Temperature Controllers
BT6 Series Intelligent PID Temperature Controller with Timer and RS485 Modbus
BT6 panel-mount PID temperature controller with a built-in 0–9999 timer and universal TC, RTD or linear input, 4–20 mA retransmission.

- Panel size
- 48×48 / 48×96 / 72×72 / 96×96mm
- Panel cutout
- 46×46 / 45×91 / 67×67 / 91×91mm
- Supply voltage
- 100–240VAC, 50Hz
- Input
- Thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50mV, 0–5V, 1–5V
Ordering & Selection Guide
The same code, broken into its positions: what each character fixes, and which values this family actually uses.
| Position | Value | What it selects | Sold as |
|---|---|---|---|
| Series | BT6 | The BT6 series of panel-mount PID temperature controllers | BT6-AK1220 →BT6-AK320 →BT6-AK1620 →BT6-AK120 RS485 →+22 more, see the table above |
| Size | A | 48 × 48 bezel on a 46 × 46 mm cut-out | BT6-AK1220 →BT6-AK320 →BT6-AK1620 →BT6-AK120 RS485 →+4 more, see the table above |
| B | 48 × 96 bezel on a 45 × 91 mm cut-out | BT6-BK1220 →BT6-BK320 →BT6-BK1620 →BT6-BK1220 RS485 →+2 more, see the table above | |
| D | 72 × 72 bezel on a 67 × 67 mm cut-out | BT6-DK1220 →BT6-DK320 →BT6-DK1620 →BT6-DK1220 RS485 →+2 more, see the table above | |
| E | 96 × 96 bezel on a 91 × 91 mm cut-out | BT6-EK1220 →BT6-EK320 →BT6-EK1620 →BT6-EK1220 RS485 →+2 more, see the table above | |
| Input | K | K thermocouple input. The manual's code table lists J, R, S, B, E, N, T, Pt100, Cu50 and the linear ranges as the other choices; the listing sells the K version | BT6-AK1220 →BT6-AK320 →BT6-AK1620 →BT6-AK120 RS485 →+22 more, see the table above |
| Output and alarms | 120 | Relay contact output with the RS485 board, one high-deviation alarmOutput 1 (relay) and alarm pair 20: one high-deviation alarm on AL1, AL2 unused | BT6-AK120 RS485 → |
| 124 | Relay contact output, two alarms (high and low deviation)Output 1 (relay) and alarm pair 24: high and low deviation, the two alarms the listing labels as such | BT6-AK124 → | |
| 220 | Solid-state (SSR) drive with the RS485 board, one high-deviation alarmOutput 2 (solid state) and alarm pair 20: one high-deviation alarm on AL1 | BT6-AK220 RS485 → | |
| 224 | Solid-state (SSR) drive, two alarms (high and low deviation)Output 2 (solid state) and alarm pair 24: high and low deviation | BT6-AK224 → | |
| 320 | PID 4–20 mA control output, one high-deviation alarmOutput 3 (PID 4–20 mA) and alarm pair 20: one high-deviation alarm. The listing prints the RS485 rows of this block without the input letter (BT6-A 320 RS485); it is the same instrument | BT6-AK320 →BT6-AK320 RS485 →BT6-BK320 →BT6-BK320 RS485 →+4 more, see the table above | |
| 1220 | Relay contact plus solid-state (SSR) drive, one high-deviation alarmOutputs 1 and 2 (relay plus solid state) and alarm pair 20: one high-deviation alarm | BT6-AK1220 →BT6-BK1220 →BT6-BK1220 RS485 →BT6-DK1220 →+3 more, see the table above | |
| 1224 | Relay contact plus solid-state (SSR) drive, two alarms (high and low deviation)Outputs 1 and 2 (relay plus solid state) and alarm pair 24: high and low deviation | BT6-BK1224 →BT6-DK1224 →BT6-EK1224 → | |
| 1620 | Relay contact plus 4–20 mA retransmission output, one high-deviation alarmOutputs 1 and 6 (relay plus 4–20 mA retransmission) and alarm pair 20: one high-deviation alarm | BT6-AK1620 →BT6-BK1620 →BT6-DK1620 →BT6-EK1620 → |
| 1 | Relay output, built in |
| 2 | Logic-level output driving an external solid state relay |
| 3 | PID 4–20 mA current output (custom build) |
| 4 | SCR phase-angle or zero-crossing triggering (custom build) |
| 5 | 30 A relay (custom build) |
| 6 | 4–20 mA retransmission of the measured value (custom build) |
Digits 1 and 2 are the two stages the factory builds as standard, which is why the listing sells almost nothing else. A two-digit block is two outputs fitted together: 12 is the relay and the logic-level output on one instrument.
| 0 | No alarm; the AL1 and AL2 menus stay hidden |
| 1 | High absolute alarm |
| 2 | High deviation alarm, the AL1 default |
| 3 | Low absolute alarm, the AL2 default |
| 4 | Low deviation alarm |
| 5 | Outside-band alarm |
| 6 | Inside-band alarm |
| P1–P4 | The four digits above with power-on hold: the alarm stays inhibited until the instrument has been powered for the configured time |
The supplier's 型号定义 sheet prints digit 2 as 下限偏差报警 and then prints 下限偏差报警 again for digit 4. The manual's A4 table and its alarm-mode list both put high deviation at 2 and low deviation at 4, and the rows the listing marks as two alarms carry 24 — which only reads as high plus low that way. This page follows the manual.
Technical specifications
| Series | BT6 Series (panel-mount PID temperature controller with timer) |
|---|---|
| Models | BT6-A / BT6-B / BT6-D / BT6-E |
| Display | Two-row LED display for PV and SV |
| Control method | PID with auto-tuning; P = 0 selects ON/OFF control with an adjustable switching differential |
| Timer | 0–9999s or minutes, set independently of the control loop |
| Input | Thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50mV, 0–5V, 1–5V |
| Main output | Relay, logic-level SSR drive, 4–20mA control or 4–20mA retransmission, by order code |
| Alarm output | Up to 2 alarms; modes 0–6 and P1–P4 (11 modes) |
| Communication | RS485 Modbus, optional |
| Supply voltage | 100–240VAC, 50Hz |
| Power consumption | ≤ 5VA |
| Accuracy | ±0.5 °C |
| Display resolution | 1°C or 0.1°C, selectable |
| Panel size | 48×48 / 48×96 / 72×72 / 96×96mm |
| Case depth | 83mm for all four sizes |
| Panel cutout | 46×46 / 45×91 / 67×67 / 91×91mm |
| Terminal torque | 0.74–0.90N·m |
| Warranty | 3 years |
Product overview
Part no. SE-BT6
Also known as: BT6 temperature controller · BT6 PID controller · BT6 controlador de temperatura
BT6 Series is a panel-mount PID temperature controller for equipment builders who need a timed heating cycle and a retransmission signal in the same instrument. It accepts thermocouple, RTD and linear input, drives a relay or an external solid state relay, carries up to two alarm outputs, and offers an optional RS485 Modbus port — in four panel sizes sharing one 83 mm case depth.
Key features
- Built-in timer, 0–9999 s or minutes, set independently of the control loop
- Universal input: thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50 mV, 0–5 V, 1–5 V
- PID with auto-tuning; P = 0 switches the instrument to ON/OFF control with an adjustable differential
- Main output selectable as relay, logic-level SSR drive, 4–20 mA control or 4–20 mA retransmission
- Up to two alarm outputs with eleven selectable modes, including absolute, deviation, band and power-on hold
- Optional RS485 Modbus for PLC, HMI and data logger integration
- Four panel sizes — 48×48 / 48×96 / 72×72 / 96×96 mm — at a common 83 mm case depth
- Manual output mode with direct percentage setting, useful when commissioning a heater
- Non-volatile memory retains setpoints and parameters without a backup battery
- Screw terminals tightened to 0.74–0.90 N·m; no special tooling required at the panel
Works with
The parts that go into the same panel and are usually ordered with it.
Compatible sensors & outputs
also supplied as dual-output temperature controller, relay plus SSR controller
Show supported sensors & probe links (8: K, E, J, N, T, R / S / B, Pt100, Cu50)
| Sensor | Range | Available as |
|---|---|---|
| K | 0–400 / 0–1200 / 0–1372 °C | K / E probe thermocoupleStainless steel probeSpring-loaded M12 probeRing-terminal thermocoupleThreaded shielded-lead probe |
| E | 0–800 / 0–1000 °C | K / E probe thermocoupleStainless steel probeM6 / M8 screw-in probe |
| J | 0–600 / 0–1200 °C | Simple 4 × 40 thermocouple |
| N | 0–1300 °C | Threaded shielded-lead probe |
| T | −200–400 °C | Stainless steel probe |
| R / S / B | 0–1769 °C | Threaded shielded-lead probe |
| Pt100 | −199.9–649.0 °C | Pt100 / Cu50 sheathed RTDM6 / M8 screw-in probe |
| Cu50 | −50.0–150.0 °C | Pt100 / Cu50 sheathed RTD |
Output types and what goes with them
| Output | Rating | Order with it |
|---|---|---|
| Electromagnetic relay | 3 A at 250 VAC, resistive | — |
| SSR drive, 12 VDC | Drives a solid state relay; the module carries the load | SSR-DA single phase 10–40 A |
| Current output, 4–20 mA | Into a controller or recorder input | — |
| SCR / triac, zero-cross | Phase-angle or zero-cross firing | BDTY SCR voltage regulator |
Front panel
Two displays and four keys. The upper display carries the process value, the lower the set point and the parameter you are editing - which is why the same two digits can mean a temperature on one screen and a menu code on the next. Everything else on the front is a lamp or a key.
BT6 front panel overview
Indicator lamps
- AT
- Auto-tuning is running.
- OUT1
- Main control output is on.
- OUT2
- Second output is on.
- AL1
- Alarm 1 is active.
- AL2
- Alarm 2 is active.
- A/M
- Auto or manual mode.
- 10–100%
- Output percentage
Keys
- SET
- Main and sub-menu entry; confirm a parameter edit.
- ▼
- Decrease a value; parameter toggle; the other way into auto-tuning.
- ▲
- Increase a value; parameter toggle; manual mode entry.
- ◄
- Shift the digit cursor, for settings with more than one digit to edit.
Panel sizes and cutouts
- BT6-A48 × 48 mm (1/16 DIN) front, 46 × 46 mm cut-out
- BT6-B48 × 96 mm (1/8 DIN) front, 45 × 91 mm cut-out
- BT6-D72 × 72 mm front, 67 × 67 mm cut-out
- BT6-E96 × 96 mm (1/4 DIN) front, 91 × 91 mm cut-out




One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
BT6-AK
48 × 48mm (1/16 DIN) · cut-out 46 × 46mm
BT6-BK
48 × 96mm (1/8 DIN) · cut-out 45 × 91mm
BT6-DK
72 × 72mm · cut-out 67 × 67mm
BT6-EK
96 × 96mm (1/4 DIN) · cut-out 91 × 91mm
Wiring
Both dual-output bodies on one sheet: a contactor arrangement, a solid state relay arrangement, a heater, an alarm beacon and both sensor types, for the AK and the BK block. The two blocks number the same functions differently, so read the panel that matches the code on your instrument.
BT6AK1220 / BT6BK1220 · dual-output wiring
A three-wire RTD takes its red lead to terminal 10 on the AK body (5 on the BK) and the other two wires to the pair beside it; the thermocouple sits on 11 and 12 on the AK, and on the pair marked for it on the BK. The jumpers differ by version — 2–5 for the main output, 2–8 for the alarm — and the SSR control pair is 3 and 4.
Documents for this family
- BT6 instruction manual (EN)2.5 MB · 2026-11-08
- BT6 dual-output wiring168 KB · 2026-11-19
Where it is used
- Injection moulding, extrusion and blow moulding barrel heating zones
- Packaging, heat sealing and shrink wrapping machinery
- Industrial ovens, furnaces and drying equipment
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Frequently asked questions
What panel size and cut-out does the BT6 need?
48×48 / 48×96 / 72×72 / 96×96mm. The cut-out is 46×46 / 45×91 / 67×67 / 91×91mm
Which sensors can the BT6 read?
Thermocouple K, J, R, S, B, E, N, T; RTD PT100 and CU50; linear 0–50mV, 0–5V, 1–5V
What output options does the BT6 have?
Relay, logic-level SSR drive, 4–20mA control or 4–20mA retransmission, by order code
What supply voltage does the BT6 need?
100–240VAC, 50Hz
How accurate is the BT6?
±0.5 °C, at 1°C or 0.1°C, selectable resolution
Does the BT6 have alarm outputs?
Up to 2 alarms; modes 0–6 and P1–P4 (11 modes)
Related guides
TC4 Series PID Temperature Controller: Model Code Breakdown, Outputs and RS485 Setup
How to read a TC4 model code, which sensor inputs and control outputs are available across TC4S/H/W/M/L, what the RS485 Modbus option adds, and the checks to run at commissioning.
Read guide Product Updates · 2025-04-11TCN4 Series PID Temperature Controller: Model Codes, Inputs, Outputs and Commissioning
A working reference for engineers specifying or commissioning a TCN4 series digital PID temperature controller: how the four panel sizes differ, which sensor inputs are accepted,…
Read guide Technical Guides · 2026-11-26TEL96-9001 or TEL96-2001: Choosing the Right Oven Temperature Controller
The TEL96 series is a 96 x 96 mm on/off oven temperature controller built around a K-type thermocouple input and a 10 A relay contact. It is made in two versions, the TEL96-9001…
Read guideRelated models
All Temperature Controllers
REX-C100/C400/C700/C900 Digital PID Temperature Controller
SE-C100
REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and…
View details
C700 Digital Temperature Controller, 72 × 72mm Panel Frame | Strong Electric
SE-C700
72×72mm · 68×68mm · 24mm overall, 20mm of it behind the panel
View details
TC4H Digital PID Temperature Controller
SE-TC4H
48×96mm (1/8 DIN) · 45×92mm · 75mm total, 71mm behind the panel
View details
TC4L Digital PID Temperature Controller
SE-TC4L
96×96mm (1/4 DIN) · 92×92mm · 75mm total, 71mm behind the panel
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.