Temperature Controllers

BT6-AK124

The BT6-AK124 build: 48 × 48 mm (1/16 DIN) bezel, relay output and two alarms, high and low deviation.

BT6 temperature controller, two-row LED display for PV and SV, 48×48 / 48×96 / 72×72 / 96×96mm
BT6: Two-row LED display for PV and SV; 48×48 / 48×96 / 72×72 / 96×96mm; Thermocouple K, J, R, S, B, E, N, T.
Output
Relay contact output, two alarms (high and low deviation)
Bezel
48 × 48
Panel cut-out
46 × 46
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesBT6 Series (panel-mount PID temperature controller with timer)
ModelsBT6-A / BT6-B / BT6-D / BT6-E
DisplayTwo-row LED display for PV and SV
Control methodPID with auto-tuning; P = 0 selects ON/OFF control with an adjustable switching differential
Timer0–9999s or minutes, set independently of the control loop
InputThermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50mV, 0–5V, 1–5V
Main outputRelay, logic-level SSR drive, 4–20mA control or 4–20mA retransmission, by order code
Alarm outputUp to 2 alarms; modes 0–6 and P1–P4 (11 modes)
CommunicationRS485 Modbus, optional
Supply voltage100–240VAC, 50Hz
Power consumption≤ 5VA
Accuracy±0.5 °C
Display resolution1°C or 0.1°C, selectable
Panel size48×48 / 48×96 / 72×72 / 96×96mm
Case depth83mm for all four sizes
Panel cutout46×46 / 45×91 / 67×67 / 91×91mm
Terminal torque0.74–0.90N·m
Warranty3 years

Product overview

Part no. SE-BT6

Also known as: BT6 temperature controller · BT6 PID controller · BT6 controlador de temperatura

BT6 Series is a panel-mount PID temperature controller for equipment builders who need a timed heating cycle and a retransmission signal in the same instrument. It accepts thermocouple, RTD and linear input, drives a relay or an external solid state relay, carries up to two alarm outputs, and offers an optional RS485 Modbus port — in four panel sizes sharing one 83 mm case depth.

Ordering code

BT6-AK124

The BT6-AK124 build: 48 × 48 mm (1/16 DIN) bezel, relay output and two alarms, high and low deviation.

Order codeBT6-AK124
Bezel (mm)48 × 48
Cut-out (mm)46 × 46
OutputRelay contact output, two alarms (high and low deviation)
Output terminalsper the case diagram
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: The main relay switches the load or a contactor coil; the two alarm contacts are for signalling, not for switching a heater

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
SeriesBT6The BT6 series of panel-mount PID temperature controllers
SizeA48 × 48 bezel on a 46 × 46 mm cut-out
InputKK thermocouple input. The manual's code table lists J, R, S, B, E, N, T, Pt100, Cu50 and the linear ranges as the other choices; the listing sells the K version
Output and alarms124Relay contact output, two alarms (high and low deviation)
Output terminals: per the case diagram·The main relay switches the load or a contactor coil; the two alarm contacts are for signalling, not for switching a heater

Key features

  • Built-in timer, 0–9999 s or minutes, set independently of the control loop
  • Universal input: thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50 mV, 0–5 V, 1–5 V
  • PID with auto-tuning; P = 0 switches the instrument to ON/OFF control with an adjustable differential
  • Main output selectable as relay, logic-level SSR drive, 4–20 mA control or 4–20 mA retransmission
  • Up to two alarm outputs with eleven selectable modes, including absolute, deviation, band and power-on hold
  • Optional RS485 Modbus for PLC, HMI and data logger integration
  • Four panel sizes — 48×48 / 48×96 / 72×72 / 96×96 mm — at a common 83 mm case depth
  • Manual output mode with direct percentage setting, useful when commissioning a heater
  • Non-volatile memory retains setpoints and parameters without a backup battery
  • Screw terminals tightened to 0.74–0.90 N·m; no special tooling required at the panel

Works with

The parts that go into the same panel and are usually ordered with it.

Compatible sensors & outputs

also supplied as dual-output temperature controller, relay plus SSR controller

Show supported sensors & probe links (8: K, E, J, N, T, R / S / B, Pt100, Cu50)

Output types and what goes with them

OutputRatingOrder with it
Electromagnetic relay3 A at 250 VAC, resistive—
SSR drive, 12 VDCDrives a solid state relay; the module carries the loadSSR-DA single phase 10–40 A
Current output, 4–20 mAInto a controller or recorder input—
SCR / triac, zero-crossPhase-angle or zero-cross firingBDTY SCR voltage regulator

Front panel

Two displays and four keys. The upper display carries the process value, the lower the set point and the parameter you are editing - which is why the same two digits can mean a temperature on one screen and a menu code on the next. Everything else on the front is a lamp or a key.

BT6 front panel overview

BT6 front panel overview
Display 1 shows the process value; display 2 shows the set value and the parameter settings.

Indicator lamps

AT
Auto-tuning is running.
OUT1
Main control output is on.
OUT2
Second output is on.
AL1
Alarm 1 is active.
AL2
Alarm 2 is active.
A/M
Auto or manual mode.
10–100%
Output percentage

Keys

SET
Main and sub-menu entry; confirm a parameter edit.
▼
Decrease a value; parameter toggle; the other way into auto-tuning.
▲
Increase a value; parameter toggle; manual mode entry.
◄
Shift the digit cursor, for settings with more than one digit to edit.

Panel sizes and cutouts

  • BT6-A48 × 48 mm (1/16 DIN) front, 46 × 46 mm cut-out
  • BT6-B48 × 96 mm (1/8 DIN) front, 45 × 91 mm cut-out
  • BT6-D72 × 72 mm front, 67 × 67 mm cut-out
  • BT6-E96 × 96 mm (1/4 DIN) front, 91 × 91 mm cut-out
BT6-A 48 × 48 mm mm panel
BT6-A — 48 × 48 mm (1/16 DIN), 46 × 46 mm
BT6-B 48 × 96 mm mm panel
BT6-B — 48 × 96 mm (1/8 DIN), 45 × 91 mm
BT6-D 72 × 72 mm mm panel
BT6-D — 72 × 72 mm, 67 × 67 mm
BT6-E 96 × 96 mm mm panel
BT6-E — 96 × 96 mm (1/4 DIN), 91 × 91 mm

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

Wiring

Both dual-output bodies on one sheet: a contactor arrangement, a solid state relay arrangement, a heater, an alarm beacon and both sensor types, for the AK and the BK block. The two blocks number the same functions differently, so read the panel that matches the code on your instrument.

BT6AK1220 / BT6BK1220 · dual-output wiring

BT6AK1220 / BT6BK1220 · dual-output wiring

A three-wire RTD takes its red lead to terminal 10 on the AK body (5 on the BK) and the other two wires to the pair beside it; the thermocouple sits on 11 and 12 on the AK, and on the pair marked for it on the BK. The jumpers differ by version — 2–5 for the main output, 2–8 for the alarm — and the SSR control pair is 3 and 4.

Download the sheet (PDF)

Documents for this family

All documents

Where it is used

  • Injection moulding, extrusion and blow moulding barrel heating zones
  • Packaging, heat sealing and shrink wrapping machinery
  • Industrial ovens, furnaces and drying equipment

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the BT6 need?

48×48 / 48×96 / 72×72 / 96×96mm. The cut-out is 46×46 / 45×91 / 67×67 / 91×91mm

Which sensors can the BT6 read?

Thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50mV, 0–5V, 1–5V

What output options does the BT6 have?

Relay, logic-level SSR drive, 4–20mA control or 4–20mA retransmission, by order code

What supply voltage does the BT6 need?

100–240VAC, 50Hz

How accurate is the BT6?

±0.5 °C, at 1°C or 0.1°C, selectable resolution

Does the BT6 have alarm outputs?

Up to 2 alarms; modes 0–6 and P1–P4 (11 modes)

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.