Temperature Controllers

WK-P(TH), Flush, heating action

The flush body set for heating action, heater starts below the set point.

WK-P(TH) / WSK-P(TH) temperature controller, 48×48mm (1/16 DIN), relay output, live 220VAC
WK-P(TH) / WSK-P(TH): 48×48mm (1/16 DIN); relay output, live 220VAC; −30…70 °C.
Output
Flush, heating action, heater starts below the set point
Bezel
48 × 48
Panel cut-out
45 × 45
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

ModelWK-P(TH) temperature, WSK-P(TH) temperature and humidity
Supply220VAC, 50/60Hz
Temperature range−30…70 °C
Humidity range0…99.9 %RH
Controlone-knob switching control, heating or cooling action
Outputrelay output, live 220VAC
Panel size48×48mm (1/16 DIN)
Panel cut-out45×45mm
Depth100mm on the base-socket body, 93mm on the flush body
Operating environment0…50 °C, 30–85 %RH, no corrosive gas

Product overview

Part no. SE-WK-Pindustry model WK-P(TH)

A controller for the inside of a cabinet, not for a process. One knob sets the point at which the relay closes; the temperature version drives a heater below the set point or a fan above it, and the humidity version adds a second loop for a dehumidifier. The sensor is on a lead, so it sits where the condensation actually forms rather than where the instrument is bolted.

Ordering code

WK-P(TH), Flush

The flush body set for heating action, heater starts below the set point.

Order codeWK-P(TH), Flush
Bezel (mm)48 × 48
Cut-out (mm)45 × 45
OutputFlush, heating action, heater starts below the set point
Output terminals8 · 9 temperature, 8 · 10 humidity
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: The relay carries the heater, fan or dehumidifier contactor; the sensor sits on a lead inside the cabinet

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Key features

  • 48×48mm (1/16 DIN) front, base socket or flush mounting
  • −30 to 70 °C on the temperature loop, 0 to 99.9 %RH on the humidity loop
  • One knob, no menus: the set point is the mark on the dial
  • Relay output rated for the heater, fan or dehumidifier contactor
  • Sensor on a lead, so it reads the air where the cabinet is coldest
  • WK-P is temperature only; WSK-P adds the humidity loop

Works with

The parts that go into the same panel and are usually ordered with it.

Terminals

Flush body, terminals 1 to 10 as printed on the case; the base-socket body carries the same numbers around its socket.

TerminalsConnects to
1 · 2Temperature sensor (NTC on a lead)
4 · 5Humidity sensor, WSK-P only
6 · 7Supply, 220VAC 50/60Hz
8 · 9Temperature load, live 220V out — heater or fan
8 · 10Humidity load, live 220V out — humidifier or dehumidifier

Mounting the two bodies

The same instrument is supplied flush for a door cut-out or on a socket for a DIN rail inside the cabinet.

BodySizeFits
Flush48 × 48mm front, 93mm deep45 × 45mm cut-out in the door, fixed by the frame
Base socket48 × 48mm front, 100mm deepEight-pin socket on a DIN rail, the instrument plugs in and is changed without rewiring

Inside a cabinet, not on a machine

  • Switchgear and MCC cabinets. A heater on the temperature loop keeps the inside above the dew point in winter; the same loop with cooling action starts a fan when the cabinet climbs in summer.
  • Outdoor enclosures and telecom cabinets. The humidity loop is the one that matters: it closes on a dehumidifier before condensation settles on the busbars.
  • Panel shops building to a drawing. The base-socket body is the one to specify: the instrument is replaced by pulling it off the socket, with the wiring left as commissioned.

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

WK-P(TH)

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

WSK-P(TH)

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.