Insulation Monitors
SZDCG-UBCS1-60 DC Insulation Monitor for Control Circuits
The control-circuit version of the DIN-rail family: the low voltages a panel's own rail lives at, in the same case and on the same terminals.

- DC system voltage measured
- 0–60 VDC
- Measurement accuracy
- ≤2 V across 0–60 VDC
- Auxiliary supply
- 10–30 VDC; 110 mA at 12 V or 60 mA at 24 V, ≤1.5 W
- Insulation resistance range
- 0 kΩ–1 MΩ across a 10–60 VDC system
Technical specifications
| Product | DC insulation monitor for unearthed systems |
|---|---|
| DC system voltage measured | 0–60 VDC |
| Measurement accuracy | ≤2 V across 0–60 VDC |
| Auxiliary supply | 10–30 VDC; 110 mA at 12 V or 60 mA at 24 V, ≤1.5 W |
| Insulation resistance range | 0 kΩ–1 MΩ across a 10–60 VDC system |
| Insulation accuracy, Cy² 0–0.8 µF | ≤60 kΩ: ≤3 kΩ · 60 kΩ–300 kΩ: ≤5 % |
| First reading / refresh | 0.7–2 s / 0.5–3 s |
| Earth-switch operations | 50 × 10⁵ |
| Storage / working temperature | −55 to 90 °C / −40 to 75 °C |
Product overview
Part no. SE-UBCS1-60industry model UBCS1-60
Also known as: SZDCG-UBCS1-60 insulation monitor
The control-circuit version: the low voltages a panel's own rail lives at. Same DIN case and the same terminals as the rest of the family, so a panel cut for one accepts this one.
Key features
- For a panel's own control rail, not the power bus
- Accuracy stated per band in the table
- Same DIN case and terminal pitch as the rest of the family
- Earth-switch life given in operations
Works with
The parts that go into the same panel and are usually ordered with it.
Dimensions

Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
Over-Temperature Protection and Interlock Wiring for Industrial Heating Equipment
A controller alarm tells an operator that something is wrong; it does not stop the heater. This guide shows how to add an independent limit controller, a normally-closed safety…
Read guide Technical Guides · 2026-08-27How to Wire CH102, CH402, CH702 and CH902 PID Temperature Controllers
A practical wiring guide for CH102, CH402, CH702 and CH902 PID temperature controllers, covering power, AC contactor and SSR control, thermocouple and Pt100 sensors, alarms and…
Read guide Technical Guides · 2026-08-25TEL96-9001 Temperature Controller Wiring Guide: Direct Heater and AC Contactor Methods
Terminal-by-terminal wiring for the TEL96-9001 ON/OFF temperature controller: K-type thermocouple connection, direct heater switching up to 1500 W, AC contactor control, 220 VAC…
Read guideRelated models
All Insulation Monitors
UBCS1 DIN-Rail DC Insulation Monitor
SE-UBCS1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
SZDCG-UBCS1-250 DC Insulation Monitor for Battery Systems
SE-UBCS1-250
The battery-system version of the DIN-rail family, for the voltages a stationary battery runs at: same case, same pluggable terminals at the same…
View details
UBC1 DC Insulation Monitor for Charging Posts
SE-UBC1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View details
UBCH1 Boxed DC Insulation Monitoring Device
SE-UBCH1
One version per page: the face, the setting and the response that belong to this unit alone are listed in the table below, and the drawing under it…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.