Temperature Controllers
REX-C700FK02-M*AN — REX-C700 with built-in electromechanical relay
The version to order when the controller only has to close a contactor coil, or a small heater under 3A.

- Output
- Built-in electromechanical relay, 250VAC 3A, dry contact
- Bezel
- 72 × 72
- Panel cut-out
- 68 × 68
Technical specifications
| Series | REX-C Series classic universal-input PID temperature controller |
|---|---|
| Models | REX-C100 / C400 / C410 / C700 / C900 |
| Display | Dual 4-digit LED display, red PV row above green SV row |
| Control method | ON/OFF, position PID, continuous PID; reverse-acting (F) or direct-acting (D) |
| Input | Universal input with K type fitted as standard (sensor not included). Thermocouple; Pt100; Cu50; 0–5V; 1–5V; mA signals. Input families: K (K01–K07, K13–K14), J (J01–J06), R/S/B, E/N/T, Pt100 (D01–D10), Cu50 (P01–P10), 0–5V 401, 1–5V 601, 0–20mA 701, 4–20mA 801 (external 250Ω resistor where specified) |
| Control output | M relay 250VAC 3A; V SSR drive 0–12VDC; 8 current output 0–10mA or 4–20mA; T hybrid SCR trigger; analog 0–5V / 1–5V |
| Alarm output | Up to 2 alarm outputs; N none or A–L selectable deviation / band / absolute modes |
| Supply voltage | 220VAC, 50/60Hz; 10VA at 220V |
| Accuracy | ±0.5%FS or ±1.0%FS |
| Temperature range | 0–400°C default; 0–1370°C maximum, set by the input code |
| Sampling period | 0.5s |
| PID setting range | P 0 to full range; I / D 0–3600s; control period 1–100s |
| Alarm range | freely settable across the full range |
| Operating environment | 0–50℃; 30–85% RH, no corrosive gas |
| Panel size | REX-C100 48×48; C400 48×96; C410 96×48; C700 72×72; C900 96×96mm |
| Panel cutout | REX-C100 45×45; C400 45×92; C410 92×45; C700 68×68; C900 92×92mm |
| Dimensions (depth) | REX-C100 98.5mm; C400 and C900 100mm behind the panel; 110–112mm overall including the terminal shroud |
| Weight | REX-C100 0.193kg; C400 0.294kg; C900 0.371kg |
| Mounting | Panel mount, snap-in retaining clip |
Product overview
Part no. SE-C100industry model C100
Also known as: RKC REX-C100 · REX-C100 temperature controller · REX-C100 PID controller · REX-C100 controlador de temperatura
REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and automatic temperature regulation applications. It supports PID control, relay or SSR output, multiple sensor inputs such as PT100, Cu50, K, S, E and J, and dual LED display for PV and SV values.
Ordering code
REX-C700FK02-M*AN
The version to order when the controller only has to close a contactor coil, or a small heater under 3A.
| Order code | REX-C700FK02-M*AN |
|---|---|
| Bezel (mm) | 72 × 72 |
| Cut-out (mm) | 68 × 68 |
| Output | Built-in electromechanical relay, 250VAC 3A, dry contact |
| Output terminals | 3 – 4 |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Reading this order code
How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.
| Position | Reads | Meaning |
|---|---|---|
| 1 | REX-C700 | 72 × 72 mm bezel on a 68 × 68mm panel cut-out |
| 2 | F | Control mode: reverse acting, the usual choice for heating |
| 3 | K02 | Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50 |
| 4 | C700FK02 | Built-in electromechanical relay, 250VAC 3A, dry contact |
| 5 | *AN | Alarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead |
How this build compares with the others
Same case, same cut-out, same supply. The differences are the ones below.
| Order code | Output stage | What it can switch | Terminals |
|---|---|---|---|
| REX-C700FK02-M*ANthis page | Built-in electromechanical relay, 250VAC 3A, dry contact | Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR | 3 – 4 |
| REX-C700FK02-M*AN | Built-in electromechanical relay, 250VAC 3A, dry contact | Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR | on the case diagram |
| REX-C700FK02-V*AN | Voltage pulse output, 0–12VDC, for an external solid state relay | Drives the input of an SSR and nothing else; the load current is the SSR's rating, not the controller's | on the case diagram |
| REX-C700FK02-8*AN | Analogue current output, 4–20mA (0–10mA on request) | A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue input | on the case diagram |
Key features
- Digital dual LED display for PV and SV values
- PID control for accurate and stable temperature regulation
- 24-hour continuous temperature control
- Relay output or SSR output optional
- Supports multiple input types: PT100, Cu50, K, S, E, J
- Multiple models available: REX-C100, C400, C410, C700, C900
- Over-temperature protection and alarm function
- Simple panel operation and easy parameter setting
- Suitable for heating, cooling, and industrial automation systems
- Customization available for different application requirements
Downloads
Works with
The parts that go into the same panel and are usually ordered with it.
Ordering & Selection Guide
REX plus six positions: panel size (overall depth ~112mm, ~100mm behind panel), control action, input & range, main output, and two alarm outputs.
① · Panel size (mm)
- C100
- 48×48, cut-out 45×45
- C400
- 48×96, cut-out 45×92
- C410
- 96×48, cut-out 92×45
- C700
- 72×72, cut-out 68×68
- C900
- 96×96, cut-out 92×92
② · Control action
- F
- PID, reverse action — heating
- D
- PID, direct action — cooling
③ · Common input & range
- K02
- K thermocouple, 0–400 °C
- E02
- E thermocouple, 0–1000 °C
- D10
- Pt100 RTD, 0.0–500 °C
- P02
- Cu50 RTD, 0.0–150.0 °C
④ · Main output
- M
- Relay contact (RELAY)
- V
- Voltage pulse (SSR drive)
- 8
- Current output 4–20mA
⑤⑥ First & second alarm codes (N, A–L — 12 options)
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
| Input | Code and measuring range |
|---|---|
| KThermocouple | K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C |
| JThermocouple | J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C |
| RThermocouple (accuracy not guaranteed over 0–399 °C) | R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C |
| SThermocouple (accuracy not guaranteed over 0–399 °C) | S01 0–1600 °CS02 0–1769 °C |
| BThermocouple (accuracy not guaranteed over 0–399 °C) | B01 400–1800 °CB02 0–1769 °C |
| EThermocouple | E01 0–800 °CE02 0–1000 °C |
| NThermocouple | N01 1–1300 °CN02 0–1300 °C |
| TThermocouple (accuracy held from −199 to 100 °C) | T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C |
| PT100RTD | D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C |
| Cu50RTD | P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C |
| 0–5VDCStandard signal | 401 0.0–100.0 |
| 1–5VDCStandard signal | 601 0.0–100.0 |
| 0–20mAStandard signal, 250 Ω resistor across the terminals | 701 0.0–100.0 |
| 4–20mAStandard signal, 250 Ω resistor across the terminals | 801 0.0–100.0 |
Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.
Worked example
REXC700FK02-MAB
72×72 on a 68×68 cut-out, reverse action for heating, K thermocouple to 400 °C, relay output, a deviation-high alarm on the first relay and a deviation-low alarm on the second.
Compatible sensors & outputs
also supplied as PID temperature controller, intelligent temperature controller, RKC REX-C equivalent
Show supported sensors & probe links (8: K, E, J, N, T, R / S / B, Pt100, Cu50)
| Sensor | Range | Available as |
|---|---|---|
| K | 0–400 / 0–1200 / 0–1372 °C | K / E probe thermocoupleStainless steel probeSpring-loaded M12 probeRing-terminal thermocoupleThreaded shielded-lead probe |
| E | 0–800 / 0–1000 °C | K / E probe thermocoupleStainless steel probeM6 / M8 screw-in probe |
| J | 0–600 / 0–1200 °C | Simple 4 × 40 thermocouple |
| N | 0–1300 °C | Threaded shielded-lead probe |
| T | −200–400 °C | Stainless steel probe |
| R / S / B | 0–1769 °C | Threaded shielded-lead probe |
| Pt100 | −199.9–649.0 °C | Pt100 / Cu50 sheathed RTDM6 / M8 screw-in probe |
| Cu50 | −50.0–150.0 °C | Pt100 / Cu50 sheathed RTD |
Output types and what goes with them
| Output | Rating | Order with it |
|---|---|---|
| Electromagnetic relay | 3 A at 250 VAC, resistive | — |
| SSR drive, 12 VDC | Drives a solid state relay; the module carries the load | SSR-DA single phase 10–40 A |
| Current output, 4–20 mA | Into a controller or recorder input | — |
| SCR / triac, zero-cross | Phase-angle or zero-cross firing | BDTY SCR voltage regulator |
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
Input codes and measuring ranges
Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
| Input | Code and measuring range |
|---|---|
| KThermocouple | K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C |
| JThermocouple | J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C |
| RThermocouple (accuracy not guaranteed over 0–399 °C) | R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C |
| SThermocouple (accuracy not guaranteed over 0–399 °C) | S01 0–1600 °CS02 0–1769 °C |
| BThermocouple (accuracy not guaranteed over 0–399 °C) | B01 400–1800 °CB02 0–1769 °C |
| EThermocouple | E01 0–800 °CE02 0–1000 °C |
| NThermocouple | N01 1–1300 °CN02 0–1300 °C |
| TThermocouple (accuracy held from −199 to 100 °C) | T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C |
| PT100RTD | D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C |
| Cu50RTD | P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C |
| 0–5VDCStandard signal | 401 0.0–100.0 |
| 1–5VDCStandard signal | 601 0.0–100.0 |
| 0–20mAStandard signal, 250 Ω resistor across the terminals | 701 0.0–100.0 |
| 4–20mAStandard signal, 250 Ω resistor across the terminals | 801 0.0–100.0 |
Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.
Panel and keys
Two four-digit rows and five lamps in the order REX prints them — OUT1, OUT2, AT, ALM1, ALM2. The auto-tuning lamp sits third here, not first as on the CH series. Four keys: set, shift, decrease, increase.
- PV
- Process value (PV)
- SV
- Set value (SV)
- OUT1 / OUT2
- Control output indicators (OUT1 / OUT2)
- AT
- Auto-tuning indicator (AT)
- ALM1 / ALM2
- Alarm output indicators (ALM1 / ALM2)
- SET
- Set key
- ◁
- Shift key
- ∨
- Decrease key
- ∧
- Increase key
Panel dimensions
All five sizes share one depth: 112mm to the back of the case, of which 100mm sits behind the panel line. Only the front changes, so a panel designed for one size needs the same clearance for any other.
| Model | Panel (mm) | Cut-out (mm) | Total depth | Body depth |
|---|---|---|---|---|
| REX-C100 | 48 × 48 | 45 × 45 | 112mm | 100mm |
| REX-C400 | 48 × 96 | 45 × 92 | 112mm | 100mm |
| REX-C410 | 96 × 48 | 92 × 45 | 112mm | 100mm |
| REX-C700 | 72 × 72 | 68 × 68 | 112mm | 100mm |
| REX-C900 | 96 × 96 | 92 × 92 | 112mm | 100mm |
REX-C400 / C410 / C900 wiring
The sixteen-terminal bodies, in six panels: contactor, solid state relay and alarm light, with the relay and SSR terminal references at the foot of the sheet. This block is numbered 1–8 down the left and 9–16 down the right, and the supply lands on 2 and 3 — different from the small cases drawn above, so read the number on the instrument rather than the one you remember.
REX-C400 / C410 / C900 · wiring and terminal references
Contactor version: 3–6 jumper, and the relay closes 4 to 3 so the coil sits across A1 and A2. SSR version: no jumper, the 12 VDC drive leaves on 4 (+) and 5 (−). Sensors on every version: thermocouple blue to 15 (−) and red to 16 (+); three-wire RTD with A on 14 and B on 15 and 16.
Documents for this family
- Strong Electric REX C Instruction Manual411 KB · 2026-11-16
- REX-C400 / C410 / C900 wiring309 KB · 2026-11-18
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the REX-C100/C400/C700/C900 need?
REX-C100 48×48; C400 48×96; C410 96×48; C700 72×72; C900 96×96mm. The cut-out is REX-C100 45×45; C400 45×92; C410 92×45; C700 68×68; C900 92×92mm
Which sensors can the REX-C100/C400/C700/C900 read?
Universal input with K type fitted as standard (sensor not included). Thermocouple; Pt100; Cu50; 0–5V; 1–5V; mA signals. Input families: K (K01–K07, K13–K14), J (J01–J06), R/S/B, E/N/T, Pt100 (D01–D10), Cu50 (P01–P10), 0–5V 401, 1–5V 601, 0–20mA 701, 4–20mA 801 (external 250Ω resistor where specified)
What output options does the REX-C100/C400/C700/C900 have?
M relay 250VAC 3A; V SSR drive 0–12VDC; 8 current output 0–10mA or 4–20mA; T hybrid SCR trigger; analog 0–5V / 1–5V
What supply voltage does the REX-C100/C400/C700/C900 need?
220VAC, 50/60Hz; 10VA at 220V
How accurate is the REX-C100/C400/C700/C900?
±0.5%FS or ±1.0%FS
Does the REX-C100/C400/C700/C900 have alarm outputs?
Up to 2 alarm outputs; N none or A–L selectable deviation / band / absolute modes
Related guides
How to Wire REX-C100, REX-C700 and REX-C400/C900 Temperature Controllers
English wiring diagrams for REX-series temperature controllers, including relay, AC contactor, SSR, K-type thermocouple and 3-wire PT100 connections.
Read guide Technical Guides · 2025-04-15How to Wire REX-C100/C400/C700 Temperature Controllers with Relay and SSR Output
This blog provides a comprehensive guide on wiring REX series temperature controllers, including the C100, C400, and C700 models. It explains both relay and solid-state relay…
Read guide Product Updates · 2026-03-24TC5-S PID Temperature Controller: Model Code, Terminals, Outputs and Commissioning
A working reference for the TC5-S 1/16 DIN digital PID temperature controller: how to read the model code, the electrical specification, terminal-by-terminal wiring, how to choose…
Read guideRelated models
All Temperature Controllers
C700 Digital Temperature Controller, 72 × 72mm Panel Frame | Strong Electric
SE-C700
72×72mm · 68×68mm · 24mm overall, 20mm of it behind the panel
View details
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View details
TC4W Digital PID Temperature Controller
SE-TC4W
96×48mm (1/8 DIN) · 92×45mm · 75mm total, 71mm behind the panel
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.