Insulation Monitors

UB1K DC Insulation Monitor

DC insulation monitor for 100 to 1000 VDC floating systems, pole to earth at 1 k to 10 M, alarm relay and buzzer, four 5 mm holes at 90 mm centres.

UB1K DC insulation monitor, front view with its switch bank and terminal strips
UB1K: three lamps read L1, supply and L2, and six switches set the response.
System voltage measured
0–1000 VDC
Measurement accuracy
±2 V from 0 to 400 VDC, ±0.5 % from 400 to 1000 VDC
Auxiliary supply
10–30 VDC
Auxiliary consumption
3 W
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

ProductDC insulation monitor for unearthed systems
System voltage measured0–1000 VDC
Measurement accuracy±2 V from 0 to 400 VDC, ±0.5 % from 400 to 1000 VDC
Auxiliary supply10–30 VDC
Auxiliary consumption3 W
Insulation resistance range1 kΩ–10 MΩ across a 100–1000 VDC system
Insulation accuracy, Cy² 0–0.8 µF≤60 kΩ: ≤3 kΩ · 60 kΩ–1 MΩ: ≤5 %
Insulation accuracy, Cy² 0.8–3 µF≤60 kΩ: ≤6 kΩ · 60 kΩ–1 MΩ: ≤20 %
Alarm relay switching voltage400 VAC / 600 VDC
Alarm relay switching current4 A
Alarm relay contact resistance<100 mΩ
Alarm relay insulation1000 MΩ
Storage / working temperature−55 to 90 °C / −40 to 75 °C
Altitude / humidity≤3500 m / ≤90 %

Product overview

Part no. SE-UB1K

Also known as: UB1K insulation monitor

The kilovolt version: 100 to 1000 VDC floating systems, read pole to earth at 1 kΩ to 10 MΩ, with the alarm relay and the buzzer on the same board. Four Ø5 holes at 90 mm centres fix it, and the drawing below is the cut-out.

Key features

  • The face, the setting and the response of this version, listed in its own table
  • One version per page, because these differ between them
  • Photograph and drawing where the factory has supplied one

Works with

The parts that go into the same panel and are usually ordered with it.

Dimensions

Dimensional drawing of the insulation monitor
UB1K outline: the case, the terminal strips and the fixing holes a panel needs.

Supply & OEM

Available with your logoMOQ 5 units·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.