Temperature Controllers

TC4W with dual output

The TC4W build with dual output.

TC4W temperature controller, 96×48mm (1/8 DIN), K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD
TC4W: 96×48mm (1/8 DIN); K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD; Relay contact or SSR drive, plus 4–20mA and 0–10V control on the analogue builds.
Output
Dual output
Bezel
96 × 48
Panel cut-out
92 × 45
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

ModelTC4W, 96×48mm
Supply220VAC, 50/60Hz
Measurement accuracy±0.5%FS or ±1.0%FS
Control methodPID control and ON/OFF (hysteresis) control
Alarm rangefreely settable across the full range
InputK, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD
OutputRelay contact or SSR drive, plus 4–20mA and 0–10V control on the analogue builds
Panel size96×48mm (1/8 DIN)
Panel cut-out92×45mm
Depth75mm total, 71mm behind the panel
Front protectionIP44 front
Operating environment0…50°C, 30–85%RH, no corrosive gas

Product overview

Part no. SE-TC4W

TC4W is the 96×48mm (1/8 DIN) landscape member of the TC4 family: a dual-row four-digit display, measured value above and setpoint below, on the 1/8 DIN front, with a control output that is either a relay contact or an SSR drive, selected by the ordered version. The input accepts thermocouple and RTD types on one unit, the front face meets IP44, and the case is 71mm behind the panel line.

Ordering code

TC4W Cu50 RTD, Dual output

The TC4W build with dual output.

Order codeTC4W Cu50 RTD, Dual output
Bezel (mm)96 × 48
Cut-out (mm)92 × 45
OutputDual output
Output terminalsper the case diagram
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: Selected on the order line; the terminals follow the case diagram for that version

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
1TC44-digit dual-row LED family
2W96 × 48 mm (1/8 DIN) DIN bezel, 92 × 45mm cut-out
inputCu50 RTDSensor the controller is set up for
optionDual outputThe version chosen on the order line
Output terminals: per the case diagram·Selected on the order line; the terminals follow the case diagram for that version

Key features

  • 96×48mm front on a 92×45mm cut-out, 71mm behind the panel
  • Dual-row display: measured value above, setpoint below
  • Relay contact or SSR drive, chosen by the output code
  • Up to two alarm outputs with full-range setpoints
  • Thermocouple and RTD input on one unit
  • PID or ON/OFF (hysteresis) control with auto-tuning
  • 4–20mA or 0–10V control output on the analogue versions
  • IP44 front, 0–50°C ambient

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

The code has five positions: TC4, then the panel size, the output type, the alarm count, the input type, and an optional suffix for current output or RS485. Reading it left to right tells you everything about the unit without a second table.

TC4−WSizeROutput2AlarmsTCInput−RS485Option

1. Panel size

S48×48×75mm, cut-out 45×45
H48×96×75mm, cut-out 45×92
W96×48×75mm, cut-out 92×45
M72×72×75mm, cut-out 68×68
L96×96×75mm, cut-out 92×92

2. Output type

RRelay contact output (RELAY)
QVoltage pulse output (SSR drive)
8Current output 4–20mA (control)

3. Alarms

1One alarm output (ALM1)
2Two alarm outputs (ALM1 and ALM2)

4. Input type

TCThermocouple: K, E, J, S, R, B, N, T
RtRTD: Pt100, Cu50

5. Additional functions

4Current output 4–20mA (transmission)
RS485RS485 communication

Worked example

TC4W-R1TC

96×48mm panel on a 92×45mm cut-out, relay output, one alarm, thermocouple input, no suffix. Adding 4 gives 4–20mA transmission; adding RS485 gives the talking version.

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

Dimensions

One size only: a 96×48 front on a 92×45 cut-out. The case is 75mm to the back, 71mm of it behind the panel line.

Panel (mm)Cut-out (mm)Total depthBody depth
96 × 4892 × 4575mm71mm

Wiring

Four sheets for the four bodies: the relay version into a contactor, the same version into a solid-state relay, the alarm beacon with the terminal reference beside it, and the RS485 versions in both output versions. The sensor lands on 5, 6 and 7 whichever version you have.

Relay output into a contactor, SSR output into a solid-state relay

Relay output into a contactor, SSR output into a solid-state relay

8 and 9 take the supply, 10 and 11 the output; 9–13 is linked on the contactor sheet. The heater hangs across T1 and T2 on the contactor, or across the SSR's two output terminals.

Alarm beacon on ALM1, with the terminal reference

Alarm beacon on ALM1, with the terminal reference

ALM1 closes 12–13–14 at 250 VAC 5 A; jumper 9–10 feeds the beacon's live. The reference beside the drawing gives the group each terminal belongs to.

RS485 version with SSR output

RS485 version with SSR output

RS485 on 3 (A+) and 4 (B−); on the single-output build the 12 VDC SSR drive leaves on 10 and 11, and ALM1 keeps its own contact group, set out in the terminal reference beside the drawing.

RS485 version with relay output into a contactor

RS485 version with relay output into a contactor

RS485 on 3 and 4, the relay output on 10 and 11 closing the coil, 9–10 linked, heater across T1 and T2.

Download the four sheets (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the TC4W need?

96×48mm (1/8 DIN). The cut-out is 92×45mm

Which sensors can the TC4W read?

K, E, J, S, R, B, N, T thermocouples; Pt100 and Cu50 RTD

What output options does the TC4W have?

Relay contact or SSR drive, plus 4–20mA and 0–10V control on the analogue builds

What supply voltage does the TC4W need?

220VAC, 50/60Hz

Does the TC4W have alarm outputs?

freely settable across the full range

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.