Solid State Relays & SCR Power Modules
BSTY Three-Phase SCR Voltage Regulator 380V, 150A–450A
BSTY three-phase SCR voltage regulator with 380VAC, phase-angle control, soft start, 4-20mA input and 150A-450A current.

- Rated Current
- 150A / 200A / 300A / 350A / 400A / 450A
- Product Series
- BSTY Series
- Product Type
- Three-Phase SCR AC Voltage Regulator
- Working Voltage
- 3-Phase 380VAC ±5%
Technical specifications
| Product Series | BSTY Series |
|---|---|
| Product Type | Three-Phase SCR AC Voltage Regulator |
| Working Voltage | 3-Phase 380VAC ±5% |
| Control Supply | 220VAC — separate from the 380 V main circuit; confirm for exact version |
| Rated Current | 150A / 200A / 300A / 350A / 400A / 450A |
| Control Method | Phase-Angle Regulation, 0–180° |
| Manual Control | 10KΩ / 2W Potentiometer |
| Analog Input | 1–5V, 2–10V, 4–20mA |
| Soft Start Time | 2s default, adjustable 0–15s |
| Protection | Over-temperature protection, 85°C cut-off |
| Insulation | Fully isolated control and power circuits |
| Phase Sequence | No restriction |
| Mounting | Bolt Installation |
| Application Load | Three-phase resistive load |
Product overview
Part no. SE-BSTY
Also known as: Three-Phase SCR Power Regulator · Thyristor Voltage Regulator · Phase-Angle Power Controller
BSTY provides phase-angle voltage control for 380VAC three-phase resistive heating loads. Choose the current and control-input version to match the measured load and process; the available current options span 150A to 450A. The regulator combines selectable analog control, soft start, over-temperature protection and isolated control and power circuits.
Key features
- 150A–450A heavy-duty rating for 3-phase 380 VAC resistive heating loads
- Flexible control inputs: 4–20mA, 1–5V, 2–10V, or a manual 10 kΩ potentiometer
- Built-in protection: adjustable 0–15s soft start and 85°C over-temperature cut-off
- Easy cabinet wiring: fully isolated control and power circuits, no phase-sequence restriction
Model selection & sizing
Ratings apply to a 380 V three-phase resistive load. The recommended kW figures already include a 1.5–2× industrial derating margin for continuous heating duty — size the regulator from the load, then confirm the continuous current in the table before ordering.
| Model | Rated current | Max resistive load @ 380 V, 3-phase | Cooling requirement |
|---|---|---|---|
| BSTY-150A | 150 A | up to ~45 kW (≤ 75 A continuous) | Matched heavy-duty heat sink + cooling fan |
| BSTY-200A | 200 A | up to ~60 kW (≤ 100 A continuous) | Matched heavy-duty heat sink + cooling fan |
| BSTY-300A | 300 A | up to ~90 kW (≤ 150 A continuous) | Matched heavy-duty heat sink + cooling fan |
| BSTY-350A / 400A | 350–400 A | up to ~105–120 kW | Forced-air cooling assembly required |
| BSTY-450A | 450 A | up to ~140 kW | Forced-air cooling assembly required |
Control power & signal options — The control circuit needs an independent 220 VAC supply, separate from the 380 V main circuit. Stock control inputs are 4–20 mA, 1–5 V, 2–10 V and a 10 kΩ manual potentiometer. A 0–10 V input is not a stock listing — confirm availability or a custom build before you specify it.
Physical dimensions
Envelope and fixing centres from the BSTY instruction manual — use these for the cabinet cut-out drawing.
- Overall (L × W × H)
- 140 × 96 × 48 mm
- Mounting-hole spacing
- 125 × 80 mm
| Model | Rated current | Module envelope & fixing | Recommended heat sink |
|---|---|---|---|
| BSTY-150A | 150 A | Compact frame — confirm outline drawing | Matched heavy-duty heat sink + cooling fan |
| BSTY-200A | 200 A | Compact frame — confirm outline drawing | Matched heavy-duty heat sink + cooling fan |
| BSTY-300A | 300 A | 140 × 96 × 48 mm; fixing 125 × 80 mm (ref.) | Matched heavy-duty heat sink + cooling fan |
| BSTY-350A / 400A | 350–400 A | Larger frame — confirm outline drawing | Forced-air cooling assembly required |
| BSTY-450A | 450 A | Largest frame — confirm outline drawing | Forced-air cooling assembly required |
* The 140 × 96 × 48 mm envelope and 125 × 80 mm fixing centres are the BSTY-300A reference from the instruction manual. Higher-current frames and their busbar / terminal dimensions differ — confirm the outline drawing for the ordered rating before cutting the panel.
Complete the heating control chain
A regulator only varies power — the controller, sensor and cooling hardware close the loop. Pair the BSTY with matched components from our Wenzhou factory, shipped together on one invoice.
PID temperature controller (4–20 mA)
The TC4 or TK6 series reads the probe and sends the 4–20 mA command the BSTY expects — no separate signal converter.
Temperature sensor
Industrial K-type thermocouple or Pt100 RTD probes for ovens and furnaces, matched to your controller input.
Forced-air heat sink
Heavy-duty aluminium radiator with a matched cooling fan, sized for 150–450 A duty and pre-mounted with thermal compound.
BSTY quick FAQ
How do I size a BSTY regulator for my three-phase 380 V heater?
Calculate the steady-state load current with I = P (kW) × 1000 / (1.732 × 380), then multiply by 1.5–2× for continuous industrial duty. A 60 kW heater is about 91 A, so choose a BSTY-200A, or a BSTY-300A for more margin on cold starts or in a hot cabinet. This is sizing arithmetic, not a substitute for the module's continuous-current and thermal limits — send the measured load current, duty cycle and ambient temperature for a model and cooling review.
Does BSTY need a neutral, and which load wiring should I use?
The main power circuit works with both three-phase three-wire (delta / ungrounded star) and three-phase four-wire resistive loads, with no phase-sequence restriction. Use the connection diagram for the exact load topology and module version, and confirm whether your selected connection requires a neutral before installation — do not infer the terminal arrangement from a different SCR regulator.
How do I choose the control signal and control supply?
The listed signal options are 4–20 mA, 2–10 V, 1–5 V or a 10 kΩ potentiometer; select the version that matches your controller output and verify it on the order code. The control board needs an independent 220 VAC control supply — do not assume the main power circuit feeds the control circuit. Follow the supplied wiring diagram.
Is a heat sink and fan included, and what warranty applies?
We supply the BSTY module standalone or as a pre-assembled kit mounted on a matched heavy-duty heat sink with cooling fan and thermal compound; ask us to quote a semiconductor fuse selected for your application as well. These are configuration options, not an assumed standard package — the correct thermal assembly and fuse depend on actual current, duty cycle, ambient temperature and installation airflow. A 12-month warranty is standard for high-power SCR modules; confirm model-specific terms in the quotation.
Works with
The parts that go into the same panel and are usually ordered with it.
PID controller (4–20 mA)
SE-TC4
Specify the linear 4–20 mA output version — the analog signal this regulator expects; an SSR pulse output will not regulate it
Heavy-duty forced-air heat sink
SE-HS-SSR
A large three-phase radiator with cooling fan, matched to 150–450 A duty — a small single-phase SSR sink is not enough
Thermocouple or Pt100
SE-TC-WRNK236
K-type or Pt100 sheathed probe matched to the controller input
Downloads
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
SCR3L Three-Phase SCR Voltage Regulator: Signal Wiring, Sizing and Installation
Electrical data, control signal options, four-wire 380VAC connection rules, current sizing, mounting dimensions and commissioning steps for the SCR3L three-phase intelligent SCR…
Read guide Technical Guides · 2025-08-28BSTY Three-Phase SCR AC Power Regulator: Signal Options, Sizing and Commissioning
Electrical data, control signal selection, current sizing for three-phase resistive loads, soft-start and thermal protection settings, wiring practice and commissioning steps for…
Read guide Technical Guides · 2025-04-12SCR Voltage Regulator Circuit Diagram and Wiring Guide
How to read and apply SCR voltage regulator circuit diagrams for single-phase and three-phase four-wire resistive heating, using the current SCR-100 controller and M1DK…
Read guideNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.