1370°C, default 0–400°C
  • 0.1°C display resolution
  • One-alarm (14RV), two-alarm (24R) and 4–20mA output (14mA) versions
  • Easy panel installation and simple operation
  • Suitable for heating and industrial automation equipment
  • Economical design for OEM and equipment manufacturers

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

The TCN4 opens with three characters that never change — T for temperature controller, CN for the dual-display type set by touch switch, and 4 for the four-digit display — and then takes five choices: size, alarm count, power supply, control output and the optional connector plug wiring.

FormatTCN4[SIZE]-[ALARM][POWER][OUTPUT]-[WIRING]

TCN4Fixed: T+CN+4
SSize
2Alarm
4Power supply
RVControl output
—Wiring method

Size

S
DIN W48 × H48 mm
M
DIN W72 × H72 mm
H
DIN W48 × H96 mm
L
DIN W96 × H96 mm

Alarm

1
One alarm
2
Two alarms

Power supply

2
24 VAC, 50/60 Hz / 24–48 VDC
4
100–240 VAC, 50/60 Hz

Control output

RV
Relay contact output + SSR drive output
R
Relay contact output only
V
SSR drive output only

Wiring method

Blank
Bolt wiring method
P
Connector plug connection method — TCN4S only
Panel sizes and cut-outs (S / M / H / L)
Size codePanelCut-outDepthWeight
S48 × 48 mm45 × 45 mm75 mm0.145 kg
M72 × 72 mm68 × 68 mm75 mm0.21 kg
H48 × 96 mm45 × 92 mm75 mm0.21 kg
L96 × 96 mm92 × 92 mm75 mm0.27 kg

Examples

TCN4S-24RV48 × 48 mm, one alarm, bolt wiring
TCN4S-24RV-P48 × 48 mm, one alarm, connector plug wiring
TCN4M-24R72 × 72 mm, two alarms, 100–240 VAC, relay plus SSR drive
TCN4H-24R48 × 96 mm, two alarms, 100–240 VAC, relay plus SSR drive
TCN4L-24R96 × 96 mm, two alarms, 100–240 VAC, relay plus SSR drive
  • The first three characters are fixed: T is the temperature controller, CN the dual-display touch-switch type, and 4 the four-digit display (up to 9999).
  • P in the final position is available on the TCN4S model only. Leave it blank for the bolt wiring method.
  • AC voltage models allow the SSR drive output to be set to standard ON/OFF control, cycle control or phase control.
  • The output code is printed as R in the examples, TCN4S-24R among them, while the code on the unit is RV. The first example reads as one alarm while 2 is the two-alarm code, so confirm the alarm count when ordering.

Panel and keys

Two four-digit rows — the red process value (PV) above and the green setpoint (SV) below. Four status lamps sit in two columns to the left of the setpoint row (OUT above AT, ALM2 above ALM1), above four control keys: MODE (SET), shift, decrease and increase.

TCN4M front panel: PV and SV displays, OUT/AT/ALM1/ALM2 indicators and four control keys
TCN4M front-panel layout: PV/SV rows, indicator lamps and control keysOpen full diagram
Panel marking
PV
Process value (PV), upper red row
SV
Set value (SV), lower green row
OUT
Main output indicator (OUT)
AT
Auto-tuning indicator (AT)
ALM1 / ALM2
Alarm output indicators (ALM1 / ALM2)
SET / MODE
SET / MODE key — opens parameters and confirms edits
≪
Shift key — moves between digits
∨
Decrease key
∧
Increase key

Panel dimensions

Four panel sizes, one depth: 75mm to the back of the case with 71mm behind the panel line. The cut-out follows the front, so a panel drilled for one size does not accept another.

ModelPanel (mm)Cut-out (mm)Total depthBody depth
TCN4S48 × 4845 × 4575mm71mm
TCN4H48 × 9645 × 9275mm71mm
TCN4M72 × 7268 × 6875mm71mm
TCN4L96 × 9692 × 9275mm71mm

Wiring

The range on one sheet, body by body: a contactor arrangement, a solid state relay arrangement and an alarm light, each with the electrician's diagram and the terminal reference beside it. The circuit repeats across the bodies; the terminal numbers belong to the case, so read the panel that matches yours.

TCN4 series · wiring, schematics and terminal references

TCN4 series · wiring, schematics and terminal references

Each panel carries its own jumper — the link that puts the supply on the relay common for the contactor build, or on the alarm common for the beacon build. The SSR build has no jumper at all, because its output pair is a 12 VDC drive rather than a contact.

Download the sheet (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the TCN4 need?

TCN4S 48×48; TCN4M 72×72; TCN4H 48×96; TCN4L 96×96mm. The cut-out is 45×45 / 68×68 / 45×92 / 92×92mm

Which sensors can the TCN4 read?

K, J, S, R, E thermocouple; PT100 and Cu50 RTD

What output options does the TCN4 have?

220V 5A

What supply voltage does the TCN4 need?

100–240VAC, 50/60Hz; shipped at 220VAC unless another voltage is ordered

How accurate is the TCN4?

0.1°C resolution

Does the TCN4 have alarm outputs?

One alarm on the 14RV and 14mA versions; two alarms on the 24R version

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.