Thermocouples & RTD Sensors

WRN-230, Pt100 RTD, 50mm insertion

The 50mm build of the Pt100 RTD sensor.

WRN-130 and WRN-230 armoured thermocouples with cast aluminium heads
WRN-130 on the left without a process thread, WRN-230 on the right with one.
Output
Pt100 RTD, 50mm insertion depth
Bezel
sheath
Panel cut-out
process thread
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

Product typeSheathed probe on a cast aluminium terminal head, for pipes, tanks, furnaces and flues
Element (WRNK-236)K type as standard; S, E, J, T, R, B and N to order
Element (WZP-236)Pt100 thin-film element on the WZP-236, Type K thermocouple on the WRNK-236
Measuring range (K type)0–800 °C
Measuring range (Pt100)-50–400 °C
Probe diameter6mm as standard
Model codesWRN-130 without a process thread and WRN-230 with one, each in a K or a Pt100 version; the same body is also supplied as WRNK-236 and WZP-236
Depths from stock50, 100, 150, 200, 300, 400 and 500 mm, with other depths to order
Insertion length300mm as standard as standard; 50mm to 1000mm in the steps the supplier lists
Sheath material304 stainless steel
Process connectionG1/2 as standard
HeadCast aluminium terminal head with a hinged chain cover
TerminalsTwo-wire on the K version; Three-wire as standard; two- or four-wire to order on the Pt100 version
OutputSensor output as standard; transmitter output to order
MountingDirect insertion, threaded, flange or clamp
SealingSealed head, resistant to water and dust
Typical applicationsPetrochemical and chemical plant, metallurgy, power generation, machinery, textile and HVAC ductwork

Product overview

Part no. SE-TC-WRNK236industry model TC-WRNK236

Also known as: Sheathed Thermocouple temperature sensor · Sheathed Thermocouple probe

One mechanical version, two elements. The WRNK-236 takes a K type thermocouple for readings up to 0–800 °C; the WZP-236 takes a Pt100 for the colder end, down to -50–400 °C, where a thermocouple's accuracy starts to cost more than it is worth. Both use the same 6mm as standard 304 sheath, the same G1/2 thread and the same cast aluminium head, so the choice is made once, at ordering, and the spare fits either.

Ordering code

WRN-230 Pt100 · 50mm

The 50mm build of the Pt100 RTD sensor.

Order codeWRN-230 Pt100 · 50mm
Bezel (mm)sheath
Cut-out (mm)process thread
OutputPt100 RTD, 50mm insertion depth
Output terminalshead terminals
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: The insertion depth is what the wall thickness decides; the element is what the instrument reads

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Key features

  • K type reads 0–800 °C; the Pt100 version reads -50–400 °C, so the same probe covers a flue and a chilled line without changing the mounting.
  • Pt100 is read on Three-wire as standard; two- or four-wire to order. The third wire cancels the lead resistance that would otherwise read as temperature.
  • The K version is Two-wire. Two wires is all a thermocouple needs; the head has the terminals and the ceramic block to land them on.
  • A 6mm as standard 304 sheath on G1/2 as standard. The sheath is the part that sees the process, so its grade is stated rather than left as single-word stainless.
  • Cast aluminium head with a hinged chain cover — the cover is why the terminals stay dry when the head is washed down or rained on.
  • Direct insertion, threaded, flange or clamp — the same probe is supplied plain for a welded boss, threaded for a pipe, flanged for a tank or clamped for a duct.

Works with

The parts that go into the same panel and are usually ordered with it.

Thermocouple index and ranges

Eight letter codes cover almost everything on a panel. The letter is the alloy pair, and the range beside it is what the pair can be trusted to measure — outside that range the millivolt curve stops being usable, whatever the controller claims.

TypeAlloysWorking rangeWhere it is used
KNiCr–NiSi−200…1300 °CThe default. Ovens, extruders, heat presses, kilns below 1200 °C
ENiCr–CuNi−200…800 °CHighest EMF per degree, so the noisiest installations still read
JFe–CuNi−40…750 °COlder plant and reducing atmospheres; iron oxidises if it gets wet
NNiCrSi–NiSi−200…1300 °CWhere K drifts: long holds, cycling furnaces, sulphur-bearing gas
TCu–CuNi−200…350 °CLow temperature and cryogenic work, chillers, food equipment
SPt10Rh–Pt0…1600 °CKilns and glass; needs a thin sheath and clean air
RPt13Rh–Pt0…1600 °CSame duty as S with a higher output; platinum and ceramic firing
BPt30Rh–Pt6Rh600…1700 °CVery high temperature only: glass melt, refractory, 1500 °C and above

Ranges are the industrial working range, not the full IEC 60584 table. Type B has almost no output below 600 °C, which is why it is never specified for a low-temperature job.

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

How to specify

WZP-236-6-300-G12 is a Pt100 version in a 6 mm sheath with a 300 mm insertion on a G1/2 thread. The model block is the only one that changes the electronics: WRNK is the K type thermocouple and WZP is the Pt100. Everything after it is mechanical, so a spare ordered against the same code fits either.

WZP-236Element
6Sheath diameter
300Insertion length
G12Process connection

Fixed in this familyChosen when ordering

PositionCodeSelects
ElementWRNK-236K type thermocouple, 0 to 800°C, two-wire
WZP-236Pt100 thin-film, -50 to 400°C, three-wire
Sheath diameter66 mm
Insertion length5050 mm
100100 mm
200200 mm
300300 mm (standard)
500500 mm
800800 mm
10001000 mm
Process connectionG12G1/2 (4 fen), standard
N12NPT 1/2
M20M20 × 1.5
FLFlange or clamp instead of a thread
  • The element block decides three things at once — range, accuracy class and wiring. K is two-wire and reads 0 to 800°C; Pt100 is three-wire and reads -50 to 400°C. Ordering the wrong block is not a swap of a part, it is a different input card.
  • Insertion length is the process-side length to the seating face, not the overall length. Measure the thread plus the reach into the pipe, not the whole probe.
  • The transmitter output option is not in the code because the output range is set per order. State it with the enquiry or you will receive the plain sensor output.

Dimensions

Insertion length is measured on the process side, from the tip to the seating face under the thread — not the length of the whole assembly, and not the head. The head adds height above the thread, which is what decides whether the sensor clears a lagging jacket or a duct wall. Dimensions are nominal, ±1 mm.

Ø6 mmL = insertion, 50 to 1000 mmG1/2 as standardcast aluminium headØ6 mm 304 sheath

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
12 months
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Certification and model-specific options

Certification

If CE or RoHS documentation is required, identify the exact model and ask us to confirm which current documents apply with the quotation. ATEX / IECEx zone-rated assemblies are not listed in this range; confirm requirements before specifying.

OEM and private label

Private-label marking or packaging may be available for selected probe models. The marking locations, supported construction and minimum quantity are confirmed against the model and order in the quotation.

What can be changed

Thread, sheath, lead insulation, terminal style and insertion length depend on the probe model and construction. Send the drawing or installation dimensions and we will confirm available options and quote accordingly.

Tolerance has to be stated

A tolerance class is not implied by a part number. Say Class 1 or Class 2 for K and E type (IEC 60584), Class A or B for Pt100 (IEC 60751), on the order — otherwise the probe is built to the standard class and the loop may not hold the accuracy you designed for.

Pressure

None of these probes is rated for pressure service. If the sensor goes into a pressurised pipe or vessel, ask for a thermowell and we will supply a probe that fits it — a bare sheath in a pressurised line is a leak waiting to happen.

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.