Insulation Monitors

UBCW4K Four-Kilovolt DC Insulation Monitor

Four-kilovolt DC insulation monitor in a long cast enclosure mounting on the frame rather than a DIN rail, reading far into the megohms.

SZDCG-UBCW4K four-kilovolt DC insulation monitoring device in its cast case
UBCW4K: cast case with the cable glands on top, DC+ and DC− studs at the corners, and the address and response switch blocks on the face.
DC system voltage measured
0–4000 VDC
Measurement accuracy
±2 V from 0 to 400 VDC, ±1 % from 400 to 4000 VDC
Auxiliary supply
10–30 VDC; 90 mA at 12 V or 45 mA at 24 V, ≤1.5 W
Insulation resistance range
0 kΩ–50 MΩ across a 1000–4000 VDC system
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

ProductDC insulation monitor for unearthed systems
DC system voltage measured0–4000 VDC
Measurement accuracy±2 V from 0 to 400 VDC, ±1 % from 400 to 4000 VDC
Auxiliary supply10–30 VDC; 90 mA at 12 V or 45 mA at 24 V, ≤1.5 W
Insulation resistance range0 kΩ–50 MΩ across a 1000–4000 VDC system
Insulation accuracy, 1 kV–2 kV≤3 kΩ at 0–100 kΩ, then ±2 %, ±3 %, ±5 %, ±7 %, ±8 %, ±10 % by capacitance
Insulation accuracy, 2 kV–3 kV≤3 kΩ, then ±2 %, ±3 %, ±4 %, ±6 %, ±8 %, ±8 %
Insulation accuracy, 3 kV–4 kV≤2 kΩ, then ±2 %, ±2 %, ±3 %, ±5 %, ±5 %, ±7 %
First reading after switch-on0.7–50 s
Reading refresh after a change0.5–50 s
Alarm relay250 VAC / 30 VDC, 5 A, <100 mΩ, 100 MΩ
Storage / working temperature−55 to 90 °C / −40 to 75 °C

Product overview

Part no. SE-UBCW4K

Also known as: UBCW4K insulation monitor

A different instrument, not a bigger version of the last one: a long cast enclosure that mounts on the frame rather than on a DIN rail, and reads far into the megohms because at four kilovolts there is nothing useful to see near the bottom of the scale.

Key features

  • The face, the setting and the response of this version, listed in its own table
  • One version per page, because these differ between them
  • Photograph and drawing where the factory has supplied one

Works with

The parts that go into the same panel and are usually ordered with it.

Dimensions

Dimensional drawing of the insulation monitor
UBCW4K outline: the cast body, its length and the fixing points that replace the rail.

Supply & OEM

Available with your logoMOQ 5 units·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.