Temperature Controllers

TK6D with relay plus ssr drive

TK6D-24RV-RS485, in the 23 mm rail case. K, E, J, S, R thermocouple or Pt100 input, 0.1 C resolution, 0-400 C by default.

Two TK6D single-loop DIN-rail temperature controllers side by side, showing the terminal rows, the two display rows and the four setting keys
TK6D on a 35mm DIN rail: terminals 1–12 above the display and 13–20 below, with the AT, OUT, AL2 and AL1 lamps under the readout
Output
Relay plus SSR drive
Bezel
116 x 23 x 110 mm
Panel cut-out
none - DIN rail module
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesTK6D Series (single-loop DIN-rail temperature controller)
ModelsEight order codes — 14RV, 14MA, 24RV and 24MA, each with or without RS485 — sold as twelve SKUs because every MA version is offered with a K-thermocouple default input or a 4–20mA default input (INPUT TC/RTD [Default K] or [Default 4-20MA] on the nameplate)
Control methodPID with autotuning; P = 0 switches the loop to two-position control with an adjustable hysteresis
Second outputCooling output with its own proportional band and cycle time, separated from the heating output by an adjustable dead band
InputThermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default
Temperature range0–400°C as standard; 0–1200°C and 0–1370°C to order
DisplayTwo four-digit rows for the measured value and the setpoint, with AT, OUT, AL2, AL1 and °C lamps
Resolution0.1°C
Accuracy±0.5°C
Control outputRelay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA)
Relay contact rating10A / 800W resistive
Alarm outputOne alarm (code 1) or two (code 2), each with a selectable alarm mode
CommunicationRS485 Modbus-RTU, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only
Supply voltage100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2)
Front dimensions20 × 76.8mm label window in a 23mm-wide body
Depth116mm from the front face back to the rail, 110mm overall height and 100mm of body between the terminal shrouds
Mounting35mm DIN rail, clip-on, no panel cut-out
HousingABS, self-extinguishing
Weight0.2kg packed
CertificationCE
Modbus registersMeasured value, setpoint, output percentage, autotuning, both alarms and their hysteresis, P, I, D, the integral overshoot limit, the control period, the input offset, the second output's proportional band and cycle time, the dead band and a timer block are all in holding registers; the measured value and the display status are read-only.

Product overview

Part no. SE-TK6D

Also known as: TK6D temperature controller · TK6D PID controller · TK6D controlador de temperatura

The TK6D is the DIN-rail member of the TK6 series: the same control loop as the panel instruments, folded into a module that clips onto the rail and needs no cut-out. One input takes a thermocouple or a three-wire Pt100, and the loop runs PID with autotuning — set P to zero and it becomes two-position control with an adjustable hysteresis instead. A second output is there for cooling, with its own proportional band and cycle time and a dead band between the two, so a chamber that overshoots can be pulled back rather than left to coast. The relay contact and the SSR drive both sit on the terminal block; the other version puts a current output there instead. RS485 Modbus-RTU is available on either version and exposes the measured value, the setpoint, the tuning constants and the alarm settings, which is what lets the module report into a PLC rather than only hold a temperature. Everything is set from the four keys on the face.

Ordering code

TK6D-24RV-RS485

TK6D-24RV-RS485, in the 23 mm rail case. K, E, J, S, R thermocouple or Pt100 input, 0.1 C resolution, 0-400 C by default.

Order codeTK6D-24RV-RS485
Bezel (mm)116 x 23 x 110 mm
Cut-out (mm)none - DIN rail module
OutputRelay plus SSR drive
Output terminalstypical; confirm against the case label
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: Two alarms and RS485, the version for a supervised process

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Key features

  • One loop on a rail-mounted module — no panel cut-out and no separate meter in the door
  • Universal input: Thermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default
  • PID with autotuning; P = 0 switches the loop to two-position control with an adjustable hysteresis
  • A second output for cooling, with its own proportional band, cycle time and a dead band against the heating output
  • Relay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA)
  • One alarm (code 1) or two (code 2), each with a selectable alarm mode
  • RS485 Modbus-RTU, 8N1, address 1–250, 300–38400 bps (19200 by default); function codes 03 and 06 only
  • 100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2) supply
  • Two four-digit rows for the measured value and the setpoint, with lamps for autotuning, the output and both alarms
  • Terminals along both edges, numbered 1–20 and printed on the face, so a module can be replaced without the drawing
  • ABS, self-extinguishing housing, CE marked

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

Every TK6 is ordered by the same nine-character code; this page's example is TK6D-14RV (the D case, one alarm, 100–240VAC, relay + SSR).

TSeries
KSetting
6Family
DCase
1Auxiliary
4Supply
RVControl output

Case

S
48 × 48mm panel case
M
72 × 72mm panel case
H
48 × 96mm panel case
L
96 × 96mm panel case
D
DIN-rail case (19.7 × 75 × 116mm)

Auxiliary

1
One alarm output
2
Two alarm outputs
3
RS485 communication

Supply

2
24VAC 50/60Hz or 24–48VDC
4
100–240VAC 50/60Hz

Control output

RV
Relay contact + SSR drive
MA
4–20mA output
  • H is the horizontal 48 × 96mm case (TK6H) and L is the 96 × 96mm case.
  • RS485 is also sold as a suffix (e.g. TK6D-14RV-Rs485) while keeping the auxiliary position at 1 or 2.

Dimensions and rail mounting

The case measures 116 × 23 × 110mm: a 23mm-wide front, 110mm tall overall, and 116mm from the front face back to the rail. The 100mm body between the two terminal shrouds accounts for the 10mm difference. The clip takes a standard 35mm DIN rail, so there is no panel cut-out to make.

Supplier dimension sheet for the TK6D: the front 23mm wide and 110mm tall with a 20 × 76.8mm display window, the side 116mm deep with a 100mm body between the two terminal shrouds and a 35mm rail clip on the back, and the two lower drawings showing the case hooked onto a DIN rail
The manufacturer's own sheet, drawn four ways. The front is 23mm across and 110mm from terminal shroud to terminal shroud; the side puts 100mm of body between those shrouds and 116mm from the front face to the back of the clip. The two lower drawings are the reason there is no panel cut-out to make: the case hooks over the top edge of a 35mm rail and the spring clip catches the bottom lip. The terminal screws face up and down, not sideways, so the clearance you have to leave is above and below the case.
MeasurementValue
Display / key window20 × 76.8mm
Front width23mm
Overall height110mm
Body between terminal shrouds100mm
Depth behind the front face116mm
Rail35mm DIN
  • Dimensions are nominal; allow ±0.2mm tolerance.
  • The module clips onto the rail from the front, with terminal screws facing up and down — leave clearance above and below for a screwdriver, not just for the case.
  • The D case measures 23 × 110mm overall; 19.7 × 75mm is the rail mounting footprint. Use 23 × 110mm when laying out the rail.

Terminals and wiring

The TK6D has twenty screw terminals in two stepped blocks, numbered 1–20 on the front. Three terminal assignments are shown below, one for each version and input configuration. Check the full SKU and the INPUT line on the nameplate before wiring, then match the assignment to the terminal block in your hand.

Terminal assignment

ALM19 – 10ALM211 – 12OUTrelay contact, 6 – 7Control output · RV versionSSR1 + / 2 −100-240VAC50/60Hz+−tcRtBBASensor input3-wire RTD or thermocoupleRS48517 A / 18 B-Rs485 versions only19, 20 not usedTEMPERATURE CONTROLLERMODELTK6D-14RV / 24RVINPUTTC/RTD [ Default K ]OUTPUTRELAY/SSR + ( ALM×1 / ×2 )SUPPLY100-240VAC, 50/60HzCASE116 × 23 × 110mm9101112567812341314151617181920
RV versions — relay contact on 6–7 plus the SSR drive on 1–2
ALM19 – 10ALM211 – 124-20mA5 − / 7 +Control output · MA versionSSR1 + / 2 −100-240VAC50/60Hz+−tcRtBBASensor input3-wire RTD or thermocoupleRS48517 A / 18 B-Rs485 versions only19, 20 not usedTEMPERATURE CONTROLLERMODELTK6D-14MA / 24MAINPUTTC/RTD [ Default K ]OUTPUT4-20MA + ( ALM×1 / ×2 )SUPPLY100-240VAC, 50/60HzCASE116 × 23 × 110mm9101112567812341314151617181920
MA version, INPUT TC/RTD [Default K] — one current loop: 4–20mA output on 5 (−) and 7 (+), RTD or thermocouple on 13–15
ALM19 – 10ALM211 – 124-20mA5 − / 7 +Control output · MA versionSSR1 + / 2 −100-240VAC50/60Hz4-20mA14 − / 15 + · inputRS48517 A / 18 B-Rs485 versions only19, 20 not usedTEMPERATURE CONTROLLERMODELTK6D-14MA / 24MAINPUTTC/RTD [ Default 4-20MA ]OUTPUT4-20MA + ( ALM×1 / ×2 )SUPPLY100-240VAC, 50/60HzCASE116 × 23 × 110mm9101112567812341314151617181920
MA version, INPUT TC/RTD [Default 4-20MA] — two current loops: 4–20mA output on 5 (−) and 7 (+), 4–20mA input on 14 (−) and 15 (+)

Where the numbers sit on the module

Upper block · 1–12Lower block · 13–201SSR +2SSR −3AC ~4AC ~5mA − / —6OUT / —7OUT / mA +8not used9ALM110ALM111ALM212ALM213B / TC +14B / TC −15A16not used17A / RS48518B / RS48519not used20not usedRV version first in the slashed labels, MA version second14 and 15 become the 4-20mA input on the Default 4-20MA version
TerminalFunctionNote
1SSR drive, +DC pulse output for a solid-state relay, not a mains terminal
2SSR drive, −—
3Supply, 100–240VAC50/60Hz, either way round
4Supply, 100–240VAC—
5Control output — MA versions: 4–20mA −Unused on RV versions
6Control output — RV versions: relay contactUnused on MA versions
7RV: other side of the relay contact · MA: 4–20mA +—
8Not used—
9Alarm 1 contact—
10Alarm 1 contact—
11Alarm 2 contactFitted on 24-code versions only
12Alarm 2 contact—
13Sensor, B · thermocouple +Three-wire RTD: B on 13 and 14, A on 15. Unused when the default input is 4–20mA
14Sensor, B · thermocouple −On the Default 4-20MA version this is the current input − instead
15Sensor, AOn the Default 4-20MA version this is the current input + instead
16Not used—
17RS485 A (+)Fitted on -Rs485 versions only
18RS485 B (−)—
19Not used—
20Not used—
  • The 1–2 SSR pair and the 6–7 relay contact are two different things: the first is a low-voltage DC drive for an external solid-state relay, the second switches the load. On RV versions both are fitted and the output mode is selected in the parameter set; MA versions use the 4–20mA output. Confirm the output type on the nameplate before wiring.
  • Alarm count follows the code: 14-code versions carry one alarm on 9–10, 24-code versions carry two on 9–10 and 11–12. Wire ALM2 only on a version whose full SKU reads 24 or carries 2 in the auxiliary position.
  • MA versions are available with two input configurations. With INPUT TC/RTD [Default K], terminals 13–15 take a K thermocouple or three-wire RTD and there is one 4–20mA loop, the output on 5 and 7. With INPUT TC/RTD [Default 4-20MA], the input is 4–20mA on 14 (−) and 15 (+) and there are two current loops, one in and one out. Both SKUs share the MA suffix — confirm the default input when ordering.
  • RS485 lives on 17 (A) and 18 (B). It is a suffix on the SKU, not something a non-communicating version can be upgraded to by adding wire: 19 and 20 are unused.
  • The stepped blocks keep mains, output and sensor wiring in separate zones: three rows of four above the display, two rows of four below. Plated screws and numbers printed beside each position allow a module to be replaced quickly.

RS485 Modbus-RTU register map

Communicating versions expose the whole control loop over RS485 Modbus RTU, with one start bit, eight data bits and one stop bit. Function 03 (read holding registers) and 06 (write a single register) are supported. Addresses are 1–250 and baud rates 300–38400; both default settings are reached with the menu code Con = 100.

Protocol
Modbus RTU · 1 start + 8 data + 1 stop
Address (Addr)
1–250 · default 1 · Con = 100
Baud rate (bps)
300–38400 · default 19200 · Con = 100
Function codes
03 read / 06 write only
AddressCodeRegisterAccess
0000HPVMeasured valueR
0001HLEDDisplay / lamp statusR
0002HSVSetpointR/W
0003HOOTOutput percentageR
0004HATAutotuning switchR/W
0005HAL1Alarm 1 valueR/W
0006HAL2Alarm 2 valueR/W
0007HHY1Alarm 1 hysteresisR/W
0008HHY2Alarm 2 hysteresisR/W
0009HPProportional bandR/W
000AHIIntegral termR/W
000BHDDerivative termR/W
000CHARIntegral overshoot limit, %R/W
000DHTControl periodR/W
000EHPB (SC)Measured-value correctionR/W
000FHHYMain hysteresis (active when P = 0)R/W
0010HAL1TAlarm 1 modeR/W
0011HAL2TAlarm 2 modeR/W
0012HPCSecond output, proportional bandR/W
0013HTCSecond output, control periodR/W
0014HDBDead bandR/W
0015HCTHCurrent detector inputR/W
0016HACTSensor-break alarm valueR/W
0017HTONTimer function switchR
0018HETTimer modeR/W
0019HTIETimer time unitR/W
001AHALTTimer temperature hysteresisR/W
001BHBLAlarm time after the timer endsR/W
001CHSTTimer setpointR/W
001DHTIMCurrent timer value (seconds if TIE = 0, minutes if TIE = 1)R
001EHTISCurrent timer seconds (TIE = 1); BL counter, alarm 2 output timeR

Verify scaling, word order, register width and parity against your master before writing: a PID constant written with the wrong decimal scaling will move the loop, not the setpoint.

Applications and immunity

Designed for single-loop control on plastics machinery. In a twin-screw extruder, OUT1 drives the barrel heaters and OUT2 drives the fan or cooling valve, with the dead band between them keeping the melt temperature steady. The same two-output arrangement is why the second proportional band and cycle time appear in the register map.

Typical applications

  • Injection moulding machines
  • Extruders, including twin-screw
  • Film blowing machines
  • Bottle blowing machines
  • Pelletisers
  • Powder coating machinery

EMC immunity

3KV
Surge / lightning protection
8KV
Electrostatic discharge protection
10V/m
Radiated immunity

Figures are design values; verify the EMC requirements of your installation before commissioning.

  • Partitioned terminal blocks keep the mains, output and sensor wiring in separate zones; plated screws are specified for vibration resistance.
  • Fuzzy PID with one-key autotuning that returns to control automatically.
  • The front has two four-digit rows, AT / OUT / AL2 / AL1 lamps and four keys; every setting is reachable without opening the case.

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

Which sensors can the TK6D read?

Thermocouple K, J, E, S, R; RTD Pt100, three-wire; type selected in the menu, K by default

What output options does the TK6D have?

Relay contact plus an SSR drive output (code RV), or a 4–20mA output (code MA)

What supply voltage does the TK6D need?

100–240VAC 50/60Hz (code 4) or 24VAC / 24–48VDC (code 2)

How accurate is the TK6D?

±0.5°C, at 0.1°C resolution

Does the TK6D have alarm outputs?

One alarm (code 1) or two (code 2), each with a selectable alarm mode

What is the temperature range?

0–400°C as standard; 0–1200°C and 0–1370°C to order

Related guides

Need help selecting the right model?