Thermocouples & RTD Sensors
WRN-130, Pt100 RTD, 500mm insertion
The 500mm build of the Pt100 RTD sensor.

- Output
- Pt100 RTD, 500mm insertion depth
- Bezel
- sheath
- Panel cut-out
- process thread
Technical specifications
| Product type | Sheathed probe on a cast aluminium terminal head, for pipes, tanks, furnaces and flues |
|---|---|
| Element (WRNK-236) | K type as standard; S, E, J, T, R, B and N to order |
| Element (WZP-236) | Pt100 thin-film element on the WZP-236, Type K thermocouple on the WRNK-236 |
| Measuring range (K type) | 0–800 °C |
| Measuring range (Pt100) | -50–400 °C |
| Probe diameter | 6mm as standard |
| Model codes | WRN-130 without a process thread and WRN-230 with one, each in a K or a Pt100 version; the same body is also supplied as WRNK-236 and WZP-236 |
| Depths from stock | 50, 100, 150, 200, 300, 400 and 500 mm, with other depths to order |
| Insertion length | 300mm as standard as standard; 50mm to 1000mm in the steps the supplier lists |
| Sheath material | 304 stainless steel |
| Process connection | G1/2 as standard |
| Head | Cast aluminium terminal head with a hinged chain cover |
| Terminals | Two-wire on the K version; Three-wire as standard; two- or four-wire to order on the Pt100 version |
| Output | Sensor output as standard; transmitter output to order |
| Mounting | Direct insertion, threaded, flange or clamp |
| Sealing | Sealed head, resistant to water and dust |
| Typical applications | Petrochemical and chemical plant, metallurgy, power generation, machinery, textile and HVAC ductwork |
Product overview
Part no. SE-TC-WRNK236industry model TC-WRNK236
Also known as: Sheathed Thermocouple temperature sensor · Sheathed Thermocouple probe
One mechanical version, two elements. The WRNK-236 takes a K type thermocouple for readings up to 0–800 °C; the WZP-236 takes a Pt100 for the colder end, down to -50–400 °C, where a thermocouple's accuracy starts to cost more than it is worth. Both use the same 6mm as standard 304 sheath, the same G1/2 thread and the same cast aluminium head, so the choice is made once, at ordering, and the spare fits either.
Ordering code
WRN-130 Pt100 · 500mm
The 500mm build of the Pt100 RTD sensor.
| Order code | WRN-130 Pt100 · 500mm |
|---|---|
| Bezel (mm) | sheath |
| Cut-out (mm) | process thread |
| Output | Pt100 RTD, 500mm insertion depth |
| Output terminals | head terminals |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: The insertion depth is what the wall thickness decides; the element is what the instrument reads
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Key features
- K type reads 0–800 °C; the Pt100 version reads -50–400 °C, so the same probe covers a flue and a chilled line without changing the mounting.
- Pt100 is read on Three-wire as standard; two- or four-wire to order. The third wire cancels the lead resistance that would otherwise read as temperature.
- The K version is Two-wire. Two wires is all a thermocouple needs; the head has the terminals and the ceramic block to land them on.
- A 6mm as standard 304 sheath on G1/2 as standard. The sheath is the part that sees the process, so its grade is stated rather than left as single-word stainless.
- Cast aluminium head with a hinged chain cover — the cover is why the terminals stay dry when the head is washed down or rained on.
- Direct insertion, threaded, flange or clamp — the same probe is supplied plain for a welded boss, threaded for a pipe, flanged for a tank or clamped for a duct.
Works with
The parts that go into the same panel and are usually ordered with it.
Thermocouple index and ranges
Eight letter codes cover almost everything on a panel. The letter is the alloy pair, and the range beside it is what the pair can be trusted to measure — outside that range the millivolt curve stops being usable, whatever the controller claims.
| Type | Alloys | Working range | Where it is used |
|---|---|---|---|
| K | NiCr–NiSi | −200…1300 °C | The default. Ovens, extruders, heat presses, kilns below 1200 °C |
| E | NiCr–CuNi | −200…800 °C | Highest EMF per degree, so the noisiest installations still read |
| J | Fe–CuNi | −40…750 °C | Older plant and reducing atmospheres; iron oxidises if it gets wet |
| N | NiCrSi–NiSi | −200…1300 °C | Where K drifts: long holds, cycling furnaces, sulphur-bearing gas |
| T | Cu–CuNi | −200…350 °C | Low temperature and cryogenic work, chillers, food equipment |
| S | Pt10Rh–Pt | 0…1600 °C | Kilns and glass; needs a thin sheath and clean air |
| R | Pt13Rh–Pt | 0…1600 °C | Same duty as S with a higher output; platinum and ceramic firing |
| B | Pt30Rh–Pt6Rh | 600…1700 °C | Very high temperature only: glass melt, refractory, 1500 °C and above |
Ranges are the industrial working range, not the full IEC 60584 table. Type B has almost no output below 600 °C, which is why it is never specified for a low-temperature job.
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
WRN-130
sheathmm · cut-out process threadmm
WRN-230
sheathmm · cut-out process threadmm
How to specify
WZP-236-6-300-G12 is a Pt100 version in a 6 mm sheath with a 300 mm insertion on a G1/2 thread. The model block is the only one that changes the electronics: WRNK is the K type thermocouple and WZP is the Pt100. Everything after it is mechanical, so a spare ordered against the same code fits either.
Fixed in this familyChosen when ordering
| Position | Code | Selects |
|---|---|---|
| Element | WRNK-236 | K type thermocouple, 0 to 800°C, two-wire |
| WZP-236 | Pt100 thin-film, -50 to 400°C, three-wire | |
| Sheath diameter | 6 | 6 mm |
| Insertion length | 50 | 50 mm |
| 100 | 100 mm | |
| 200 | 200 mm | |
| 300 | 300 mm (standard) | |
| 500 | 500 mm | |
| 800 | 800 mm | |
| 1000 | 1000 mm | |
| Process connection | G12 | G1/2 (4 fen), standard |
| N12 | NPT 1/2 | |
| M20 | M20 × 1.5 | |
| FL | Flange or clamp instead of a thread |
- The element block decides three things at once — range, accuracy class and wiring. K is two-wire and reads 0 to 800°C; Pt100 is three-wire and reads -50 to 400°C. Ordering the wrong block is not a swap of a part, it is a different input card.
- Insertion length is the process-side length to the seating face, not the overall length. Measure the thread plus the reach into the pipe, not the whole probe.
- The transmitter output option is not in the code because the output range is set per order. State it with the enquiry or you will receive the plain sensor output.
Dimensions
Insertion length is measured on the process side, from the tip to the seating face under the thread — not the length of the whole assembly, and not the head. The head adds height above the thread, which is what decides whether the sensor clears a lagging jacket or a duct wall. Dimensions are nominal, ±1 mm.
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 12 months
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Certification and model-specific options
Certification
If CE or RoHS documentation is required, identify the exact model and ask us to confirm which current documents apply with the quotation. ATEX / IECEx zone-rated assemblies are not listed in this range; confirm requirements before specifying.
OEM and private label
Private-label marking or packaging may be available for selected probe models. The marking locations, supported construction and minimum quantity are confirmed against the model and order in the quotation.
What can be changed
Thread, sheath, lead insulation, terminal style and insertion length depend on the probe model and construction. Send the drawing or installation dimensions and we will confirm available options and quote accordingly.
Tolerance has to be stated
A tolerance class is not implied by a part number. Say Class 1 or Class 2 for K and E type (IEC 60584), Class A or B for Pt100 (IEC 60751), on the order — otherwise the probe is built to the standard class and the loop may not hold the accuracy you designed for.
Pressure
None of these probes is rated for pressure service. If the sensor goes into a pressurised pipe or vessel, ask for a thermowell and we will supply a probe that fits it — a bare sheath in a pressurised line is a leak waiting to happen.
Related guides
How to Choose a Threaded Temperature Sensor: K, E Thermocouple or Pt100 RTD
A selection and installation guide for M6 / M8 threaded temperature sensor probes: how thermocouples and RTDs differ, which element to specify, how thread size and mounting affect…
Read guide Technical Guides · 2026-08-27How to Wire CH102, CH402, CH702 and CH902 PID Temperature Controllers
A practical wiring guide for CH102, CH402, CH702 and CH902 PID temperature controllers, covering power, AC contactor and SSR control, thermocouple and Pt100 sensors, alarms and…
Read guide Technical Guides · 2026-08-23How to Wire REX-C100, REX-C700 and REX-C400/C900 Temperature Controllers
English wiring diagrams for REX-series temperature controllers, including relay, AC contactor, SSR, K-type thermocouple and 3-wire PT100 connections.
Read guideRelated models
All Thermocouples & RTD Sensors
NTC Thermistor Temperature Sensor Probe | Stainless, Waterproof, Custom Lead
SE-NTC-PROBE
An NTC thermistor reads resistance rather than microvolts, so the same probe that suits a controller also suits a $5 thermostat: the resistance…
View details
Simple-Type Thermocouple or RTD | 4 × 40mm Probe, Clamp Mount, K / E / Pt100 / Cu50
SE-TC-4X40
The plainest sensor in the range: a 4 × 40 mm stainless probe on a braided lead, clamped against the part instead of screwed into it. Bolt the clamp…
View details
K/E Type Probe Thermocouple Temperature Sensor
SE-TC-KE
A Ø5mm probe in a spring housing. The thread section fixes it to a bracket or a tapped hole, and the spring keeps the tip pressed against the part,…
View details
Probe-Type Stainless Steel Thermocouple Temperature Sensor (K, E Thermocouple or PT100 / CU50 RTD)
SE-TC-SS
An M12 threaded stainless probe for a tapped hole in a platen, barrel, mould, duct or oven wall, where the tip has to sit in the metal rather than in…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.