Temperature Controllers

REX-C100FK02-M*AN — REX-C100 with built-in electromechanical relay

The version to order when the controller only has to close a contactor coil, or a small heater under 3A.

REX-C100/C400/C700/C900 temperature controller, dual 4-digit LED display, red PV row above green SV row
REX-C100/C400/C700/C900: Dual 4-digit LED display, red PV row above green SV row; REX-C100 48×48; C400 48×96; C410 96×48; C700 72×72; C900 96×96mm; M relay 250VAC 3A.
Output
Built-in electromechanical relay, 250VAC 3A, dry contact
Bezel
48 × 48
Panel cut-out
45 × 45
Looking for a replacement? Compatibility depends on the exact model. Send your current part code or a nameplate photo and we’ll compare the panel cut-out, wiring, sensor input and output before you order. Request a cross-reference match

Technical specifications

SeriesREX-C Series classic universal-input PID temperature controller
ModelsREX-C100 / C400 / C410 / C700 / C900
DisplayDual 4-digit LED display, red PV row above green SV row
Control methodON/OFF, position PID, continuous PID; reverse-acting (F) or direct-acting (D)
InputUniversal input with K type fitted as standard (sensor not included). Thermocouple; Pt100; Cu50; 0–5V; 1–5V; mA signals. Input families: K (K01–K07, K13–K14), J (J01–J06), R/S/B, E/N/T, Pt100 (D01–D10), Cu50 (P01–P10), 0–5V 401, 1–5V 601, 0–20mA 701, 4–20mA 801 (external 250Ω resistor where specified)
Control outputM relay 250VAC 3A; V SSR drive 0–12VDC; 8 current output 0–10mA or 4–20mA; T hybrid SCR trigger; analog 0–5V / 1–5V
Alarm outputUp to 2 alarm outputs; N none or A–L selectable deviation / band / absolute modes
Supply voltage220VAC, 50/60Hz; 10VA at 220V
Accuracy±0.5%FS or ±1.0%FS
Temperature range0–400°C default; 0–1370°C maximum, set by the input code
Sampling period0.5s
PID setting rangeP 0 to full range; I / D 0–3600s; control period 1–100s
Alarm rangefreely settable across the full range
Operating environment0–50℃; 30–85% RH, no corrosive gas
Panel sizeREX-C100 48×48; C400 48×96; C410 96×48; C700 72×72; C900 96×96mm
Panel cutoutREX-C100 45×45; C400 45×92; C410 92×45; C700 68×68; C900 92×92mm
Dimensions (depth)REX-C100 98.5mm; C400 and C900 100mm behind the panel; 110–112mm overall including the terminal shroud
WeightREX-C100 0.193kg; C400 0.294kg; C900 0.371kg
MountingPanel mount, snap-in retaining clip

Product overview

Part no. SE-C100industry model C100

Also known as: RKC REX-C100 · REX-C100 temperature controller · REX-C100 PID controller · REX-C100 controlador de temperatura

REX Series Digital PID Temperature Controller is a classic and reliable industrial temperature control instrument designed for heating, cooling, and automatic temperature regulation applications. It supports PID control, relay or SSR output, multiple sensor inputs such as PT100, Cu50, K, S, E and J, and dual LED display for PV and SV values.

Ordering code

REX-C100FK02-M*AN

The version to order when the controller only has to close a contactor coil, or a small heater under 3A.

Order codeREX-C100FK02-M*AN
Bezel (mm)48 × 48
Cut-out (mm)45 × 45
OutputBuilt-in electromechanical relay, 250VAC 3A, dry contact
Output terminals3 – 4
InputUniversal, K thermocouple fitted
AlarmTwo relays, A to L selectable
Supply220VAC 50/60Hz, 10VA

What it can switch: Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR

Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.

Reading this order code

How the code on this page is put together, part by part — the same breakdown the series page gives, filled in for this version.

PositionReadsMeaning
1REX-C10048 × 48 mm (1/16 DIN) bezel on a 45 × 45mm panel cut-out
2FControl mode: reverse acting, the usual choice for heating
3K02Input: K thermocouple over 0–400 °C; other letters select J, E, N, T, R, S, B, Pt100 or Cu50
4C100FK02Built-in electromechanical relay, 250VAC 3A, dry contact
5*ANAlarm pair: A is an upper deviation alarm, N leaves the second alarm off; N-24VDC or N-24VAC would set a low-voltage supply instead
Output terminals: 3 – 4·Switches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR

How this build compares with the others

Same case, same cut-out, same supply. The differences are the ones below.

Order codeOutput stageWhat it can switchTerminals
REX-C100FK02-M*ANthis pageBuilt-in electromechanical relay, 250VAC 3A, dry contactSwitches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSR3 – 4
REX-C100FK02-M*ANBuilt-in electromechanical relay, 250VAC 3A, dry contactSwitches a contactor coil or a heater up to 3A directly; anything larger needs a contactor or an SSRon the case diagram
REX-C100FK02-V*ANVoltage pulse output, 0–12VDC, for an external solid state relayDrives the input of an SSR and nothing else; the load current is the SSR's rating, not the controller'son the case diagram
REX-C100FK02-8*ANAnalogue current output, 4–20mA (0–10mA on request)A signal, not a switch: it drives an SCR power regulator, a recorder or a PLC analogue inputon the case diagram

Key features

  • Digital dual LED display for PV and SV values
  • PID control for accurate and stable temperature regulation
  • 24-hour continuous temperature control
  • Relay output or SSR output optional
  • Supports multiple input types: PT100, Cu50, K, S, E, J
  • Multiple models available: REX-C100, C400, C410, C700, C900
  • Over-temperature protection and alarm function
  • Simple panel operation and easy parameter setting
  • Suitable for heating, cooling, and industrial automation systems
  • Customization available for different application requirements

Downloads

Download manual (PDF)12 pages · 411 KB

Works with

The parts that go into the same panel and are usually ordered with it.

Ordering & Selection Guide

REX plus six positions: panel size (overall depth ~112mm, ~100mm behind panel), control action, input & range, main output, and two alarm outputs.

REXC700①F②K02③−M④A⑤B⑥

① · Panel size (mm)

C100
48×48, cut-out 45×45
C400
48×96, cut-out 45×92
C410
96×48, cut-out 92×45
C700
72×72, cut-out 68×68
C900
96×96, cut-out 92×92

② · Control action

F
PID, reverse action — heating
D
PID, direct action — cooling

③ · Common input & range

K02
K thermocouple, 0–400 °C
E02
E thermocouple, 0–1000 °C
D10
Pt100 RTD, 0.0–500 °C
P02
Cu50 RTD, 0.0–150.0 °C

④ · Main output

M
Relay contact (RELAY)
V
Voltage pulse (SSR drive)
8
Current output 4–20mA
⑤⑥ First & second alarm codes (N, A–L — 12 options)
NNo alarm
ADeviation high (upper)
BDeviation low (lower)
CDeviation high and low
DInside the band
EDeviation high, hold action
FDeviation low, hold action
GDeviation high and low, hold action
HProcess high (absolute)
JProcess low (absolute)
KProcess high, hold action
LProcess low, hold action
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
InputCode and measuring range
KThermocouple
K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C
JThermocouple
J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C
RThermocouple (accuracy not guaranteed over 0–399 °C)
R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C
SThermocouple (accuracy not guaranteed over 0–399 °C)
S01 0–1600 °CS02 0–1769 °C
BThermocouple (accuracy not guaranteed over 0–399 °C)
B01 400–1800 °CB02 0–1769 °C
EThermocouple
E01 0–800 °CE02 0–1000 °C
NThermocouple
N01 1–1300 °CN02 0–1300 °C
TThermocouple (accuracy held from −199 to 100 °C)
T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C
PT100RTD
D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C
Cu50RTD
P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C
0–5VDCStandard signal
401 0.0–100.0
1–5VDCStandard signal
601 0.0–100.0
0–20mAStandard signal, 250 Ω resistor across the terminals
701 0.0–100.0
4–20mAStandard signal, 250 Ω resistor across the terminals
801 0.0–100.0

Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.

Worked example

REXC700FK02-MAB

72×72 on a 68×68 cut-out, reverse action for heating, K thermocouple to 400 °C, relay output, a deviation-high alarm on the first relay and a deviation-low alarm on the second.

Compatible sensors & outputs

also supplied as PID temperature controller, intelligent temperature controller, RKC REX-C equivalent

Show supported sensors & probe links (8: K, E, J, N, T, R / S / B, Pt100, Cu50)

Output types and what goes with them

OutputRatingOrder with it
Electromagnetic relay3 A at 250 VAC, resistive—
SSR drive, 12 VDCDrives a solid state relay; the module carries the loadSSR-DA single phase 10–40 A
Current output, 4–20 mAInto a controller or recorder input—
SCR / triac, zero-crossPhase-angle or zero-cross firingBDTY SCR voltage regulator

One page per order code

Every code this family ships, with the bezel, the output stage and the terminals that output uses.

REX-C100

48 × 48mm (1/16 DIN) · cut-out 45 × 45mm

REX-C400

48 × 96mm (1/8 DIN) · cut-out 45 × 92mm

REX-C700

72 × 72mm · cut-out 68 × 68mm

REX-C900

96 × 96mm (1/4 DIN) · cut-out 92 × 92mm

Input codes and measuring ranges

Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.

③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
InputCode and measuring range
KThermocouple
K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C
JThermocouple
J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C
RThermocouple (accuracy not guaranteed over 0–399 °C)
R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C
SThermocouple (accuracy not guaranteed over 0–399 °C)
S01 0–1600 °CS02 0–1769 °C
BThermocouple (accuracy not guaranteed over 0–399 °C)
B01 400–1800 °CB02 0–1769 °C
EThermocouple
E01 0–800 °CE02 0–1000 °C
NThermocouple
N01 1–1300 °CN02 0–1300 °C
TThermocouple (accuracy held from −199 to 100 °C)
T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C
PT100RTD
D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C
Cu50RTD
P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C
0–5VDCStandard signal
401 0.0–100.0
1–5VDCStandard signal
601 0.0–100.0
0–20mAStandard signal, 250 Ω resistor across the terminals
701 0.0–100.0
4–20mAStandard signal, 250 Ω resistor across the terminals
801 0.0–100.0

Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.

Panel and keys

Two four-digit rows and five lamps in the order REX prints them — OUT1, OUT2, AT, ALM1, ALM2. The auto-tuning lamp sits third here, not first as on the CH series. Four keys: set, shift, decrease, increase.

Panel marking
PV
Process value (PV)
SV
Set value (SV)
OUT1 / OUT2
Control output indicators (OUT1 / OUT2)
AT
Auto-tuning indicator (AT)
ALM1 / ALM2
Alarm output indicators (ALM1 / ALM2)
SET
Set key
◁
Shift key
∨
Decrease key
∧
Increase key

Panel dimensions

All five sizes share one depth: 112mm to the back of the case, of which 100mm sits behind the panel line. Only the front changes, so a panel designed for one size needs the same clearance for any other.

ModelPanel (mm)Cut-out (mm)Total depthBody depth
REX-C10048 × 4845 × 45112mm100mm
REX-C40048 × 9645 × 92112mm100mm
REX-C41096 × 4892 × 45112mm100mm
REX-C70072 × 7268 × 68112mm100mm
REX-C90096 × 9692 × 92112mm100mm

REX-C400 / C410 / C900 wiring

The sixteen-terminal bodies, in six panels: contactor, solid state relay and alarm light, with the relay and SSR terminal references at the foot of the sheet. This block is numbered 1–8 down the left and 9–16 down the right, and the supply lands on 2 and 3 — different from the small cases drawn above, so read the number on the instrument rather than the one you remember.

REX-C400 / C410 / C900 · wiring and terminal references

REX-C400 / C410 / C900 · wiring and terminal references

Contactor version: 3–6 jumper, and the relay closes 4 to 3 so the coil sits across A1 and A2. SSR version: no jumper, the 12 VDC drive leaves on 4 (+) and 5 (−). Sensors on every version: thermocouple blue to 15 (−) and red to 16 (+); three-wire RTD with A on 14 and B on 15 and 16.

Download the sheet (PDF)

Documents for this family

All documents

Supply & OEM

Available with your logoMOQ 500 pcs·10 days·OEM & private label →
Stock / sample dispatch
Typically 3–5 working days for available stock models after stock and order confirmation
Warranty
3 years
OEM
Selected models; confirm by quotation
Shipping
Worldwide export

Frequently asked questions

What panel size and cut-out does the REX-C100/C400/C700/C900 need?

REX-C100 48×48; C400 48×96; C410 96×48; C700 72×72; C900 96×96mm. The cut-out is REX-C100 45×45; C400 45×92; C410 92×45; C700 68×68; C900 92×92mm

Which sensors can the REX-C100/C400/C700/C900 read?

Universal input with K type fitted as standard (sensor not included). Thermocouple; Pt100; Cu50; 0–5V; 1–5V; mA signals. Input families: K (K01–K07, K13–K14), J (J01–J06), R/S/B, E/N/T, Pt100 (D01–D10), Cu50 (P01–P10), 0–5V 401, 1–5V 601, 0–20mA 701, 4–20mA 801 (external 250Ω resistor where specified)

What output options does the REX-C100/C400/C700/C900 have?

M relay 250VAC 3A; V SSR drive 0–12VDC; 8 current output 0–10mA or 4–20mA; T hybrid SCR trigger; analog 0–5V / 1–5V

What supply voltage does the REX-C100/C400/C700/C900 need?

220VAC, 50/60Hz; 10VA at 220V

How accurate is the REX-C100/C400/C700/C900?

±0.5%FS or ±1.0%FS

Does the REX-C100/C400/C700/C900 have alarm outputs?

Up to 2 alarm outputs; N none or A–L selectable deviation / band / absolute modes

Related guides

Need help selecting the right model?

Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.