UBCW4K Four-Kilovolt DC Insulation Monitor
Four-kilovolt DC insulation monitor in a long cast enclosure mounting on the frame rather than a DIN rail, reading far into the megohms.

- DC system voltage measured
- 0–4000 VDC
- Measurement accuracy
- ±2 V from 0 to 400 VDC, ±1 % from 400 to 4000 VDC
- Auxiliary supply
- 10–30 VDC; 90 mA at 12 V or 45 mA at 24 V, ≤1.5 W
- Insulation resistance range
- 0 kΩ–50 MΩ across a 1000–4000 VDC system
Technical specifications
| Product | DC insulation monitor for unearthed systems |
|---|---|
| DC system voltage measured | 0–4000 VDC |
| Measurement accuracy | ±2 V from 0 to 400 VDC, ±1 % from 400 to 4000 VDC |
| Auxiliary supply | 10–30 VDC; 90 mA at 12 V or 45 mA at 24 V, ≤1.5 W |
| Insulation resistance range | 0 kΩ–50 MΩ across a 1000–4000 VDC system |
| Insulation accuracy, 1 kV–2 kV | ≤3 kΩ at 0–100 kΩ, then ±2 %, ±3 %, ±5 %, ±7 %, ±8 %, ±10 % by capacitance |
| Insulation accuracy, 2 kV–3 kV | ≤3 kΩ, then ±2 %, ±3 %, ±4 %, ±6 %, ±8 %, ±8 % |
| Insulation accuracy, 3 kV–4 kV | ≤2 kΩ, then ±2 %, ±2 %, ±3 %, ±5 %, ±5 %, ±7 % |
| First reading after switch-on | 0.7–50 s |
| Reading refresh after a change | 0.5–50 s |
| Alarm relay | 250 VAC / 30 VDC, 5 A, <100 mΩ, 100 MΩ |
| Storage / working temperature | −55 to 90 °C / −40 to 75 °C |
Product overview
Part no. SE-UBCW4K
Also known as: UBCW4K insulation monitor
A different instrument, not a bigger version of the last one: a long cast enclosure that mounts on the frame rather than on a DIN rail, and reads far into the megohms because at four kilovolts there is nothing useful to see near the bottom of the scale.
Key features
- The face, the setting and the response of this version, listed in its own table
- One version per page, because these differ between them
- Photograph and drawing where the factory has supplied one
Works with
The parts that go into the same panel and are usually ordered with it.
Dimensions

Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related models
All Insulation Monitors
UBC1 DC Insulation Monitor for Charging Posts
SE-UBC1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
UBCS1 DIN-Rail DC Insulation Monitor
SE-UBCS1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
UBCH1 Boxed DC Insulation Monitoring Device
SE-UBCH1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
UBCH2 Dual-Channel DC Insulation Monitoring Device
SE-UBCH2
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.