Temperature Controllers
TK6D with relay plus ssr drive
TK6D-14RV-RS485, in the 23 mm rail case. K, E, J, S, R thermocouple or Pt100 input, 0.1 C resolution, 0-400 C by default.

- Output
- Relay plus SSR drive
- Bezel
- 116 x 23 x 110 mm
- Panel cut-out
- none - DIN rail module
Technical specifications
| Series | TK6D Series (single-loop DIN-rail temperature controller) |
|---|---|
| Models | Eight order codes — 14RV, 14MA, 24RV and 24MA, each with or without RS485 — sold as twelve SKUs because every MA version is offered with a K-thermocouple default input or a 4–20mA default input (INPUT TC/RTD [Default K] or [Default 4-20MA] on the nameplate) |
| Control method | PID with autotuning; P = 0 switches the loop to two-position control with an adjustable hysteresis |
| Second output | Cooling output with its own proportional band and cycle time, separated from the heating output by an adjustable dead band |
| Input | Thermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default |
| Temperature range | 0–400°C as standard; 0–1200°C and 0–1370°C to order |
| Display | Two four-digit rows for the measured value and the setpoint, with AT, OUT, AL2, AL1 and °C lamps |
| Resolution | 0.1°C |
| Accuracy | ±0.5°C |
| Control output | Relay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA) |
| Relay contact rating | 10A / 800W resistive |
| Alarm output | One alarm (code 1) or two (code 2), each with a selectable alarm mode |
| Communication | RS485 Modbus-RTU, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only |
| Supply voltage | 100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2) |
| Front dimensions | 20 × 76.8mm label window in a 23mm-wide body |
| Depth | 116mm from the front face back to the rail, 110mm overall height and 100mm of body between the terminal shrouds |
| Mounting | 35mm DIN rail, clip-on, no panel cut-out |
| Housing | ABS, self-extinguishing |
| Weight | 0.2kg packed |
| Certification | CE |
| Modbus registers | Measured value, setpoint, output percentage, autotuning, both alarms and their hysteresis, P, I, D, the integral overshoot limit, the control period, the input offset, the second output's proportional band and cycle time, the dead band and a timer block are all in holding registers; the measured value and the display status are read-only. |
Product overview
Part no. SE-TK6D
Also known as: TK6D temperature controller · TK6D PID controller · TK6D controlador de temperatura
The TK6D is the DIN-rail member of the TK6 series: the same control loop as the panel instruments, folded into a module that clips onto the rail and needs no cut-out. One input takes a thermocouple or a three-wire Pt100, and the loop runs PID with autotuning — set P to zero and it becomes two-position control with an adjustable hysteresis instead. A second output is there for cooling, with its own proportional band and cycle time and a dead band between the two, so a chamber that overshoots can be pulled back rather than left to coast. The relay contact and the SSR drive both sit on the terminal block; the other version puts a current output there instead. RS485 Modbus-RTU is available on either version and exposes the measured value, the setpoint, the tuning constants and the alarm settings, which is what lets the module report into a PLC rather than only hold a temperature. Everything is set from the four keys on the face.
Ordering code
TK6D-14RV-RS485
TK6D-14RV-RS485, in the 23 mm rail case. K, E, J, S, R thermocouple or Pt100 input, 0.1 C resolution, 0-400 C by default.
| Order code | TK6D-14RV-RS485 |
|---|---|
| Bezel (mm) | 116 x 23 x 110 mm |
| Cut-out (mm) | none - DIN rail module |
| Output | Relay plus SSR drive |
| Output terminals | typical; confirm against the case label |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: The same relay and SSR drive with RS485 for a PLC or data logger
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Key features
- One loop on a rail-mounted module — no panel cut-out and no separate meter in the door
- Universal input: Thermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default
- PID with autotuning; P = 0 switches the loop to two-position control with an adjustable hysteresis
- A second output for cooling, with its own proportional band, cycle time and a dead band against the heating output
- Relay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA)
- One alarm (code 1) or two (code 2), each with a selectable alarm mode
- RS485 Modbus-RTU, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only
- 100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2) supply
- Two four-digit rows for the measured value and the setpoint, with lamps for autotuning, the output and both alarms
- Terminals along both edges, numbered 1–20 and printed on the face, so a module can be replaced without the drawing
- ABS, self-extinguishing housing, CE marked
Works with
The parts that go into the same panel and are usually ordered with it.
Ordering & Selection Guide
Every TK6 is ordered by the same nine-character code; this page's example is TK6D-14RV (the D case, one alarm, 100–240VAC, relay + SSR).
Case
- S
- 48 × 48mm panel case
- M
- 72 × 72mm panel case
- H
- 48 × 96mm panel case
- L
- 96 × 96mm panel case
- D
- DIN-rail case (19.7 × 75 × 116mm)
Auxiliary
- 1
- One alarm output
- 2
- Two alarm outputs
- 3
- RS485 communication
Supply
- 2
- 24VAC 50/60Hz or 24–48VDC
- 4
- 100–240VAC 50/60Hz
Control output
- RV
- Relay contact + SSR drive
- MA
- 4–20mA output
- H is the horizontal 48 × 96mm case (TK6H) and L is the 96 × 96mm case.
- RS485 is also sold as a suffix (e.g. TK6D-14RV-Rs485) while keeping the auxiliary position at 1 or 2.
Dimensions and rail mounting
The case measures 116 × 23 × 110mm: a 23mm-wide front, 110mm tall overall, and 116mm from the front face back to the rail. The 100mm body between the two terminal shrouds accounts for the 10mm difference. The clip takes a standard 35mm DIN rail, so there is no panel cut-out to make.

| Measurement | Value |
|---|---|
| Display / key window | 20 × 76.8mm |
| Front width | 23mm |
| Overall height | 110mm |
| Body between terminal shrouds | 100mm |
| Depth behind the front face | 116mm |
| Rail | 35mm DIN |
- Dimensions are nominal; allow ±0.2mm tolerance.
- The module clips onto the rail from the front, with terminal screws facing up and down — leave clearance above and below for a screwdriver, not just for the case.
- The D case measures 23 × 110mm overall; 19.7 × 75mm is the rail mounting footprint. Use 23 × 110mm when laying out the rail.
Terminals and wiring
The TK6D has twenty screw terminals in two stepped blocks, numbered 1–20 on the front. Three terminal assignments are shown below, one for each version and input configuration. Check the full SKU and the INPUT line on the nameplate before wiring, then match the assignment to the terminal block in your hand.
Terminal assignment
Where the numbers sit on the module
| Terminal | Function | Note |
|---|---|---|
| 1 | SSR drive, + | DC pulse output for a solid-state relay, not a mains terminal |
| 2 | SSR drive, − | — |
| 3 | Supply, 100–240VAC | 50/60Hz, either way round |
| 4 | Supply, 100–240VAC | — |
| 5 | Control output — MA versions: 4–20mA − | Unused on RV versions |
| 6 | Control output — RV versions: relay contact | Unused on MA versions |
| 7 | RV: other side of the relay contact · MA: 4–20mA + | — |
| 8 | Not used | — |
| 9 | Alarm 1 contact | — |
| 10 | Alarm 1 contact | — |
| 11 | Alarm 2 contact | Fitted on 24-code versions only |
| 12 | Alarm 2 contact | — |
| 13 | Sensor, B · thermocouple + | Three-wire RTD: B on 13 and 14, A on 15. Unused when the default input is 4–20mA |
| 14 | Sensor, B · thermocouple − | On the Default 4-20MA version this is the current input − instead |
| 15 | Sensor, A | On the Default 4-20MA version this is the current input + instead |
| 16 | Not used | — |
| 17 | RS485 A (+) | Fitted on -Rs485 versions only |
| 18 | RS485 B (−) | — |
| 19 | Not used | — |
| 20 | Not used | — |
- The 1–2 SSR pair and the 6–7 relay contact are two different things: the first is a low-voltage DC drive for an external solid-state relay, the second switches the load. On RV versions both are fitted and the output mode is selected in the parameter set; MA versions use the 4–20mA output. Confirm the output type on the nameplate before wiring.
- Alarm count follows the code: 14-code versions carry one alarm on 9–10, 24-code versions carry two on 9–10 and 11–12. Wire ALM2 only on a version whose full SKU reads 24 or carries 2 in the auxiliary position.
- MA versions are available with two input configurations. With INPUT TC/RTD [Default K], terminals 13–15 take a K thermocouple or three-wire RTD and there is one 4–20mA loop, the output on 5 and 7. With INPUT TC/RTD [Default 4-20MA], the input is 4–20mA on 14 (−) and 15 (+) and there are two current loops, one in and one out. Both SKUs share the MA suffix — confirm the default input when ordering.
- RS485 lives on 17 (A) and 18 (B). It is a suffix on the SKU, not something a non-communicating version can be upgraded to by adding wire: 19 and 20 are unused.
- The stepped blocks keep mains, output and sensor wiring in separate zones: three rows of four above the display, two rows of four below. Plated screws and numbers printed beside each position allow a module to be replaced quickly.
RS485 Modbus-RTU register map
Communicating versions expose the whole control loop over RS485 Modbus RTU, with one start bit, eight data bits and one stop bit. Function 03 (read holding registers) and 06 (write a single register) are supported. Addresses are 1–250 and baud rates 300–38400; both default settings are reached with the menu code Con = 100.
- Protocol
- Modbus RTU · 1 start + 8 data + 1 stop
- Address (Addr)
- 1–250 · default 1 · Con = 100
- Baud rate (bps)
- 300–38400 · default 19200 · Con = 100
- Function codes
- 03 read / 06 write only
| Address | Code | Register | Access |
|---|---|---|---|
| 0000H | PV | Measured value | R |
| 0001H | LED | Display / lamp status | R |
| 0002H | SV | Setpoint | R/W |
| 0003H | OOT | Output percentage | R |
| 0004H | AT | Autotuning switch | R/W |
| 0005H | AL1 | Alarm 1 value | R/W |
| 0006H | AL2 | Alarm 2 value | R/W |
| 0007H | HY1 | Alarm 1 hysteresis | R/W |
| 0008H | HY2 | Alarm 2 hysteresis | R/W |
| 0009H | P | Proportional band | R/W |
| 000AH | I | Integral term | R/W |
| 000BH | D | Derivative term | R/W |
| 000CH | AR | Integral overshoot limit, % | R/W |
| 000DH | T | Control period | R/W |
| 000EH | PB (SC) | Measured-value correction | R/W |
| 000FH | HY | Main hysteresis (active when P = 0) | R/W |
| 0010H | AL1T | Alarm 1 mode | R/W |
| 0011H | AL2T | Alarm 2 mode | R/W |
| 0012H | PC | Second output, proportional band | R/W |
| 0013H | TC | Second output, control period | R/W |
| 0014H | DB | Dead band | R/W |
| 0015H | CTH | Current detector input | R/W |
| 0016H | ACT | Sensor-break alarm value | R/W |
| 0017H | TON | Timer function switch | R |
| 0018H | ET | Timer mode | R/W |
| 0019H | TIE | Timer time unit | R/W |
| 001AH | ALT | Timer temperature hysteresis | R/W |
| 001BH | BL | Alarm time after the timer ends | R/W |
| 001CH | ST | Timer setpoint | R/W |
| 001DH | TIM | Current timer value (seconds if TIE = 0, minutes if TIE = 1) | R |
| 001EH | TIS | Current timer seconds (TIE = 1); BL counter, alarm 2 output time | R |
Verify scaling, word order, register width and parity against your master before writing: a PID constant written with the wrong decimal scaling will move the loop, not the setpoint.
Applications and immunity
Designed for single-loop control on plastics machinery. In a twin-screw extruder, OUT1 drives the barrel heaters and OUT2 drives the fan or cooling valve, with the dead band between them keeping the melt temperature steady. The same two-output arrangement is why the second proportional band and cycle time appear in the register map.
Typical applications
- Injection moulding machines
- Extruders, including twin-screw
- Film blowing machines
- Bottle blowing machines
- Pelletisers
- Powder coating machinery
EMC immunity
Figures are design values; verify the EMC requirements of your installation before commissioning.
- Partitioned terminal blocks keep the mains, output and sensor wiring in separate zones; plated screws are specified for vibration resistance.
- Fuzzy PID with one-key autotuning that returns to control automatically.
- The front has two four-digit rows, AT / OUT / AL2 / AL1 lamps and four keys; every setting is reachable without opening the case.
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
Which sensors can the TK6D read?
Thermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default
What output options does the TK6D have?
Relay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA)
What supply voltage does the TK6D need?
100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2)
How accurate is the TK6D?
±0.5°C, at 0.1°C resolution
Does the TK6D have alarm outputs?
One alarm (code 1) or two (code 2), each with a selectable alarm mode
What is the temperature range?
0–400°C as standard; 0–1200°C and 0–1370°C to order
Related guides
How to Switch TK6D Temperature Controller to SSR Output Mode
This blog explains how to set the TK6D temperature controller to SSR output mode. Includes video demo, step-by-step guide, and highlights of this DIN rail-mounted PID unit.
Read guide Product Updates · 2026-03-24TC5-S PID Temperature Controller: Model Code, Terminals, Outputs and Commissioning
A working reference for the TC5-S 1/16 DIN digital PID temperature controller: how to read the model code, the electrical specification, terminal-by-terminal wiring, how to choose…
Read guide Technical Guides · 2025-04-15How to Wire REX-C100/C400/C700 Temperature Controllers with Relay and SSR Output
This blog provides a comprehensive guide on wiring REX series temperature controllers, including the C100, C400, and C700 models. It explains both relay and solid-state relay…
Read guideRelated models
All Temperature Controllers
TK6Z DIN Rail PID Temperature Controller — one loop, relay, SSR drive or both
SE-TK6Z
The TK6Z is the shallow member of the TK6 series: one loop in a rail-mounted module that clips on and needs no cut-out, so the cabinet door stays…
View details
TK6 Series Intelligent Digital PID Temperature Controller with RS485 Communication
SE-TK6
TK6 Series Digital PID Temperature Controller is an intelligent industrial temperature control instrument designed for accurate and stable…
View details
TH4M DIN Rail Four-Channel Temperature Controller — four zones on one module
SE-TH4M
The TH4M puts four measuring channels on one DIN-rail module, so a cabinet full of single-loop meters becomes one strip with four readings stacked on…
View details
REX-C100/C400/C700/C900 Digital PID Temperature Controller
SE-C100
REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.