Temperature Controllers

TK6Z-14R relay-output controller with RS485

The build for a machine that already has a controller above it: the relay still switches the heater, but the setpoint and the readings travel over Modbus-RTU instead of being typed in at the front. Thermocouple or RTD input on the same terminals.

Two TK6Z single-loop DIN-rail temperature controllers side by side, each with a red rail clip on top, a six-screw terminal block at each edge, the WEEK and AUTO indicators above the measured-value row, the AT, OUT1, AL1, AL2 and °C lamps beside the setpoint row, and the MODE/SET, SHIFT, DOWN and UP keys below
Two TK6Z modules front on: the red clip on the top edge is what holds the case on the rail, the two six-way screw blocks sit above and below the face, and the lamp column beside the setpoint row is where autotuning and both alarms show
Output
Relay output with RS485
Bezel
45 × 88 × 54 mm
Panel cut-out
none - 35 mm DIN rail module
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesTK6Z Series (single-loop DIN-rail temperature controller)
ModelsThree versions in one case — 14RV with a relay and an SSR output, 14R with a relay output and RS485, 14V with an SSR output and RS485
Control methodPID with autotuning, or upper and lower limit control, selected in the parameter menu
Second outputA second control output with its own proportional band and cycle time, and a deadband between the first and second control outputs; the 14RV version brings out both a relay contact and an SSR drive, each on its own terminal pair
InputThermocouple K, E, J, R, S, B, T; RTD Pt100 and Cu50
Temperature range0–400°C as standard; 0–1370°C is the widest range the instrument accepts
Resolution0.1°C
Accuracy±0.5°C
Sampling0.25s per sample
DisplayTwo four-digit rows, measured value (PV) above and setpoint (SV) below, with AT, OUT1, AL1, AL2, °C and COM lamps
KeysMODE, a left-shift key, and up and down; MODE opens the parameter menu and confirms a value
Control outputRelay and SSR drive together (code RV), relay alone (code R) or SSR drive alone (code V)
Relay contact rating10A / 800W resistive
Alarm outputOne alarm output (AL1) on its own two-terminal pair; AL2 and its hysteresis sit in the parameter set but are not brought out on these three versions
CommunicationRS485 Modbus-RTU on the R and V versions, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only
Supply voltageAC100–240V 50/60Hz
Dimensions45 × 88 × 54mm (W × H × D)
Mounting35mm DIN rail, clip-on, no panel cut-out
Ambient temperature−10 to 50°C
Weight0.35kg packed
CertificationCE
Modbus registersThe same register map as the TK6D: measured value, setpoint, output percentage, autotuning, both alarms and their hysteresis, P, I, D, the integral overshoot limit, the control period, the input offset, the second output's proportional band and cycle time, the dead band and a timer block are all in holding registers; the measured value and the display status are read-only.

Product overview

Part no. SE-TK6Z

Also known as: TK6Z temperature controller · TK6Z PID controller · TK6Z controlador de temperatura

The TK6Z is the shallow member of the TK6 series: one loop in a rail-mounted module that clips on and needs no cut-out, so the cabinet door stays free for whatever else has to be read through it. The input takes the common thermocouples and both platinum and copper RTDs, chosen in the menu, and the loop runs PID with autotuning — switch it to upper and lower limit control and the same instrument becomes a thermostat with two setpoints instead. Three versions cover the output side: a relay contact, an SSR drive, or both together on the dual-output version, which is the one to take when a contactor and a solid-state relay have to be driven from the same loop. RS485 Modbus-RTU comes with the two single-output versions and exposes the measured value, the setpoint, the tuning constants and both alarms, so the loop can be read from a PLC or a touch panel rather than only watched on its own display. Measured value and setpoint sit on separate rows, which keeps the setpoint visible while the temperature is moving.

Ordering code

TK6Z-14R

The build for a machine that already has a controller above it: the relay still switches the heater, but the setpoint and the readings travel over Modbus-RTU instead of being typed in at the front. Thermocouple or RTD input on the same terminals.

Order codeTK6Z-14R
Bezel (mm)45 × 88 × 54 mm
Cut-out (mm)none - 35 mm DIN rail module
OutputRelay output with RS485
Output terminalsas marked on the case; RS485 A/B on the communication pair
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: One relay contact plus Modbus-RTU over RS485, for a panel where the setpoint comes from a PLC or a line controller

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
SeriesTK6The TK6 single-loop PID temperature controller family; the same firmware runs the panel and the DIN-rail versions
CaseZ45 × 88 × 54 mm DIN-rail case, clips onto 35 mm rail, no panel cut-out
Auxiliary1Auxiliary position at its base value, which is how the versions on sale are written
Supply4The supply digit the ordering sheet prints for every version of this series that is on sale
Control outputRRelay output with RS485
Output terminals: as marked on the case; RS485 A/B on the communication pair·One relay contact plus Modbus-RTU over RS485, for a panel where the setpoint comes from a PLC or a line controller

How this build compares with the others

Same case, same cut-out, same supply. The differences are the ones below.

Order codeOutput stageWhat it can switchTerminals
TK6Z-14Rthis pageRelay output with RS485One relay contact plus Modbus-RTU over RS485, for a panel where the setpoint comes from a PLC or a line controlleras marked on the case; RS485 A/B on the communication pair
TK6Z-14RVRelay plus SSR drive, dual outputOne relay contact for a contactor and one SSR drive for a solid state relay, so one controller can run either stage without a second part numberas marked on the case; relay and SSR drive are separate terminal pairs
TK6Z-14VSSR drive output with RS485An SSR drive plus Modbus-RTU over RS485: no relay contact to wear out, and a switching rate the heater can actually followas marked on the case; the SSR drive pair is isolated from the supply

Key features

  • One loop in a rail-mounted module — no panel cut-out, no meter in the door, and every setting reachable from four keys on the face
  • Universal input: Thermocouple K, E, J, R, S, B, T; RTD Pt100 and Cu50
  • PID with autotuning, or upper and lower limit control when the job only needs two setpoints
  • Relay and SSR drive together (code RV), relay alone (code R) or SSR drive alone (code V)
  • One alarm output (AL1) on its own two-terminal pair; AL2 and its hysteresis sit in the parameter set but are not brought out on these three versions
  • RS485 Modbus-RTU on the R and V versions, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only
  • AC100–240V 50/60Hz supply
  • Measured value and setpoint on separate four-digit rows, so the setpoint stays visible while the temperature moves
  • Screw terminals in two six-way blocks, with the supply, alarm and output groups printed on a label strip beside the lower one
  • Samples four times a second, and keeps the loop stable in a cold cabinet

Works with

The parts that go into the same panel and are usually ordered with it.

Panel overview

The front of the TK6Z, drawn square on: both display rows, the lamp column beside the setpoint and the four keys.

Flat drawing of the TK6Z front: PV and SV display rows, the AT, OUT1, AL1, AL2 and °C lamps beside the setpoint, MODE/SET, shift, down and up keys, a red rail clip on the top edge and a six-screw terminal block at each edge
PV sits over SV; AT, OUT1, AL1, AL2, °C and COM run down the right of the setpoint row. MODE/SET on the left with shift, down and up beside it. The red clip on the top edge is what holds the case on a 35 mm rail, and the six-way screw blocks above and below the face are the terminals.

Dimensions and rail mounting

The TK6Z case measures 45 × 88 × 54mm (W × H × D) — wider, shorter and far shallower than the TK6D's 23mm-wide, 110mm-tall strip, because the Z trades front-panel real estate for depth behind the rail. Both clip onto the same 35mm DIN rail, so the two can sit side by side on one rail.

MeasurementValue
Width45mm
Height88mm
Depth54mm
Rail35mm DIN
Panel cut-outNone — rail clip only
  • Dimensions are the published case figures (W × H × D); allow ±0.2mm tolerance when laying out a rail.
  • The case clips onto the rail from the front, so allow screwdriver clearance above and below it, not only the 45mm width.
  • Depth is measured to the back of the case; a rail-mounted terminal cover, if fitted, adds to the space needed behind the front face.

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

Which sensors can the TK6Z read?

Thermocouple K, E, J, R, S, B, T; RTD Pt100 and Cu50

What output options does the TK6Z have?

Relay and SSR drive together (code RV), relay alone (code R) or SSR drive alone (code V)

What supply voltage does the TK6Z need?

AC100–240V 50/60Hz

How accurate is the TK6Z?

±0.5°C, at 0.1°C resolution

Does the TK6Z have alarm outputs?

One alarm output (AL1) on its own two-terminal pair; AL2 and its hysteresis sit in the parameter set but are not brought out on these three versions

What is the temperature range?

0–400°C as standard; 0–1370°C is the widest range the instrument accepts

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.