Technical specifications
| Model | TC4S, 48×48mm |
|---|---|
| Supply | 220VAC, 50/60Hz |
| Measurement accuracy | ±0.5%FS or ±1.0%FS |
| Control method | PID control and ON/OFF (hysteresis) control |
| Alarm range | freely settable across the full range |
| Input | K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD |
| Output | Control output by ordered version: a relay contact, an SSR drive, both together on the dual-output build, or a 4–20 mA current output (order code 8) |
| Panel size | 48×48mm (1/16 DIN) |
| Panel cut-out | 45×45mm |
| Depth | 75mm total, 71mm behind the panel |
| Front protection | IP44 front |
| Operating environment | 0…50°C, 30–85%RH, no corrosive gas |
Product overview
Part no. SE-TC4S
Also known as: Autonics TC4S · TC4S temperature controller · TC4S PID controller · TC4S controlador de temperatura
TC4S is the 48×48mm (1/16 DIN) member of the TC4 family: a four-digit display of measured value and setpoint, with dual output available as a relay contact or an SSR drive. The input accepts thermocouple and RTD types on one unit, the front is IP44, and the case is 71mm behind the panel line.
Ordering code
TC4S Cu50 RTD, Dual output
The TC4S build with dual output.
| Order code | TC4S Cu50 RTD, Dual output |
|---|---|
| Bezel (mm) | 48 × 48 |
| Cut-out (mm) | 45 × 45 |
| Output | Dual output |
| Output terminals | per the case diagram |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: Selected on the order line; the terminals follow the case diagram for that version
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Reading this order code
How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.
| Position | Reads | Meaning |
|---|---|---|
| 1 | TC4 | 4-digit dual-row LED family |
| 2 | S | 48 × 48 mm (1/16 DIN) DIN bezel, 45 × 45mm cut-out |
| input | Cu50 RTD | Sensor the controller is set up for |
| option | Dual output | The version chosen on the order line |
Key features
- 48×48mm front on a 45×45mm cut-out, 71mm behind the panel
- Dual-row display: measured value above, setpoint below
- Relay contact or SSR drive, chosen by the output code
- Up to two alarm outputs with full-range setpoints
- Thermocouple and RTD input on one unit
- PID or ON/OFF (hysteresis) control with auto-tuning
- Optional Optional 4–20 mA retransmission output or RS485 Modbus communication, by order code, chosen by the fifth code position
- IP44 front, 0–50°C ambient
Works with
The parts that go into the same panel and are usually ordered with it.
Ordering & Selection Guide
The code has five positions: TC4, then the panel size, the output type, the alarm count, the input type, and an optional suffix for current output or RS485. Reading it left to right tells you everything about the unit without a second table.
1. Panel size
| S | 48×48×75mm, cut-out 45×45 |
| H | 48×96×75mm, cut-out 45×92 |
| W | 96×48×75mm, cut-out 92×45 |
| M | 72×72×75mm, cut-out 68×68 |
| L | 96×96×75mm, cut-out 92×92 |
2. Output type
| R | Relay contact output (RELAY) |
| Q | Voltage pulse output (SSR drive) |
| 8 | Current output 4–20mA (control) |
3. Alarms
| 1 | One alarm output (ALM1) |
| 2 | Two alarm outputs (ALM1 and ALM2) |
4. Input type
| TC | Thermocouple: K, E, J, S, R, B, N, T |
| Rt | RTD: Pt100, Cu50 |
5. Additional functions
| 4 | Current output 4–20mA (transmission) |
| RS485 | RS485 communication |
Worked example
TC4S-R1TC
48×48mm panel on a 45×45mm cut-out, relay output, one alarm, thermocouple input, no suffix. Adding 4 gives 4–20mA transmission; adding RS485 gives the talking version.
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
TC4S
48 × 48mm (1/16 DIN) · cut-out 45 × 45mm
- TC4S K thermocouple, Dual output
- TC4S E thermocouple, Dual output
- TC4S Pt100 RTD, Dual output
- TC4S Cu50 RTD, Dual output
- TC4S Universal, Two alarms, relay main output
- TC4S Universal, Two alarms, SSR main output
- TC4S Universal, 4–20 mA control output
- TC4S Universal, 0–10 V control output
- TC4S Universal, 4–20 mA transmitter, relay main output
- TC4S Universal, RS485 Modbus, relay main output
- TC4S Universal, 30 A relay output
- TC4S Universal, 24 VDC supply
Dimensions
One size only: a 48×48 front on a 45×45 cut-out. The case is 75mm to the back, 71mm of it behind the panel line.
| Panel (mm) | Cut-out (mm) | Total depth | Body depth |
|---|---|---|---|
| 48 × 48 | 45 × 45 | 75mm | 71mm |
Wiring
The 48 × 48 body, in both electronics: dual output and RS485. Each has a contactor arrangement, an SSR arrangement and — on the dual-output version — an alarm beacon, with the rear terminal order for every block at the foot of the sheet.
TC4S · dual output and RS485 wiring, with terminal diagrams

On the dual-output version the relay uses 3 / 4 / 5 with a 2–4 jumper, the SSR drive leaves on 11 (+) and 12 (−), and the beacon hangs on 6 / 7 with a 2–7 jumper. On the RS485 version 11 and 12 become A+ and B−, and the SSR drive moves to 3 (+) and 4 (−). The sensor stays on 9 (−) / 10 (+) with the RTD on 8 / 9 / 10 either way.
Documents for this family
- TC4S wiring940 KB · 2026-11-18
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the TC4S need?
48×48mm (1/16 DIN). The cut-out is 45×45mm
Which sensors can the TC4S read?
K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD
What output options does the TC4S have?
Control output by ordered version: a relay contact, an SSR drive, both together on the dual-output build, or a 4–20 mA current output (order code 8)
What supply voltage does the TC4S need?
220VAC, 50/60Hz
Does the TC4S have alarm outputs?
freely settable across the full range
Related guides
TC5-S PID Temperature Controller: Model Code, Terminals, Outputs and Commissioning
A working reference for the TC5-S 1/16 DIN digital PID temperature controller: how to read the model code, the electrical specification, terminal-by-terminal wiring, how to choose…
Read guide Product Updates · 2025-04-11TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guide Product Updates · 2024-02-03TC4 Series PID Temperature Controller: Model Code Breakdown, Outputs and RS485 Setup
How to read a TC4 model code, which sensor inputs and control outputs are available across TC4S/H/W/M/L, what the RS485 Modbus option adds, and the checks to run at commissioning.
Read guideRelated models
All Temperature Controllers
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View details
TC4W Digital PID Temperature Controller
SE-TC4W
96×48mm (1/8 DIN) · 92×45mm · 75mm total, 71mm behind the panel
View details
TC4M Digital PID Temperature Controller
SE-TC4M
72×72mm · 68×68mm · 75mm
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.