Technical specifications
| Series | XMT-8000 series panel PID temperature controller |
|---|---|
| Models | XMTG-8411 / XMTE-8411 / XMTD-8411 / XMTA-8411 |
| Panel sizes | 48×48×65, 48×96×65, 72×72×65 and 96×96×65 mm |
| Panel cutouts | 45×45, 45×92, 68×68 and 92×92 mm |
| Supply | 100–240 VAC, 50/60 Hz |
| Accuracy | ±0.5% or ±1.0% FS |
| Control | PID with autotuning, and on/off with an adjustable differential |
| Input | selectable input for K, E, J, S, R, B, N or T thermocouples, or Pt100 or Cu50 RTDs |
| Output | relay contact 3 A at 250 V AC (resistive load), SSR drive, combined relay and SSR, or 4–20 mA |
| Alarm | full-range setting, up to two relays |
| Terminals | 24 and 23 supply; 22 output common with 21 and 20 as the SSR drive pair or the relay NO/NC; 19 and 18 alarm 1 NO/NC with 17 alarm 1 common and 16 alarm 2; 15, 14 and 13 the sensor — A/B/B for a 3-wire RTD, plus and minus for a thermocouple |
| Operating environment | 0–50 °C, 30–85% RH, no corrosive gas |
Product overview
Part no. SE-XMT-8411industry model XMT-8411
Also known as: XMT-8411 temperature controller · XMT-8411 PID controller
The codes on this page carry an XMTG, XMTE, XMTD or XMTA front-panel prefix — XMTD-8411 included. XMTD-2001 and XMTD-2201 are a separate thumbwheel controller with a relay output, covered on their own page. See the XMTD-2001 / 2201 instead
The 8000 series is the smaller series' body with a wider instrument behind the bezel: one input that takes the whole thermocouple and RTD range, a second alarm relay, a current output, and half a percent accuracy on request. Four bezels, the same 65 mm behind the panel.
Ordering code
XMTE-8412, Pt100 input, dual output
The XMTE-8412 build with pt100 input, dual output.
| Order code | XMTE-8412, Pt100 input, dual output |
|---|---|
| Bezel (mm) | 96 × 96 |
| Cut-out (mm) | 92 × 92 |
| Output | Pt100 input, dual output |
| Output terminals | per the case diagram |
| Input | Universal, K thermocouple fitted |
| Alarm | Two relays, A to L selectable |
| Supply | 220VAC 50/60Hz, 10VA |
What it can switch: Selected on the order line; the terminals follow the case diagram for that version
Terminals follow the diagram printed on the side of the instrument; if the unit you receive carries a different numbering, that diagram takes precedence.
Other output stages of the same bezel
Key features
- XMTG-8411 / XMTE-8411 / XMTD-8411 / XMTA-8411
- Panel cutouts 45×45, 45×92, 68×68 and 92×92 mm
- selectable input for K, E, J, S, R, B, N or T thermocouples, or Pt100 or Cu50 RTDs
- relay contact 3 A at 250 V AC (resistive load), SSR drive, combined relay and SSR, or 4–20 mA
- ±0.5% or ±1.0% FS accuracy, 100–240 VAC, 50/60 Hz supply
Works with
The parts that go into the same panel and are usually ordered with it.
Four bezels, one body
Same shell and the same 65 mm behind the panel as the 6000 series; the difference is inside, where the input accepts ten sensor types instead of one family.
| Model | Panel W×H×D (mm) | Cutout (mm) |
|---|---|---|
| XMTA | 96 × 96 × 65 mm (1/4 DIN front) | 92 × 92 |
| XMTD | 72 × 72 × 65 mm | 68 × 68 |
| XMTE | 48 × 96 × 65 mm (1/8 DIN front) | 45 × 92 |
| XMTG | 48 × 48 × 65 mm (1/16 DIN front) | 45 × 45 |
Ordering & Selection Guide
The 8000 series keeps the 6000 layout and widens two positions: the output gains a current version and, on the larger bezels, a combined relay-plus-SSR version; the alarm position carries a second relay.
① · Bezel letter
| G | 48 × 48 × 65, cut-out 45 × 45 |
| E | 48 × 96 × 65, cut-out 45 × 92 |
| D | 72 × 72 × 65, cut-out 68 × 68 |
| A | 96 × 96 × 65, cut-out 92 × 92 |
② · Main output
| 4 | Relay contact output |
| 5 | SSR drive output |
| 9 | Current output 4–20 mA |
③ · Alarm output
| 1 | One alarm relay |
| 3 | Two alarm relays |
④ · Input type
| 1 | Thermocouple — K, E, J, S, R, B, N or T, set on the unit |
| 2 | RTD — Pt100 or Cu50 |
Worked example
XMTG-8411
A controller with a 48 × 48 mm front, 8000 series, relay output, one alarm, thermocouple input. The same body with an SSR drive reads XMTG-8511, and with a Pt100 input XMTG-8412.
The codes that ship
Rather than a theoretical grid, these are the combinations the factory lists. Sizes below are the G; the same suffix works on E, D and A.
| Code | Version |
|---|---|
| XMTG-8411 | Relay output, one alarm, thermocouple |
| XMTG-8412 | Relay output, one alarm, Pt100 |
| XMTG-8511 | SSR drive, one alarm, thermocouple |
| XMTG-8512 | SSR drive, one alarm, Pt100 |
| XMTG-8431 | Relay output with two alarms |
| XMTG-8911 | Current output 4–20 mA |
| XMTE/D/A-8411 | The same versions on the larger bezels, where 8411 is a combined relay and SSR output |
In the range
The 8411 is the step above the 6311: the same panel, a tighter display accuracy on request, a ten-type input, a second alarm and a current output. Where a machine only needs a K thermocouple and a relay, the 6311 does the job for less.
| XMT 8411 | XMT 6311 | |
|---|---|---|
| Input | ten types, selectable | thermocouple or RTD |
| Accuracy | ±0.5% or ±1.0% FS | ±1.0% FS |
| Alarms | up to two | one as listed |
| Output | relay, SSR, combined, or 4–20 mA | relay or SSR |
Compatible sensors & outputs
also supplied as XMT-8000 series controller, dual-output temperature controller
Show supported sensors & probe links (8: K, E, J, N, T, R / S / B, Pt100, Cu50)
| Sensor | Range | Available as |
|---|---|---|
| K | 0–400 / 0–1200 / 0–1372 °C | K / E probe thermocoupleStainless steel probeSpring-loaded M12 probeRing-terminal thermocoupleThreaded shielded-lead probe |
| E | 0–800 / 0–1000 °C | K / E probe thermocoupleStainless steel probeM6 / M8 screw-in probe |
| J | 0–600 / 0–1200 °C | Simple 4 × 40 thermocouple |
| N | 0–1300 °C | Threaded shielded-lead probe |
| T | −200–400 °C | Stainless steel probe |
| R / S / B | 0–1769 °C | Threaded shielded-lead probe |
| Pt100 | −199.9–649.0 °C | Pt100 / Cu50 sheathed RTDM6 / M8 screw-in probe |
| Cu50 | −50.0–150.0 °C | Pt100 / Cu50 sheathed RTD |
Output types and what goes with them
| Output | Rating | Order with it |
|---|---|---|
| Electromagnetic relay | 3 A at 250 VAC, resistive | — |
| SSR drive, 12 VDC | Drives a solid state relay; the module carries the load | SSR-DA single phase 10–40 A |
| Current output, 4–20 mA | Into a controller or recorder input | — |
| SCR / triac, zero-cross | Phase-angle or zero-cross firing | BDTY SCR voltage regulator |
Input codes and measuring ranges
Most orders use K02 (K 0–400 °C), K06 (K 0–1200 °C), D10 (Pt100 0–500 °C) or 801 (4–20 mA). Expand the full table below for all 14 sensor types and range codes.
③ Full input code table (14 sensor types: K, J, R, S, B, E, N, T, Pt100, Cu50 & 4–20 mA)
| Input | Code and measuring range |
|---|---|
| KThermocouple | K01 0–200 °CK02 0–400 °CK03 0–600 °CK04 0–800 °CK05 0–1000 °CK06 0–1200 °CK07 0–1372 °CK13 0–100 °CK14 0–300 °C |
| JThermocouple | J01 0–200 °CJ02 0–400 °CJ03 0–600 °CJ04 0–800 °CJ05 0–100 °CJ06 0–1200 °C |
| RThermocouple (accuracy not guaranteed over 0–399 °C) | R01 0–1600 °CR02 0–1769 °CR03 0–1350 °C |
| SThermocouple (accuracy not guaranteed over 0–399 °C) | S01 0–1600 °CS02 0–1769 °C |
| BThermocouple (accuracy not guaranteed over 0–399 °C) | B01 400–1800 °CB02 0–1769 °C |
| EThermocouple | E01 0–800 °CE02 0–1000 °C |
| NThermocouple | N01 1–1300 °CN02 0–1300 °C |
| TThermocouple (accuracy held from −199 to 100 °C) | T01 −199.9–400.0 °CT02 −199.9–100.0 °CT03 −199.9–200.0 °CT04 0–350.0 °C |
| PT100RTD | D01 −199.9–649.0 °CD02 −199.9–200.0 °CD03 −100–50 °CD04 −100–100 °CD05 −100–200 °CD06 0.0–50.0 °CD07 0.0–100 °CD08 0.0–200 °CD09 0.0–300 °CD10 0.0–500 °C |
| Cu50RTD | P01 −50.0–150.0 °CP02 0.0–150.0 °CP03 0.0–100.0 °CP04 −50.0–0.0 °CP05 −50.0–100.0 °CP06 −50.0–50.0 °CP07 −50–150 °CP08 0–150 °CP09 0–100 °CP10 0–50 °C |
| 0–5VDCStandard signal | 401 0.0–100.0 |
| 1–5VDCStandard signal | 601 0.0–100.0 |
| 0–20mAStandard signal, 250 Ω resistor across the terminals | 701 0.0–100.0 |
| 4–20mAStandard signal, 250 Ω resistor across the terminals | 801 0.0–100.0 |
Linear inputs scale over 0.0–100.0 in engineering units; 0–20 mA and 4–20 mA require a 250 Ω shunt resistor across the terminals.
Alarm type codes
The alarm position in the model code is a letter, not a number. These are the twelve codes the REX, CH and XMT families accept, in the order the factory sheets print them, so a code read off one sheet means the same thing on the next.
| Code | Alarm type |
|---|---|
| N | No alarm |
| A | Deviation high (upper) |
| B | Deviation low (lower) |
| C | Deviation high and low |
| D | Band (deviation range) |
| E | Deviation high, hold action |
| F | Deviation low, hold action |
| G | Deviation high and low, hold action |
| H | Process high (absolute) |
| J | Process low (absolute) |
| K | Process high, hold action |
| L | Process low, hold action |
Codes E, F and G behave like A, B and C but stay latched after the condition clears, until the operator resets the instrument. K and L do the same for the absolute limits.
Codes H, J, K and L compare against an absolute temperature instead of an offset from the set point.
XMT-8000 series wiring
The XMT-8000 bodies carry a different block from the 8411 sheet above: it is numbered from 1, in ten or sixteen terminals. Six panels cover the XMTG-8411 and XMTG-8511 (ten terminals) and the XMTE-8411 and XMTA-8411 (sixteen), on a contactor, on a solid state relay and on an alarm light, with the terminal reference for each.
Read the block on your instrument before wiring: this sheet numbers it 1–10 or 1–16, while the drawing above this one numbers it 13–24. The same physical terminal is not the same number in both.
XMT-8000 series · six panels with terminal references
One page per order code
Every code this family ships, with the bezel, the output stage and the terminals that output uses.
Documents for this family
- XMT-8000 series wiring308 KB · 2026-11-18
Supply & OEM
- Stock / sample dispatch
- Typically 3–5 working days for available stock models after stock and order confirmation
- Warranty
- 3 years
- OEM
- Selected models; confirm by quotation
- Shipping
- Worldwide export
Related guides
PID Controller Selection: Cutouts, Ten Input Types and the 3 A Relay Trap
Most panel PID controller problems are specification problems, not control problems. This guide compares the four 8411 series fronts by cutout, explains the ten input types behind…
Read guide Technical Guides · 2026-08-27How to Wire CH102, CH402, CH702 and CH902 PID Temperature Controllers
A practical wiring guide for CH102, CH402, CH702 and CH902 PID temperature controllers, covering power, AC contactor and SSR control, thermocouple and Pt100 sensors, alarms and…
Read guide Technical Guides · 2026-08-23How to Wire REX-C100, REX-C700 and REX-C400/C900 Temperature Controllers
English wiring diagrams for REX-series temperature controllers, including relay, AC contactor, SSR, K-type thermocouple and 3-wire PT100 connections.
Read guideRelated models
All Temperature Controllers
XMT M / MS Single-Display Controller — 48×48 to 96×96mm
SE-XMT-MS
One big display and three keys. The measurement fills the front, the mode key steps between the alarm limit and the output limit, and a lamp beside…
View details
6311 Series Digital Temperature Controllers (XMTG / XMTE / XMTD / XMTA fronts)
SE-XMT-6311
The XMT-6311 is the four-bezel member of the XMT-6000 family, and the only one here that reaches the large strip format. One body is built as…
View details
XMT-1000 Series Digital Temperature Controller
SE-XMT-1000
The measured value on the display, the setpoint on a three-digit thumbwheel switch underneath. No menu, no key sequence: whoever is standing at the…
View details
XMTD Series Digital Temperature Controller
SE-XMTD
The XMTD-2001 and XMTD-2201 are 72×72 mm panel-mount On/Off temperature controllers built for straightforward, menu-free operation. Operators set the…
View detailsNeed help selecting the right model?
Send us the load, voltage, sensor type and output signal. We reply with the matching model, wiring notes and an OEM quotation.